Definitions & glossary
Statutory definitions from reg. 2 of the IBR 2026 and s.2 of the Boilers Act, 2025. Reg. 2(2) says that words not defined in the regulations take their meaning from the Act or the rules. Act and regulation definitions are listed separately; their scope may differ, so read the cited provision. This is not a glossary of every technical term used in the regulations.
Definitions are not yet verified; check the linked Act or Gazette provision.
| Term | Statutory definition (not yet verified) | Source |
|---|---|---|
| accident | means an explosion of boiler or boiler components, which is calculated to weaken the strength or an uncontrolled release of water or steam therefrom, liable to cause death or injury to any person or damage to any property; | Boilers Act 2025, s.2(a) |
| Act | means the Boilers Act, 2025 (12 of 2025); | IBR 2026, reg. 2(1)(a) |
| Appraisal Committee | means a Committee constituted by the Central Boilers Board to evaluate the performance of a firm or a company applying for recognition as Inspecting Authority; | IBR 2026, reg. 2(1)(b) |
| Board | means the Central Boilers Board constituted under section 3; | Boilers Act 2025, s.2(b) |
| boiler | means a pressure vessel in which steam is generated for use external to itself by application of heat which is wholly or partly under pressure when steam is shut off but does not include a pressure vessel,— (i) with capacity less than twenty-five litres, such capacity being measured from the feed check valve to the main steam stop valve; or (ii) with less than one kilogram per centimetre square design gauge pressure and working gauge pressure; or (iii) in which water is heated below one hundred degrees centigrade; | Boilers Act 2025, s.2(c) |
| boiler components | means steam piping, feed piping, economiser, superheater, any mounting or other fitting and any other external or internal part of a boiler which is subject to pressure exceeding one kilogram per centimetre square gauge. Explanation.—For the purposes of this clause, the term “superheater” means any equipment which is partly or wholly exposed to flue gases for the purpose of raising the temperature of steam beyond the saturation temperature at that pressure and includes a re-heater; | Boilers Act 2025, s.2(d) |
| Central Boilers Board Examination Standing Committee | means a Committee constituted by the Central Boilers Board to conduct examination for recognition of competent persons; | IBR 2026, reg. 2(1)(c) |
| Chief Inspector | , “Deputy Chief Inspector” and “Inspector”, mean, respectively, a person appointed to be a Chief Inspector, a Deputy Chief Inspector and an Inspector under section 5; | Boilers Act 2025, s.2(e) |
| competent authority | means an institution referred to in sub-section (1) of section 6; | Boilers Act 2025, s.2(f) |
| competent person | means an inspector or a person recognised in such manner as may be specified by regulations, for inspection and certification of boilers and boiler components during manufacture, erection and use; | Boilers Act 2025, s.2(g) |
| design pressure of boiler | (i) in relation to a natural or assisted circulation boiler means the maximum allowable working pressure in the steam drum of the boiler; (ii) in relation to an once through forced-circulation boiler means the maximum allowable working pressure at the final superheater steam outlet; | IBR 2026, reg. 2(1)(d) |
| design temperature | (i) for unheated components means the fluid temperature inside the component, under operation; (ii) for heated components, means the fluid temperature inside the component under sustained conditions increased by specified code allowances; | IBR 2026, reg. 2(1)(e) |
| economiser | means any part of a feed-pipe that is wholly or partially exposed to the action of flue gases for the purpose of recovery of waste heat; | Boilers Act 2025, s.2(h) |
| Evaluation Committee | means a committee constituted by the Central Government to evaluate the performance of firm or a company applying for recognition as competent authority, well-known material testing laboratory, well-known steel maker, well-known foundry or forge, well-known tube or pipe maker and well-known remnant life assessment organisation; | IBR 2026, reg. 2(1)(f) |
| feed-pipe | means any pipe or connected fitting wholly or partly under pressure through which feed water passes directly to a boiler and which does not form an integral part thereof; | Boilers Act 2025, s.2(i) |
| firm | means a firm and includes a company; | IBR 2026, reg. 2(1)(g) |
| Form | means the forms appended to these regulations; | IBR 2026, reg. 2(1)(h) |
| inspecting authority | means a chief inspector or an institution recognised in such manner as may be specified by regulations, for the inspection and certification of boilers and boiler components during manufacture and erection; | Boilers Act 2025, s.2(j) |
| manufacture | means manufacture, construction and fabrication of boiler or boiler components, or both; | Boilers Act 2025, s.2(k) |
| manufacturer | means a person engaged in the manufacture of boiler or boiler components, or both; | Boilers Act 2025, s.2(l) |
| maximum allowable working pressure | means the design pressure of any part, adjusted to take into account the pressure drop and hydraulic head; | IBR 2026, reg. 2(1)(i) |
| notification | means a notification published in the Official Gazette; | Boilers Act 2025, s.2(m) |
| owner | includes any person possessing or using a boiler as agent of the owner thereof and any person using a boiler which he has hired or obtained on loan from the owner thereof; | Boilers Act 2025, s.2(n) |
| pipe | means the cylindrical hollow parts, other than tube, drum or header with a design intent to carry a flow of steam or water or water-steam mixture during normal operation, including those that carry intermittent flow, such as drain pipes; Explanation.─ For the purpose of this clause , the expression ‘pipe’ implies that there is no design intent to effect heat transfer through the wall of the pressure part; | IBR 2026, reg. 2(1)(j) |
| prescribed | means prescribed by rules made under this Act; | Boilers Act 2025, s.2(o) |
| regulations | means regulations made by the Board under section 40; | Boilers Act 2025, s.2(p) |
| State Government | shall include Union territory administration; | Boilers Act 2025, s.2(q) |
| steam-pipe | means any pipe through which steam passes, if— (i) the pressure at which steam passes through such pipe exceeds three and half kilogram per square centimeters above atmospheric pressure; or (ii) such pipe exceeds two hundred fifty-four millimeters in internal diameter and the pressure of steam exceeds one kilogram per square centimeters above the atmospheric pressure, and includes in either case, any connected fitting of a steam-pipe and feed-pipe; | Boilers Act 2025, s.2(r) |
| structural alteration, addition or renewal | means,— (i) any change in the design of a boiler or boiler components; (ii) replacement of any part of boiler or boiler components by a part which does not conform to the same specification; or (iii) any addition to any part of a boiler or boiler components; | Boilers Act 2025, s.2(s) |
| Technical Adviser | means the Technical Adviser appointed under sub-section (1) of section 4. | Boilers Act 2025, s.2(t) |
| tube | means a tubular pressure part that is either exposed over much of its length to hot gases for purposes of heat transfer or is directly butt welded to such a tubular pressure part including a tube stub on a drum or header. | IBR 2026, reg. 2(1)(k) |