406. End plates, crown plates and tube plates.─ (1) End plate of welded Lancashire and Cornish boilers shall be flanged for attachment to shell plates.

(2)For requirements of end plates of boilers, sub-regulation (1) of regulation 86 shall apply.

(3)For requirements of hemispherical crowns, regulation 89 shall apply.

(4)For requirements of flanging, sub-regulation (2) of regulation 86 shall apply.

(5)In the construction of unfired boilers when the dished ends do not form a part of the heating surface, cold spun dished ends conforming to IS: 2825 may be used.

(6)Where flats are pressed in dished end plates, for the attachment of mountings they shall be formed with an ample radius at the junction of the flat and curved surfaces, and shall be free from sharp corners or tool marks. The plate shall not be unduly thinned.

(7)(a) Plates which are flanged in accordance with sub-regulation (4), shall be welded to the parts to which they are to be connected as follows:

(i)to shells or cylindrical fireboxes as shown in Figures 12/7, 12/8, 12/9, 12/10 or 12/11.

(ii)to internal flue tubes as shown in Figures 12/14, 12/15 or 12/16.

(iii)to uptake as shown in Figure 12/16.

(iv)to combustion chamber or firebox wrapper plates as shown in Figure 12/19.

(b)Plates which are not flanged shall be welded to the parts to which they are to be connected as follows:

(i)to shells as shown in Figure 12/12 or 12/13.

(ii)to internal flue tubes or uptakes as shown in Figure 12/17.

(iii)to combustion chamber or firebox wrapper plates as shown in Figures 12/20, 12/21 or 12/22.

(c)Where dished ends or crowns are used, they shall be flanged for connection to the shell or the cylindrical portion of the firebox. Flat shell and firebox crown plates of vertical boilers shall also be flanged for connection to the cylindrical portions of the shell or firebox.

(d)The opening in the firebox crown plate of a vertical boiler for the uptake shall be flanged and the connection to the uptake made by means of a circumferential butt-weld. (see Figures 12/3, 12/4, 12/5, 12/6).

Referenced provisions

Reg. 86 · Reg. 89

Figures cited in this regulation (19, exact crops of the Gazette)

Gazette Fig. 12/3
Fig. 12/3(no caption printed with this figure)
View Gazette page 798 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/4
Fig. 12/4(no caption printed with this figure)
View Gazette page 798 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/5
Fig. 12/5(no caption printed with this figure)
View Gazette page 798 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/6
Fig. 12/6(no caption printed with this figure)
View Gazette page 798 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/7
Fig. 12/7(no caption printed with this figure)
View Gazette page 799 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/8: Flanged End Plates Ends Thicker Than Shell
Fig. 12/8Flanged End Plates Ends Thicker Than Shell
View Gazette page 799 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/9: Flanged End Plates Ends Thicker Than Shell
Fig. 12/9Flanged End Plates Ends Thicker Than Shell
View Gazette page 799 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/10: Flanged Flat End Plates
Fig. 12/10Flanged Flat End Plates
View Gazette page 799 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/11: Flanged Flat End Plates to Shell (Shell Thicker than Ends)
Fig. 12/11Flanged Flat End Plates to Shell (Shell Thicker than Ends)
View Gazette page 799 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/12: Flat End
Fig. 12/12Flat End
View Gazette page 799 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/13
Fig. 12/13(no caption printed with this figure)
View Gazette page 800 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/14: Attachment of Flues to End Plates – Dished or Flat
Fig. 12/14Attachment of Flues to End Plates – Dished or Flat
View Gazette page 800 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/15
Fig. 12/15(no caption printed with this figure)
View Gazette page 800 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/16: Flue Connections to End Plates (Dished or Flat)
Fig. 12/16Flue Connections to End Plates (Dished or Flat)
View Gazette page 800 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/17: Flue Connections to End Plates (Dished or Flat)
Fig. 12/17Flue Connections to End Plates (Dished or Flat)
View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/19
Fig. 12/19(no caption printed with this figure)
View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/20
Fig. 12/20(no caption printed with this figure)
View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/21
Fig. 12/21(no caption printed with this figure)
View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/22
Fig. 12/22(no caption printed with this figure)
View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 406 covers end plates, crown plates and tube plates of welded boilers, and how they are welded to the parts they join.

Key points

  • (1) End plates of welded Lancashire and Cornish boilers must be flanged for attachment to the shell plates.
  • (2) End plates follow sub-regulation (1) of regulation 86; (4) flanging follows sub-regulation (2) of that regulation.
  • (3) Hemispherical crowns follow regulation 89.
  • (5) In unfired boilers, where dished ends are not part of the heating surface, cold spun dished ends conforming to IS: 2825 may be used.
  • (6) Flats pressed in dished ends for mountings need an ample radius where flat meets curve, no sharp corners or tool marks, and no undue thinning.
  • (7)(a) Flanged plates are welded to shells, fireboxes, flue tubes, uptakes or combustion chamber and firebox wrapper plates as shown in the listed figures.
  • (7)(b) Unflanged plates are welded to shells, flue tubes, uptakes or wrapper plates as shown in the listed figures.
  • (7)(c) Dished ends or crowns are flanged for connection to the shell or cylindrical firebox. Flat shell and firebox crown plates of vertical boilers are also flanged.
  • (7)(d) The uptake opening in a vertical boiler's firebox crown plate is flanged and joined to the uptake by a circumferential butt-weld.

Watch out

  • Each joint type has its own permitted figures. Check the Official text tab and the Gazette figures for the one that applies.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
33Plates100%Chapter II (DPIIT scan), image 3
118Tube Plates100%Chapter III (DPIIT scan), image 2
634Tube plates100%Chapter XV (DPIIT scan), image 3
IBR 1950 regulation 33 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 33 page for its amendments.

Reg. 33
MATERIALS OF CONSTRUCTION

COPPER PLATES, STAY AND RIVET BARS

Plates

(a) Process.- The copper shall be fire-refined or electrolytic and hot-rolled from suitable cakes.

(b) Chemical Composition.- The chemical composition of the plates shall be as follows:-

Per cent.
Copper 99.2 minimum
Arsenic .30 to .50
Antimony 0.05 maximum
Bismuth 0.05 maximum
Oxygen 0.10 maximum

(c) Freedom from defects.- The plates shall be clean, smooth and free from defects and shall have a workmanlike finish. They shall be thoroughly annealed.

(d) Rolling Margin.- No plate shall be under the specified thickness at any part, not more than 5% over the calculated weight. The scrap margin, partly sheared and left attached, shall be not less than 3 inches at the ends and 1½ inches at each side.

(e) Tensile Tests.- One tensile test shall be taken from each plate as rolled.

The tensile breaking strength, from Standard Test Piece A, shall not be less than 14 tons per sq. inch with an elongation of not less than 35%.

(f) Hot and Cold Bend tests.- One hot (temperature between 1200°F and 1400°F) and one cold bend test shall be taken from each plate as rolled.

For either hot or cold bend tests, the test piece shall withstand being doubled over without fracture until the sides are touching and parallel.

IBR 1950 regulation 118 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 118 page for its amendments.

Reg. 118, Reg. 119, Reg. 120
END PLATES

 

Tube Plates

Smoke-box tube plates shall be flanged for attachment to the barrel or shall be flat and connected thereto by an external riveted angle ring.

Reg. 119
END PLATES

 

Parts of flat tube plates within the tube nests

a) where the total area of all tube nests in directly fired multi-tubular boilers exceeds 7 sq. ft., stay tubes shall be fitted.

Where the total number of tubes in horizontal multitubular waste heat boilers and direct fired loco type boilers is arranged in one next, the area of which exceed 21 sq. ft., stay tubes shall be fitted.

In all cases where the total number of tubes is arranged in more than one nest, stay tubes shall be fitted.
b) The parts of tube plates which lie outside the nests of tubes shall be stayed or supported wherever the size of the area of plate subject to steam pressure necessitates staying or support, either by marginal stay tubes or other means.


Reg. 120
END PLATES
Flanging of End Plates

All flanges shall be a good fit to the shell and flues. Flogging and/or hammering in the fitting of these parts is prohibited. The caulking edges of all flanged plates shall be machined or machine gas cut.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
757–758
PDF page index
757–758 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash a860091b3f8e3087
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 406, Regulation 406, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.757–758. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.