In short
Manholes and other openings in the shells of boilers under this chapter must meet regulation 139, which covers their position relative to seams and the orientation and proportions of the openings.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
IBR 1950 regulation 427 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 427 page for its amendments.
Reg. 427, Reg. 428, Reg. 429, Reg. 430 TESTS FOR CLASS II FUSION WELDED SEAMS
Manholes and other openings in Shells
Manholes and other openings in boiler shells shall be placed away from any welded seam. Oval openings shall be arranged with their minor axis parallel to the longitudinal centre line of the boiler.
(a)
Un-compensated openings shall comply with Regulation 187.
(b)
Compensated openings shall comply with Regulations 170, 171, 186 and 279.
Reg. 428 TESTS FOR CLASS II FUSION WELDED SEAMS
Dished End Plates with pressure on Concave side
This shall comply with Regulation 408.
Reg. 429 TESTS FOR CLASS II FUSION WELDED SEAMS
Unstayed Flat End Plates
The working pressure of unstayed flat end plates shall comply with Regulation 412.
Where the diameter of the openings in an unstayed flat end plate is greater than 2½ inches or the pitch in inches is less than four times the diameter of the holes full compensation shall be provided as in Regulation 279.
Reg. 430 TESTS FOR CLASS II FUSION WELDED SEAMS
Thickness of Angle Rings
Thickness of angle rings shall comply with Regulation 379(a).
IBR 1950 regulation 564 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 564 page for its amendments.
Reg. 563, Reg. 564
Classification of Fusion-Welded Boilers
The boilers covered by this Chapter shall be classified in accordance with Table XII/3.
TABLE XII/3
Classification of Fusion-Welded Boilers
Classification
Limits of application
Minimum thickness
Class I
No. limit
¼ inch.
Class II
When the following limits are not exceed:
(a) Working pressure105 pounds per sq. in. (b) Working pressure in pounds per sq. in. multiplied by internal diameter in inches = 5250
Boilers up to and including 36 inches internal diameter-5/16 inch.
Class III
When the following limits are not exceeded:
(a) Working presure 30 lbs. per sq. in. (b) Working pressure multiplied by internal diameter in inches = 3000.
Boiler over 36 inches internal diameter-3/8 inch.
Reg. 564
Shells
a)
The working pressure of cylindrical shells for class I boilers shall be determined in accordance with regulations 270 and 271.
b)
The working pressure of cylindrical shells for Class II and Class III boilers shall be determined by the following formula:-
WP =
(t – 1.5)SC
Equation XII/1
0.7 D
Where,
t is minimum thickness of shell plate in mm. WP is working pressure in kg/cm². D is maximum internal diameter in mm. S is minimum tensile strength of plate in kg/mm². C is a constant, as given below.
In no case, however, shall the factor of safety of the shell be less than 4 or the plate thickness be less than specified in Table XII/3 given under Regulation 563.
C=27 where Class II requirements are complied with. C=23 for Class III boilers when stress relieved. C=21 for Class III boilers when not stress relieved.
Where boilers have a nest or nests of horizontal tubes, so that there is a direct tension on the tube plates due to the vertical load on the boiler ends or to tube plates acting as horizontal ties across the shell:
i)
each alternate tube in the outer vertical row of tubes shall be a stay tube.
ii)
The thickness of tube plates and the spacing of the tubes shall be such that the section of metal taking the load is sufficient to keep the stress within that allowed on the shell plate, as determined by the following formula:-
WP =
(t – 2) SJ
Equation XII/2
2D
Where,
t is the thickness of the tube plate in mm. WP is the working pressure in kg/cm². S is the minimum tensile strength in kg/mm². D is twice the radial distance of the centre of the outer row of tube holes from the axis of the shell in mm. J is the percentage strength of the plate through the tube holes,
i.e. =
100 (P-D)
Eqn. XII/3
P
P is the vertical pitch of tubes in mm. D is the diameter of the tube holes in mm.
NOTE:- The tube plates between the stay tubes shall comply with the requirements for tubes plates (Regulation 577).
IBR 1950 regulation 297 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 297 page for its amendments.
Reg. 297, Reg. 298, Reg. 299
Opening in Shell
No accessories other than those integral with the Safety Valve shall obstruct the openings in the boiler shell. Discharging steam shall have direct access to the safety valve without flowing through internal pipes.
Reg. 298
Discharge Passage
The safety valve discharge pipes shall comply with the requirements of clauses (a) and (b) of this regulation. The discharge pipe shall be as short and straight as possible and be fitted with open drain to prevent accumulation water in the pipe. Suitable arrangement shall be provided in the discharge pipe system so that the discharge can readily be heard by the Boiler Attendant.
a)
Steam safety valves: -
(i)
Ordinary and high lift valves. Where a waste steam-pipe is fitted the pipe and the passage leading to it shall have a cross-sectional area not less than the minimum combined area of the safety valves required by Regulation 293.
(ii)
Full lift valves. For full lift valves the area of waste steam-pipe and passages leading to it shall have a cross-sectional area not less than twice A, or such area above this minimum as may be required for valves having a higher approved constant, where A,E and P are as defined in regulation 293.
b)
Economiser safety valves. The area of the discharge pipe from an economiser safety valve shall be at least twice the area of the valve seating. Where the discharge from several economiser safety valves is connected to the main discharge pipe, the diameter of the main discharge pipe shall be designed to prevent accumulation of pressure due to the formation of steam under the particular conditions of temperature and pressure which may be applicable.
Reg. 299
Drainage
For each enclosed safety valve chest a means of draining shall be provided. The drain pipe shall be laid with a continuous downward gradient clear of the boiler to a place where the discharge is visible and cannot do injury to any person.
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.
pdftotext layout mode, sequential regulation detector · text hash 116aeffd983e1a5b
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite
Indian Boiler Regulations, 2026, reg. 462, Regulation 462, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.775–776. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).