Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 497. Hemispherical furnaces of vertical boilers
Not yet checked against the official Gazette; verify before relying on it.
497.Hemispherical furnaces of vertical boilers.─ (1) When furnaces are hemispherical in form and subject to pressure on the convex side and are without support from stays of any kind, the maximum allowable working pressure shall be found by the following formula:
𝑃 = 19.33441 (32 𝑡−25.4) Equation (12/31)
𝑅 where
P is maximum allowable working pressure in kg/cm2 (g)
t is thickness of the top plate in mm.
R is outer radius of curvature of the furnace in mm.
(2)The thickness of these furnaces shall in no case exceed 22 mm.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 497 covers hemispherical furnaces of vertical boilers that take pressure on the convex side and have no stays of any kind.
Key points
- (1) Maximum allowable working pressure P (kg/cm² (g)) comes from Equation (12/31), which uses the constant 19.33441, the top plate thickness t (mm) and the outer radius of curvature R (mm).
- (2) The thickness of these furnaces must never exceed 22 mm.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 595 | Hemispherical Furnacesof Vertical Boilers | 99% | Chapter XII (DPIIT scan), image 14 |
| 122 | Furnaces of Horizontal Boilers | 78% | Chapter III (DPIIT scan), image 3 |
| 596 | Foundations of Vertical Boiler Furnaces | 74% | Chapter XII (DPIIT scan), image 14 |
IBR 1950 regulation 595 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 595 page for its amendments.
| Reg. 593, Reg. 594, Reg. 595 | |||||||||||||||
Reg. 594 Corrugated Fireboxes of Vertical Boilers
Reg. 595
| |||||||||||||||
IBR 1950 regulation 122 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 122 page for its amendments.
| Reg. 122 FURNACES Furnaces of Horizontal boilers
|
IBR 1950 regulation 596 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 596 page for its amendments.
| Reg. 596, Reg. 597 | ||||||||||||||||||
Reg. 597 Foundations of Loco-type Boiler Fireboxes
| ||||||||||||||||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 497, Regulation 497, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.794–795. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.