Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 588 — Loads on Stay Tubes and Bar Stays
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 587. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 587, Reg. 588 | |||||||||||||||||||||||||||||||||
Reg. 588 Loads on Stay Tubes and Bar Stays
| |||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Loads on Stay Tubes and Bar Stays
Stay tubes and bar stays shall be designed to carry the whole load due to the pressure on the area to be supported, the areas being calculated as follows:-
a)For a stay tube within the tube nest the net area to be supported shall be the product of the horizontal and vertical pitches, in inches, of the stay tubes less the area of the tube holes embraced. Where the pitch of the stay tubes is irregular the area shall be taken as the square of the mean pitch of the stay tubes (i.e., the square of ¼ of the sum of the four sides, of any quadrilateral bounded by four adjacent stay tubes), less the area of the tube holes embraced.
b)
For a stay tube in the boundary row, or for a bar stay, the net area to be supported shall be the area, in square inches enclosed by lines passing midway between the
stay and the adjacent points of support and by the boundary margin (see Regulation 589), less the area of any tubes or stays embraced.
c)In the case of a bar stay where there are no stay tubes in the tube nest the area to be supported shall extend to the tangential boundary of the tube nest.
Possible IBR 2026 successors (heading match, unverified): Reg. 102, Reg. 119, Reg. 414, Reg. 415, Reg. 473, Reg. 480