Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 473. Stay Tubes
Not yet checked against the official Gazette; verify before relying on it.
473. Stay Tubes.─ (1) Stay tubes shall be of seamless steel or electrically resistance welded steel.
(2)The minimum thickness of stay tubes shall be as per regulation 119.
(3)The maximum allowable working pressure for screwed in stay tube shall be calculated by the following formula:
𝑃 = 414.81108 [(𝐷 − 1.28)2 − 𝐷12] Equation (12/14)
𝐴 𝑁
Where, is maximum allowable working pressure in kg/cm2 (g)
P is diameter of the stay tube over threads in mm.
D is internal diameter of the tubes under the threads in mm. D1 is number of threads per mm.
N is the area in square mm supported by one Stay tube, measured from centre to centre of stay tubes. A When the area contains tubes or parts of tubes their aggregate area, calculated from their smallest external diameter of body when in tension and smallest internal diameter when in compression, shall be deducted from the area of the containing figure and the remainder used as A in the formula.
(4)Where stay tubes have their thickness increased at the screwed ends to provide for plus threads, the increased thickness shall be obtained by upsetting and not by welding, and the tubes shall be subsequently annealed.
(5)Stay tubes may be attached to the tube plates either by screwing or by metal arc welding.
(6)Where stay tubes are screwed into the tube plates, they shall be screwed with a continuous thread not finer than 4 threads per centimeter at both ends and shall be expanded into the tube plates, by roller expander and, if desired, may be seal welded.
(7)Welded attachment of stay tubes be as shown in Figures 12/81, 12/82, 12/83, 12/84and12/85.
Parts of this extracted text look garbled; read the Gazette page before using any value.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
Figures cited in this regulation (3, exact crops of the Gazette)

View Gazette page 818 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 820 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 820 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
In short
Sets material, thickness, pressure and fixing rules for stay tubes.
Key points
- (1) Stay tubes must be seamless steel or electrically resistance welded steel.
- (2) Minimum thickness is as per regulation 119.
- (3) For screwed-in stay tubes, maximum allowable working pressure comes from Equation (12/14), using diameter over threads, internal diameter under threads, threads per mm and the area A supported by one stay tube. Areas of tubes within that figure are deducted from A.
- (4) Where ends are thickened for threading, the extra thickness must be made by upsetting, not welding, and the tubes then annealed.
- (5) Stay tubes may be attached by screwing or by metal arc welding.
- (6) Screwed stay tubes need a continuous thread not finer than 4 threads per centimetre at both ends and must be expanded with a roller expander; they may also be seal welded.
- (7) Welded attachment follows Figures 12/81 to 12/85.
Watch out
- In the extracted text, the symbol definitions under Equation (12/14) are shifted one line against the symbols. Check the Gazette page for the exact formula.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 147 | Screw Threads of Stay Tubes | 100% | Chapter III (DPIIT scan), image 7 |
| 581 | Stay tubes | 100% | Chapter XII (DPIIT scan), image 9 |
| 588 | Loads on Stay Tubes and Bar Stays | 100% | Chapter XII (DPIIT scan), image 11 |
Amendment history of the candidate IBR 1950 regulations: Reg. 581 (3 amendments)
IBR 1950 regulation 147 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 147 page for its amendments.
| Reg. 147 STAY TUBES Screw Threads of Stay Tubes
|
IBR 1950 regulation 581 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 581 page for its amendments.
| Reg. 580, Reg. 581 | |||||||||||||||||
Reg. 581 Stay tubes
| |||||||||||||||||
IBR 1950 regulation 588 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 588 page for its amendments.
| Reg. 587, Reg. 588 | |||||||||||||||||||||||||||||||||
Reg. 588 Loads on Stay Tubes and Bar Stays
| |||||||||||||||||||||||||||||||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 473, Regulation 473, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.782. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.