Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction

Regulation 500. Uptakes of vertical boilers

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 796Formula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

500. Uptakes of vertical boilers.─ (1) The maximum allowable working pressure for uptake tubes of vertical boilers shall be determined by the following formula:

(i)When an internal liner is not fitted:

𝑃 = 7.03070 (32 𝑡−50.8) Equation (12/34)

𝐷

(ii)When an internal liner is fitted extending below the low water level:

𝑃 = 50.97255 (32 𝑡−25.4)2 Equation (12/35)

𝐷(𝐿+609.6)

Where,

P is maximum allowable working pressure in kg/cm2 (g)
t is thickness of the uptake in mm.
D is external diameter in mm.
L is length of the uptake in mm, measured between the circumferential seams.

(2)In no case, the thickness of an uptake tube shall be less than 10 mm.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 500 sets the maximum allowable working pressure for uptake tubes of vertical boilers, with one formula for uptakes without a liner and another for uptakes with a liner. No uptake tube may be thinner than 10 mm.

Key points

  • (1)(i) No internal liner: Equation (12/34), with the constant 7.03070.
  • (1)(ii) Internal liner extending below the low water level: Equation (12/35), with the constant 50.97255.
  • Symbols: P in kg/cm² (g); t, uptake thickness (mm); D, external diameter (mm); L, uptake length between the circumferential seams (mm).
  • (2) Minimum thickness: 10 mm.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
574Stayed flat surfaces (other than crowns of Vertical boilers)83%Chapter XII (DPIIT scan), image 6
594Corrugated Fireboxes of Vertical Boilers83%Chapter XII (DPIIT scan), image 14
595Hemispherical Furnacesof Vertical Boilers74%Chapter XII (DPIIT scan), image 14

Amendment history of the candidate IBR 1950 regulations: Reg. 574 (1 amendment)

IBR 1950 regulation 574 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 574 page for its amendments.

Reg. 572, Reg. 573, Reg. 574

Raised manhole frames, cover plates and joint bolts

Raised circular manhole frames not exceeding 16 inches in diameter shall not be less than ¾ inch thick in all parts.

The circular cover plates and joint flanges for such frames shall be not less than-

1 inch thick for pressures not exceeding 120 pounds per square inch.

1- 1/8 inches thick for pressures exceeding 120 pounds per square inch but not exceeding 200 pounds per square inch.

1 ¼ inches thick for pressure exceeding 200 pounds but not exceeding 250 pounds per square inch.

For pressure exceeding 250 pounds per square inch, raised circular manhole frames shall not be fitted.

The cover plates shall be secured by at least sixteen steel bolts not less than 1 inch diameter, such that the stress in the bolts due to steam pressure shall not exceed:-
5,000 pounds per square inch for 1 inch bolts.
6,000 pounds per square inch for 1- 1/8 inches bolts.
6,500 pounds per square inch for 1 ¼ inches bolts.

For the purpose of calculation the pressure shall be assumed to act on the whole area within the pitch circle of the bolts and the bolt area at the bottom of the screw thread shall be taken.



Reg. 573

Stand Pipes and branches-
a) The thickness and bolting of all flanges for joining the mountings  and fittings shall be in accordance with the dimensions as laid down in Appendix- E to these regulations. In no case, however, shall the thickness of flanges be less than 13 mm.
b)
(i) The Wall thickness of nozzles and other connections shall not be less than that specified for the applicable loading, namely, internal pressure, bending and static loads.
(ii) The pressure loading shall be determined by regulation 564, but in no case shall the thickness be less than that calculated by the following formula:-

t = 0.04D + 2.5 mm (equation XII/10)

where, t is the thickness of standpipe and D is the outside diameter of connection. If the branch is connected by screwing, the thickness ‘t’ shall be measured at the root of the thread.
c) Where a double flanged steam pipe is tapered, the thickness of flange joining the boiler and fitting shall correspond to the bore of pipe at the flange connection in accordance with Appendix-E to these regulations.


Reg. 574

Stayed Flat surfaces (other than Crowns of Vertical Boilers).

Stayed heads/ Braced and stayed surfaces.

For various braced and stayed flat plates and those which by these regulations require staying as flat surfaces with braces or stay bolts of uniform diameter symmetrically spaced, the thickness should be calculate by the following formula; namely:-

                                             __________
                        e  =  Cd      Ö P        +   e1
Ö   f1

Where,

P=design pressure in kgf/cm²
e=thickness, in mm.
d=diameter of the largest circle taken between staying points of the plate (in mm)
f1=0.85 f (f as defined in regulation 271), kfg/cm²
e1=additional thickness equal to 0.75 mm (0.03 in)
C=coefficient having the following values:-

1) C=0.33 for flanged connections;

NOTE:
d is the diameter of the largest circle taken from the commencement of the curvature of the flange.
2) C=0.40 for stays screwed in plate with nut or screwed and welded, or plain end strength welded on the outside;
3) C=0.33 for screwed bar stays with washer of not less than 3.5 times the diameter of bar stay;
4) C=0.31 for screwed bar stays with reinforcing plate, washer and nut on the outside.

NOTES:
1. If the plate is stayed in any other way, average values of C shall be taken into account.

2. If the plate is flame swept, the thickness shall be increased by 10%.

3. The welding materials used in the manufacture of these plates shall not have the ultimate tensile strength less than that of the plate used.
IBR 1950 regulation 594 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 594 page for its amendments.

Reg. 593, Reg. 594, Reg. 595

Plain Furnaces of Vertical Boilers

The maximum working pressure of Plain Furnaces of Vertical boilers shall be the lesser of the two values obtained by Equations XII/25 and XII/26.

Where,

D = external diameter of the firebox in inches. Where the firebox is tapered the diameter taken shall be the mean of that at the top and at the bottom where it meets the substantial support from the flange or ring.

L is length of the firebox in inches between points of substantial support measured from the commencement of flange curvature or from the foundation connection, or from a row of screwed stays which comply with Regulations 550(b), 585(b), whichever is applicable.

In no case, however, shall the thickness be more than 7/8 inch. For fireboxes under 2 feet and 6 inches in diameter, the thickness shall be not less than 5/16 inch and for fireboxes 2 feet and 6 inches in diameter and over the thickness shall be not less than 3/8 inch.


Reg. 594

Corrugated Fireboxes of Vertical Boilers

For the semi-spirally corrugated fireboxes of ‘Sentinel’ standard motor wagon boilers the working pressure shall be determined by the following formula-

W.P. = C(t-1) Equation XII/29
D

W.P. is working pressure in pounds per square inch.
t is thickness of the firebox plate in thirty seconds of an inch.
D is mean of the external diameters of firebox measured over the plain part at each end at commencement of curvature of flange.
C = 390.

No corrugated furnace shall be less than 3/8 inch thick.
 

Reg. 595

Hemispherical Furnaces of Vertical Boilers

When furnaces are hemispherical in form and subject to pressure on the convex side and are without support from stays of any kind the maximum working pressure shall be found by the following formula:-

W.P. = 275(t-1) Equation XII/30
R

W.P. is working pressure in pounds per square inch.
t is thickness of the top plate in thirty seconds of an inch.
R is outer radius of curvature of the furnace in inches.
The thickness of these furnaces shall in no case exceed 7/8 inch
IBR 1950 regulation 595 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 595 page for its amendments.

Reg. 593, Reg. 594, Reg. 595

Plain Furnaces of Vertical Boilers

The maximum working pressure of Plain Furnaces of Vertical boilers shall be the lesser of the two values obtained by Equations XII/25 and XII/26.

Where,

D = external diameter of the firebox in inches. Where the firebox is tapered the diameter taken shall be the mean of that at the top and at the bottom where it meets the substantial support from the flange or ring.

L is length of the firebox in inches between points of substantial support measured from the commencement of flange curvature or from the foundation connection, or from a row of screwed stays which comply with Regulations 550(b), 585(b), whichever is applicable.

In no case, however, shall the thickness be more than 7/8 inch. For fireboxes under 2 feet and 6 inches in diameter, the thickness shall be not less than 5/16 inch and for fireboxes 2 feet and 6 inches in diameter and over the thickness shall be not less than 3/8 inch.


Reg. 594

Corrugated Fireboxes of Vertical Boilers

For the semi-spirally corrugated fireboxes of ‘Sentinel’ standard motor wagon boilers the working pressure shall be determined by the following formula-

W.P. = C(t-1) Equation XII/29
D

W.P. is working pressure in pounds per square inch.
t is thickness of the firebox plate in thirty seconds of an inch.
D is mean of the external diameters of firebox measured over the plain part at each end at commencement of curvature of flange.
C = 390.

No corrugated furnace shall be less than 3/8 inch thick.
 

Reg. 595

Hemispherical Furnaces of Vertical Boilers

When furnaces are hemispherical in form and subject to pressure on the convex side and are without support from stays of any kind the maximum working pressure shall be found by the following formula:-

W.P. = 275(t-1) Equation XII/30
R

W.P. is working pressure in pounds per square inch.
t is thickness of the top plate in thirty seconds of an inch.
R is outer radius of curvature of the furnace in inches.
The thickness of these furnaces shall in no case exceed 7/8 inch

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
796
PDF page index
796 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 35473e63734718fb
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 500, Regulation 500, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.796. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.