Regulation 466. Stayed flat surfaces (other than crowns of vertical boilers)

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 778–779TableFormula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

466. Stayed flat surfaces (other than crowns of vertical boilers).─ For various braced and stayed flat plates and those which by these regulations require staying as flat surfaces with braces or stay bolts of uniform diameter symmetrically spaced, the thickness shall be calculated by the following formula; namely:-

e = Cd P Equation (12/11)
--- + e1
f1

Where,
P = maximum allowable working pressure in kgf / cm2,
e = thickness, in mm,
d = diameter of the largest circle taken between staying points of the plate (in mm), f1 = 0.85 f (‘f’ as defined in regulation 169), kgf/cm2,
e1= additional thickness equal to 0.75 mm,
C = coefficient having values given in table 12/5below, depending upon the form or method of support adopted.

Original extracted text of the table above, continued (diagnostic)
S. No                                      Table 12/5                             Value for ‘C’
S. NoComponentValue for ‘C’
(1)(2)(3)
1Flanged End Plate0.32
2Flat end plates welded to shell from both sides, with following end plate
thickness to shell plate thickness ratios
≤ 1.4
> 1.4 ≤ 1.6
> 1.6 ≤ 1.8
> 1.8 ≤ 2.0
0.33
0.36
0.39
0.42
3Plain Furnace Less than or equal to 6.5 meters long0.3
4Corrugated furnace with corrugation depths ≤ 50 mm0.32
5Corrugated furnace with corrugation depths > 50 mm with a length ≤ 6 meter
with a length > 6 meter
0.35
0.37
6Bowling hoop furnace0.35
7Access ring welded from both sides0.3
8Access ring welded from one side only0.45
9Gusset or Link stays0.3
10Stay tube in tube nest0.39
11Isolated stay tube0.45
12Stay bar in group0.39
13Isolated stay bar0.45

Table structure read from the Gazette PDF, pages 778, 779. Verification status as for the text above.

Show original extracted text (diagnostic, not authoritative)
 (1)                              Component                                             (3)
  1                                                                                    0.32
                                       (2)
  2                                                                                    0.33
       Flanged End Plate                                                               0.36
                                                                                       0.39
       Flat end plates welded to shell from both sides, with following end plate       0.42
       thickness to shell plate thickness ratios
       ≤ 1.4
       > 1.4 ≤ 1.6
       > 1.6 ≤ 1.8
       > 1.8 ≤ 2.0


3 Plain Furnace Less than or equal to 6.5 meters long                                          0.3

4 Corrugated furnace with corrugation depths ≤ 50 mm                                           0.32

5 Corrugated furnace with corrugation depths > 50 mm with a length ≤ 6 meter 0.35
        with a length > 6 meter 0.37

6 Bowling hoop furnace                                                                         0.35

7 Access ring welded from both sides                                                           0.3

8 Access ring welded from one side only                                                        0.45

9 Gusset or Link stays                                                                         0.3

10 Stay tube in tube nest                                                                      0.39

11 Isolated stay tube                                                                          0.45

12 Stay bar in group                                                                           0.39

13 Isolated stay bar                                                                           0.45

Notes: For Flanged end plates, the diameter of largest circle shall be taken from the commencement of the curvature i. of flange.
When largest circle is arrived with different types of supports as mentioned above, average value of ‘C’ shall ii. be taken for calculation.
If the plate is Flame swept, the thickness shall be increased by 10%. iii. The welding material used in the manufacture of these plates shall not have the ultimate tensile strength less iv. than that of the plate used.

Parts of this extracted text look garbled; read the Gazette page before using any value.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Referenced provisions

Reg. 169

Independent explanation — not the law · draft · engineer review in progress

In short

Gives the formula for the thickness of braced and stayed flat plates (other than crowns of vertical boilers) supported by stays of uniform diameter, symmetrically spaced.

Key points

  • Thickness e is found from Equation (12/11), using P (pressure, kgf/cm2), d (diameter of the largest circle between staying points, mm), f1 = 0.85 f (f as in regulation 169), an additional thickness e1 of 0.75 mm, and coefficient C.
  • Table 12/5 gives C for each form of support: flanged end plates, flat end plates welded from both sides (by end plate to shell plate thickness ratio), plain and corrugated furnaces, bowling hoop furnaces, access rings, gusset or link stays, stay tubes and stay bars. See the Official text tab for values.

Watch out

  • For flanged end plates, d is taken from the start of the flange curvature.
  • Where the largest circle touches different types of support, use the average value of C.
  • If the plate is flame swept, increase the thickness by 10%.
  • Welding material must not have a lower ultimate tensile strength than the plate.
  • The table layout is broken in the extracted text; check the Gazette page for which C value goes with which row.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
574Stayed flat surfaces (other than crowns of Vertical boilers)100%Chapter XII (DPIIT scan), image 6

Amendment history of the candidate IBR 1950 regulation: Reg. 574 (1 amendment)

IBR 1950 regulation 574 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 574 page for its amendments.

Reg. 572, Reg. 573, Reg. 574

Raised manhole frames, cover plates and joint bolts

Raised circular manhole frames not exceeding 16 inches in diameter shall not be less than ¾ inch thick in all parts.

The circular cover plates and joint flanges for such frames shall be not less than-

1 inch thick for pressures not exceeding 120 pounds per square inch.

1- 1/8 inches thick for pressures exceeding 120 pounds per square inch but not exceeding 200 pounds per square inch.

1 ¼ inches thick for pressure exceeding 200 pounds but not exceeding 250 pounds per square inch.

For pressure exceeding 250 pounds per square inch, raised circular manhole frames shall not be fitted.

The cover plates shall be secured by at least sixteen steel bolts not less than 1 inch diameter, such that the stress in the bolts due to steam pressure shall not exceed:-
5,000 pounds per square inch for 1 inch bolts.
6,000 pounds per square inch for 1- 1/8 inches bolts.
6,500 pounds per square inch for 1 ¼ inches bolts.

For the purpose of calculation the pressure shall be assumed to act on the whole area within the pitch circle of the bolts and the bolt area at the bottom of the screw thread shall be taken.



Reg. 573

Stand Pipes and branches-
a) The thickness and bolting of all flanges for joining the mountings  and fittings shall be in accordance with the dimensions as laid down in Appendix- E to these regulations. In no case, however, shall the thickness of flanges be less than 13 mm.
b)
(i) The Wall thickness of nozzles and other connections shall not be less than that specified for the applicable loading, namely, internal pressure, bending and static loads.
(ii) The pressure loading shall be determined by regulation 564, but in no case shall the thickness be less than that calculated by the following formula:-

t = 0.04D + 2.5 mm (equation XII/10)

where, t is the thickness of standpipe and D is the outside diameter of connection. If the branch is connected by screwing, the thickness ‘t’ shall be measured at the root of the thread.
c) Where a double flanged steam pipe is tapered, the thickness of flange joining the boiler and fitting shall correspond to the bore of pipe at the flange connection in accordance with Appendix-E to these regulations.


Reg. 574

Stayed Flat surfaces (other than Crowns of Vertical Boilers).

Stayed heads/ Braced and stayed surfaces.

For various braced and stayed flat plates and those which by these regulations require staying as flat surfaces with braces or stay bolts of uniform diameter symmetrically spaced, the thickness should be calculate by the following formula; namely:-

                                             __________
                        e  =  Cd      Ö P        +   e1
Ö   f1

Where,

P=design pressure in kgf/cm²
e=thickness, in mm.
d=diameter of the largest circle taken between staying points of the plate (in mm)
f1=0.85 f (f as defined in regulation 271), kfg/cm²
e1=additional thickness equal to 0.75 mm (0.03 in)
C=coefficient having the following values:-

1) C=0.33 for flanged connections;

NOTE:
d is the diameter of the largest circle taken from the commencement of the curvature of the flange.
2) C=0.40 for stays screwed in plate with nut or screwed and welded, or plain end strength welded on the outside;
3) C=0.33 for screwed bar stays with washer of not less than 3.5 times the diameter of bar stay;
4) C=0.31 for screwed bar stays with reinforcing plate, washer and nut on the outside.

NOTES:
1. If the plate is stayed in any other way, average values of C shall be taken into account.

2. If the plate is flame swept, the thickness shall be increased by 10%.

3. The welding materials used in the manufacture of these plates shall not have the ultimate tensile strength less than that of the plate used.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
778–779
PDF page index
778–779 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 8eb29956d5960519
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 466, Regulation 466, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.778–779. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.