Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 574 — Stayed Flat surfaces (other than Crowns of Vertical Boilers).
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 572, 573. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 572, Reg. 573, Reg. 574 | |||||||||||||||||||||||||
Reg. 573 Stand Pipes and branches-
Reg. 574 Stayed Flat surfaces (other than Crowns of Vertical Boilers). Stayed heads/ Braced and stayed surfaces.
| |||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Stayed Flat surfaces (other than Crowns of Vertical Boilers).
Stayed heads/ Braced and stayed surfaces.
For various braced and stayed flat plates and those which by these regulations require staying as flat surfaces with braces or stay bolts of uniform diameter symmetrically spaced, the thickness should be calculate by the following formula; namely:-
__________
e = Cd √ P + e1
√ f1
Where,
P=design pressure in kgf/cm²
e=thickness, in mm.
d=diameter of the largest circle taken between staying points of the plate (in mm)
f1=0.85 f (f as defined in regulation 271), kfg/cm²
e1=additional thickness equal to 0.75 mm (0.03 in)
C=coefficient having the following values:-
1)C=0.33 for flanged connections;
NOTE: d is the diameter of the largest circle taken from the commencement of the curvature of the flange.
2)C=0.40 for stays screwed in plate with nut or screwed and welded, or plain end strength welded on the outside;
3)C=0.33 for screwed bar stays with washer of not less than 3.5 times the diameter of bar stay;
4)C=0.31 for screwed bar stays with reinforcing plate, washer and nut on the outside.
NOTES:
1.If the plate is stayed in any other way, average values of C shall be taken into account.
2.If the plate is flame swept, the thickness shall be increased by 10%.
3.The welding materials used in the manufacture of these plates shall not have the ultimate tensile strength less than that of the plate used.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 1996-12-06 | G.S.R. 59 OCR of scan | Substituted | Replaces regulation 574 on stayed flat surfaces with a thickness formula and coefficients C for stay types. | listed before the capture |
Possible IBR 2026 successors (heading match, unverified): Reg. 410, Reg. 466, Reg. 467, Reg. 500