BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction

Regulation 486. Gusset Link, brace and similar stays

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 789–790TableFigure referenced

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

486. Gusset Link, brace and similar stays.─ (1) For welded Lancashire, Cornish and Cylindrical Horizontal Multi-tubular type boilers, all welded gussets stays shall not be used. To ensure flexibility, link stays, bar stays, brace stays other than the all-welded type shall be used. All welded gusset stays, however, may be used in cylindrical horizontal waste heat and cylindrical vertical multi-tubular boilers.

(2)Welded gusset stays and brace may be used for welded Lancashire Cornish and Cylindrical Horizontal Multi-tubular type boilers provided their method of attachment is approved by the inspecting Authority.

(3)Each gusset or link stay supporting the flat end plate of a boiler shall be designed to carry the whole load due to pressure on the area it supports. The areas supported by any one stay shall be obtained by considering the total area to be supported which lies within the limits of the flat plate margins and dividing this area by boundary lines drawn between the stays. These boundary lines shall be at all points equidistant from the adjacent points of support in the area under consideration. The effective uniformly distributed load on a triangular gusset plate or on a diagonal link stay shall be assumed to be equal to the perpendicular load on the portion of the end plate to be supported (determined as above) multiplied by L/L1 (see Figures 12/101, 12/102 and 12/103).

(4)(a)Gusset plates shall be so proportioned that the angle "V" (see Figures 12/101 and 12/102), is not less than 60°.
The thickness of the gusset plate shall be such that the stress in the plate to withstand the effective uniformly

(b)distributed load (as defined above) calculated on the smallest cross-section on line XX or YY (Figure 12/101 and 12/102), shall not exceed one-seventh of the minimum tensile stress of the plate used but in no case shall

(c)the thickness be less than seven-eighths of the thickness of the shell, plate with a minimum of 11 mm. Where all-welded gusset stays are used a stiffening plate shall be welded at the toe of the gusset where it is secured to the end plate i.e. where the maximum stress occurs, (see Figure 12/101).

(5)Link stays shall be so arranged that the angle "V" (figure 12/103) is not less than 600 and the dimensions shall be such that stress in the stay at its weakest part does not exceed one-seventh of the minimum tensile stress of the plate used.

(6)The strength of anchor plates, angles and link pins calculated at the weakest section shall be as follows:

(a)Link pins shall be so designed that the shear stress does not exceed 562 kg/cm2, the strength of pins in double shear being taken as 1.875 times the strength of pins in single shear.

(b)Anchor plates or angles shall be so designed that the calculated stress does not exceed one-seventh of the minimum tensile stress of the material used, but in no case shall the thickness be less than seven-eighth of the thickness of the shell plate with a minimum of 12.7 mm, nor the length of the portion attached to the end plate be less than the distance between the lines of end to shell flat margin and the breathing space line around the flues of tube nests.

(7)(a)Where gusset plates, anchor plates or angles are welded to the shell and/ or end plates, the attachments shall be by mean of continuous fillet welds on each side or by butt-welds prepared in accordance with following paragraph and details l, m, n, or p of Appendix –J.

(b)The welds shall be of such dimension that the stress calculated on an area equal to the effective length of the weld multiplied by the effective throat thickness shall not exceed that permitted for the parent metal multiplied by the appropriate weld factor in Table 12/13.

(c)The effective length of a weld shall be taken as that length of weld which is of the specified size throughout.

(d)For open-ended fillet welds the effective length shall be the overall length less twice the weld size.

(e)For the purpose of stress calculation, the effective throat thickness of a butt weld shall be taken as the thickness of the gusset or another plate and the effective throat thickness of fillet weld shall be taken as 0.7 of the fillet size. For compound welds the effective thickness shall be the sum of those of the constituent parts.

Table 12/13: Weld attachments

Form of weldWeld factor
Not stress relievedStress-relieved
(1)(2)(3)
Single J or bevel butt-welds
(with or without superimposed fillet)
Unsealed0.350.45
Sealed0.600.70
Double J or bevel butt-welds
(with or without superimposed fillets)
0.600.70
Double fillet welds0.550.65

Table structure read from the Gazette PDF, page 790. Verification status as for the text above.

Show original extracted text (diagnostic, not authoritative)
                         Form of weld                                  Weld factor

                               (1)                Not stress relieved               Stress-relieved
Single J or bevel butt-welds
(with or without superimposed fillet)             (2)                               (3)

                                        Unsealed  0.35                              0.45
                                        Sealed
                                                  0.60                              0.70

Double J or bevel butt-welds                      0.60                              0.70
(with or without superimposed fillets)
                                                  0.55                              0.65
Double fillet welds

PART-12
Furnaces, furnace components, wet-back reversal chambers and fire boxes of cylindrical form subject to external pressure

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Referenced provisions

Appendix J

Figures cited in this regulation (3, exact crops of the Gazette)

Gazette Fig. 12/101: Typical Details For All-Welded Gusset Stay
Fig. 12/101Typical Details For All-Welded Gusset Stay
View Gazette page 826 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/102: Typical Details for Welded and Pinned Gusset Stay
Fig. 12/102Typical Details for Welded and Pinned Gusset Stay
View Gazette page 826 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/103: Typical Details for Diagonal Stays (Chain Lines Indicates Stay with Multiple Links)
Fig. 12/103Typical Details for Diagonal Stays (Chain Lines Indicates Stay with Multiple Links)
View Gazette page 827 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 486 covers gusset, link, brace and similar stays for flat end plates: which types may be used, how load is shared, minimum proportions, and how welded attachments are sized.

Key points

  • (1) Welded Lancashire, Cornish and cylindrical horizontal multi-tubular boilers: all-welded gusset stays shall not be used. For flexibility, use link, bar or brace stays other than the all-welded type. All-welded gusset stays may be used in cylindrical horizontal waste heat and cylindrical vertical multi-tubular boilers.
  • (2) Welded gusset stays and braces may still be used in those three boiler types if the Inspecting Authority approves their method of attachment.
  • (3) Each stay carries the whole pressure load on the area it supports. Areas are found by dividing the area inside the flat plate margins with boundary lines equidistant from adjacent supports. The load on a triangular gusset or diagonal link stay is that load multiplied by L/L1 (Figures 12/101 to 12/103).
  • (4) Gusset plates: angle V at least 60°. Stress on the smallest section (line XX or YY) at most one-seventh of the plate's minimum tensile stress. Thickness at least seven-eighths of the shell plate thickness, with a minimum of 11 mm. All-welded gussets need a stiffening plate at the toe.
  • (5) Link stays: angle V at least 60°, and stress at the weakest part at most one-seventh of the minimum tensile stress.
  • (6)(a) Link pins: shear stress at most 562 kg/cm². Double shear strength is taken as 1.875 times single shear.
  • (6)(b) Anchor plates or angles: stress at most one-seventh of minimum tensile stress. Thickness at least seven-eighths of the shell plate, minimum 12.7 mm. The attached length must reach from the flat margin line to the breathing space line.
  • (7) Welded attachments: continuous fillet welds on each side, or butt welds per details l, m, n or p of Appendix J. Stress on effective length × effective throat must not exceed the parent metal value × the weld factor in Table 12/13.
  • For open-ended fillet welds, the effective length is the overall length less twice the weld size.
  • The effective throat is the plate thickness for butt welds and 0.7 of the fillet size for fillet welds. For compound welds, add the parts.

Watch out

  • Table 12/13 factors depend on weld form and on whether the weld is stress relieved. See the Gazette page for the values.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
140Gusset Stays100%Chapter III (DPIIT scan), image 7
IBR 1950 regulation 140 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 140 page for its amendments.

Reg. 140
GIRDER STAYS
Gusset Stays

a) Gusset plates shall be flat and perpendicular to the end plates. The gusset angles shall be fitted to bed closely to the shell end plate and gusset plates. Cranking or setting of the plates is prohibited.
b) Gusset stays, where fitted, shall comprise flat plates secured by double angles to the shell and end plate respectively, and shall be designed in accordance with the following conditions.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
789–790
PDF page index
789–790 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 26916b858e98fec7
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 486, Regulation 486, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.789–790. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.