Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 419. Access
Not yet checked against the official Gazette; verify before relying on it.
419. Access.─ (1) The requirements specified in sub-regulations (1), (2),(3) and (4) of regulation 135 shall apply in addition to the requirements given in sub-regulations (2), (3) and (4).
(2)At the bottom of the narrow water space in vertical boilers where internal access is not possible, mud holes shall be arranged at equal distances round the circumference of the boiler not less in number than as given in
Table 12/2.
TABLE 12/2: Number of lower cleaning holes or mud holes
| Serial number | Diameter of boiler | No. of Holes |
|---|---|---|
| (1) | (2) | (3) |
| 1 | 610 mm and over but not exceeding 915 mm | 3 |
| 2 | Over 915 mm and not exceeding 1525 mm | 4 |
| 3 | Over 1525 mm and not exceeding 1830 mm | 5 |
| 4 | Over 1830 mm and not exceeding 2290 mm | 6 |
| 5 | Over 2290 mm and not exceeding 2590 mm | 7 |
| 6 | Over 2590 mm and not exceeding 2745 mm | 8 |
Table structure read from the Gazette PDF, page 762. Verification status as for the text above.
Show original extracted text (diagnostic, not authoritative)
Serial Diameter of boiler No. of Holes
number
(2) (3)
(1) 610 mm and over but not exceeding 915 mm 3
1 Over 915 mm and not exceeding 1525 mm 4
2 Over 1525 mm and not exceeding 1830 mm 5
3 Over 1830 mm and not exceeding 2290 mm 6
4 Over 2290 mm and not exceeding 2590 mm 7
5 Over 2590 mm and not exceeding 2745 mm 8
6(3)Cleaning holes or mud holes in loco-type boilers shall be provided at each bottom corner or as nearly as possible in the corners of the outer firebox casing and at the top corners above fire hole opening and also at each corner of the saddle plate in line with the bottom of barrel Smoke box tube shall be provided with a mud hole.
(4)A manhole shall be provided in the lower part of front end plates of Lancashire boilers and in similar boilers with internal flues wherever practicable.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 419 sets access and cleaning openings for welded boilers. Sub-regulations (1) to (4) of regulation 135 apply as well as sub-regulations (2) to (4) here.
Key points
- (2) In vertical boilers where the narrow water space at the bottom cannot be reached internally, mud holes are spaced equally round the circumference. Table 12/2 sets the minimum number by boiler diameter, from 3 holes for 610 mm and over but not exceeding 915 mm, up to 8 holes for over 2590 mm and not exceeding 2745 mm.
- (3) In loco-type boilers, cleaning or mud holes go at each bottom corner of the outer firebox casing (or as near as possible), at the top corners above the fire hole opening, and at each corner of the saddle plate in line with the bottom of the barrel. The smoke box tube needs a mud hole (as printed; this is presumably the smoke box tube plate).
- (4) Lancashire boilers, and similar boilers with internal flues, need a manhole in the lower part of the front end plate wherever practicable.
Watch out
- See the Official text tab for the full Table 12/2.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
No candidate heading found in the historical print edition.
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 419, Regulation 419, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.762. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.