480. Loads on stay tubes and bar stays.─ Requirements of regulation 121 shall apply.

Referenced provisions

Reg. 121

Independent explanation — not the law · draft · engineer review in progress

In short

Loads on stay tubes and bar stays for boilers under this chapter are worked out as set out in regulation 121, which defines the area each stay tube or stay bar must support.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
581Stay tubes100%Chapter XII (DPIIT scan), image 9
588Loads on Stay Tubes and Bar Stays100%Chapter XII (DPIIT scan), image 11
631Tubes100%Chapter XV (DPIIT scan), image 3

Amendment history of the candidate IBR 1950 regulations: Reg. 581 (3 amendments)

IBR 1950 regulation 581 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 581 page for its amendments.

Reg. 580, Reg. 581

Pitch of tubes

The spacing of tube holes shall be such that the minimum width in inches of any ligament between the tube holes shall be not less than:-

D + ½
8

alternatively,

the thickness and cross-section of the plate between the tube holes shall be not less than

0.125D+0.2=minimum thickness in inches.
0.17D+0.025=minimum cross-section in square inches where D is diameter of the tube holes in inches.

In no case shall the minimum thickness of any tube plate in the tube area be less than the following limits:-

T=1/2 inch, Where the diameter of the tube holes does not exceed 2 inches.
T=9/16 inch, Where the diameter of the tube hole is greater than 2 inches.



Reg. 581

Stay tubes

Stay tubes shall be of steel seamless or electrically resistance welded.
a) Minimum thickness of stay tubes – The minimum thickness of stay tubes shall be as per regulation 148.
b) The maximum working pressure for screwed in stay tube shall be calculated by the following formula:

WP = 5900         1.28
[(D---------------/N )² - D1²]
Equation XII/16
A

D is diameter of the stay tube over threads in inches.
D1 is internal diameter of the tubes under the threads in inches.
N is number of threads per inch.

A is the area in square inches supported by one Stay tube, measured from centre to centre of stay tubes. When the area contains tubes or parts of tubes their aggregate area, calculated from their smallest external diameter of body when in tension and smallest internal diameter when in compression, shall be deducted from the area of the containing figure and the remainder used as A in the formula.

Where stay tubes have their thickness increased at the screwed, ends to provide for plus threads the increased thickness shall be obtained by up-setting and not by welding, and the tubes shall be subsequently annealed.

Stay tubes may be attached to the tube plates either by screwing or by metal arc welding.

Where stay tubes are screwed into the tube plates they shall be screwed with a continuous thread not finer than 11 threads per inch at both ends and shall be expanded into the tube plates, by roller expander and, if desired, may be seal welded.

Welded attachment of stay tubes be as shown in Figure XII/67,XII/67A,XII/68, ,XII/68A and XII/69.
IBR 1950 regulation 588 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 588 page for its amendments.

Reg. 587, Reg. 588

Longitudinal Bar Stays

The maximum working pressure for longitudinal bar stays is to be calculated from the appropriate one of the following two formulae:

WP= C         1.28
(D - ------------)²
        N
Equation XII/21
A

WP= C x D1² Equation XII/22
A

WP is working pressure in pounds per square inch,
D is diameter of stays over threads in inches,
D1 is diameter of body of stays at its smallest part in inches,
N is the number of threads of stay per inch,
A is area in square inches supported by one stay.
C is values given in Table below:

TABLE XII/5
Stress on Longitudinal Bar Stays
Range of tensile strength of bar
Value of C
Tons per square inch Pounds per square inch
26/30 7850
28/32 8640
30/34 9420
32/36 10200

Where bar stays are fitted in vertical boilers, not less than four bar stays shall be fitted to boilers of 4 feet and over but under 5 feet in diameter; five bar stays to boilers of 5 feet and over but under 6 feet in diameter; six bar stays to boiler of 6 feet and over in diameter.

In no case, shall the diameter of the stay at any part be less than 1 inch. Where joined stays are fitted, the strength of the knuckle joint employed shall be at least equal to the strength of the remainder of the bar stay.


Reg. 588

Loads on Stay Tubes and Bar Stays

Stay tubes and bar stays shall be designed to carry the whole load due to the pressure on the area to be supported, the areas being calculated as follows:-

a) For a stay tube within the tube nest the net area to be supported shall be the product of the horizontal and vertical pitches, in inches, of the stay tubes less the area of the tube holes embraced. Where the pitch of the stay tubes is irregular the area shall be taken as the square of the mean pitch of the stay tubes (i.e., the square of ¼ of the sum of the four sides, of any quadrilateral bounded by four adjacent stay tubes), less the area of the tube holes embraced.
b) For a stay tube in the boundary row, or for a bar stay, the net area to be supported shall be the area, in square inches enclosed by lines passing midway between the stay and the adjacent points of support and by the boundary margin (see Regulation 589), less the area of any tubes or stays embraced.
c) In the case of a bar stay where there are no stay tubes in the tube nest the area to be supported shall extend to the tangential boundary of the tube nest.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
785
PDF page index
785 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash e0e04695ca02af26
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 480, Regulation 480, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.785. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.