Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 410. Furnace of vertical boilers
Not yet checked against the official Gazette; verify before relying on it.
410.Furnace of vertical boilers.─ (1) The furnaces of vertical boilers may be constructed in one or more lengthwise sections, each section being rolled from one plate to a full circle. In such cases, the component sections may be jointed circumferentially by electric butt-welding. The welding shall be stress relieved in accordance with regulation 432.
(2)In the case of vertical boilers where tube plates form part of the firebox, the tube plate portion may be constructed in two vertical sections and the welding of the vertical seams when welded shall be stress relieved.
(3)The maximum permissible variation in diameter, at any cross-section shall not exceed 6 mm for fireboxes up to 900 mm in diameter, or 10 mm for fireboxes over 900 mm in diameter, or half the thickness of the plate whichever is the greater.
(4)Circular fireboxes shall preferably be tapered. A taper of 38 mm in diameter per 300 mm of height is recommended. The water space at the bottom between the firebox and the shell shall be not less than 50 mm for boilers up to and including 760 mm in diameter and shall be not less than 63 mm for boilers over 760 mm in diameter.
(5)The method of welding shall be in accordance with regulation 432.
(6)Flats formed in the firebox for the insertion of water tubes shall have an ample radius at the junction of the flat and the curved surfaces and shall be free from sharp corners or tool marks. The plate shall not be unduly thinned.
(7)Ogee flanging whether integral with the firebox or made as separate ring shall preferably be formed in one heat by suitable machinery and shall be allowed to cool gradually to avoid internal stresses.
(8)Rings of fire holes mouthpieces or foundation rings shall be made of mild steel. ‘Z’ sections shall not be used for foundations rings.
(9)Attachment of fireboxes to cylindrical shells shall be in accordance with Figures 12/34, 12/35, 12/36 or 12/37.
(10)The method of attachment of fire holes mouthpieces shall be in accordance with Figures 12/40 or 12/41).
Figures cited in this regulation (6, exact crops of the Gazette)

View Gazette page 805 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 805 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 805 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 805 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 806 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 806 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
In short
Regulation 410 sets construction rules for the furnaces (fireboxes) of welded vertical boilers.
Key points
- (1) Furnaces may be built in one or more lengthwise sections, each rolled from one plate to a full circle and joined circumferentially by electric butt-welding, stress relieved as per regulation 432.
- (2) Where tube plates form part of the firebox, the tube plate portion may be in two vertical sections; welded vertical seams must be stress relieved.
- (3) Variation in diameter at any cross-section must not exceed 6 mm for fireboxes up to 900 mm in diameter, or 10 mm over 900 mm, or half the plate thickness, whichever is greater.
- (4) Circular fireboxes should preferably be tapered; 38 mm in diameter per 300 mm of height is recommended. The bottom water space between firebox and shell must be at least 50 mm for boilers up to and including 760 mm diameter, and at least 63 mm above that.
- (5) The welding method follows regulation 432.
- (6) Flats for water tubes need an ample radius, no sharp corners or tool marks, and no undue thinning.
- (7) Ogee flanging should preferably be formed in one heat by machinery and cooled gradually.
- (9), (10) Firebox and fire hole mouthpiece attachments follow the listed figures.
Watch out
- (8) Fire hole mouthpiece rings and foundation rings must be mild steel, and Z sections must not be used for foundation rings.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 574 | Stayed flat surfaces (other than crowns of Vertical boilers) | 83% | Chapter XII (DPIIT scan), image 6 |
| 594 | Corrugated Fireboxes of Vertical Boilers | 83% | Chapter XII (DPIIT scan), image 14 |
| 596 | Foundations of Vertical Boiler Furnaces | 82% | Chapter XII (DPIIT scan), image 14 |
Amendment history of the candidate IBR 1950 regulations: Reg. 574 (1 amendment)
IBR 1950 regulation 574 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 574 page for its amendments.
| Reg. 572, Reg. 573, Reg. 574 | |||||||||||||||||||||||||
Reg. 573 Stand Pipes and branches-
Reg. 574 Stayed Flat surfaces (other than Crowns of Vertical Boilers). Stayed heads/ Braced and stayed surfaces.
| |||||||||||||||||||||||||
IBR 1950 regulation 594 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 594 page for its amendments.
| Reg. 593, Reg. 594, Reg. 595 | |||||||||||||||
Reg. 594 Corrugated Fireboxes of Vertical Boilers
Reg. 595
| |||||||||||||||
IBR 1950 regulation 596 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 596 page for its amendments.
| Reg. 596, Reg. 597 | ||||||||||||||||||
Reg. 597 Foundations of Loco-type Boiler Fireboxes
| ||||||||||||||||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 410, Regulation 410, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.759–760. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.