BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction

Regulation 474. Compression of Tube Plates

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 782–783Formula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

474.Compression of Tube Plates.─ (1) For fire-box or combustion chamber tube plates which are subject to compression due to the pressure on the roof plate, the maximum allowable working pressure shall be:

𝑃 = 𝐶 (𝑝−𝐷) 32 𝑡 Equation (12/15)

Where, 𝐿 𝑝 t is thickness of the tube plate in mm.

p is pitch of the tubes in mm, measured horizontally where the tubes are chain pitched or diagonally where the tubes are zigzag pitched and the diagonal pitch is less than the horizontal.

D is internal diameter of the plain tubes in mm.

L is internal length of the fire-box or combustion chamber in mm measured at top between tube plate and Firehole plate or back plate, or between tube plates in double ended boilers with combustion chambers common to two opposite furnaces.

C = 61.16706

Provided that the above formula shall not apply in the cases of fire-boxes where the girders do not rest on the tube plate, or where the roof plate is stayed direct to the outer shell or to girders supported by the shell.

(2)Where girders rest on the side plates or the roof plate is so formed that the load is carried both by side and end plates, the compressive stress on the plates shall not in either case exceed 984 kg/cm2.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Independent explanation — not the law · draft · engineer review in progress

In short

Sets the maximum allowable working pressure for fire-box and combustion chamber tube plates under compression from the pressure on the roof plate.

Key points

  • (1) Pressure from Equation (12/15), with C = 61.16706, t (tube plate thickness), p (tube pitch), D (internal diameter of plain tubes) and L (internal length of the fire-box or combustion chamber at the top), all in mm.
  • (1) p is measured horizontally for chain pitching, or diagonally for zigzag pitching where the diagonal pitch is less than the horizontal.
  • (2) Where girders rest on the side plates, or the roof plate carries load to both side and end plates, compressive stress on the plates must not exceed 984 kg/cm2.

Watch out

  • The formula does not apply to fire-boxes where the girders do not rest on the tube plate, or where the roof plate is stayed directly to the outer shell or to girders supported by the shell.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
33Plates100%Chapter II (DPIIT scan), image 3
118Tube Plates100%Chapter III (DPIIT scan), image 2
582Compression of tube plates100%Chapter XII (DPIIT scan), image 9
IBR 1950 regulation 33 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 33 page for its amendments.

Reg. 33
MATERIALS OF CONSTRUCTION

COPPER PLATES, STAY AND RIVET BARS

Plates

(a) Process.- The copper shall be fire-refined or electrolytic and hot-rolled from suitable cakes.

(b) Chemical Composition.- The chemical composition of the plates shall be as follows:-

Per cent.
Copper 99.2 minimum
Arsenic .30 to .50
Antimony 0.05 maximum
Bismuth 0.05 maximum
Oxygen 0.10 maximum

(c) Freedom from defects.- The plates shall be clean, smooth and free from defects and shall have a workmanlike finish. They shall be thoroughly annealed.

(d) Rolling Margin.- No plate shall be under the specified thickness at any part, not more than 5% over the calculated weight. The scrap margin, partly sheared and left attached, shall be not less than 3 inches at the ends and 1½ inches at each side.

(e) Tensile Tests.- One tensile test shall be taken from each plate as rolled.

The tensile breaking strength, from Standard Test Piece A, shall not be less than 14 tons per sq. inch with an elongation of not less than 35%.

(f) Hot and Cold Bend tests.- One hot (temperature between 1200°F and 1400°F) and one cold bend test shall be taken from each plate as rolled.

For either hot or cold bend tests, the test piece shall withstand being doubled over without fracture until the sides are touching and parallel.

IBR 1950 regulation 118 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 118 page for its amendments.

Reg. 118, Reg. 119, Reg. 120
END PLATES

 

Tube Plates

Smoke-box tube plates shall be flanged for attachment to the barrel or shall be flat and connected thereto by an external riveted angle ring.

Reg. 119
END PLATES

 

Parts of flat tube plates within the tube nests

a) where the total area of all tube nests in directly fired multi-tubular boilers exceeds 7 sq. ft., stay tubes shall be fitted.

Where the total number of tubes in horizontal multitubular waste heat boilers and direct fired loco type boilers is arranged in one next, the area of which exceed 21 sq. ft., stay tubes shall be fitted.

In all cases where the total number of tubes is arranged in more than one nest, stay tubes shall be fitted.
b) The parts of tube plates which lie outside the nests of tubes shall be stayed or supported wherever the size of the area of plate subject to steam pressure necessitates staying or support, either by marginal stay tubes or other means.


Reg. 120
END PLATES
Flanging of End Plates

All flanges shall be a good fit to the shell and flues. Flogging and/or hammering in the fitting of these parts is prohibited. The caulking edges of all flanged plates shall be machined or machine gas cut.

IBR 1950 regulation 582 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 582 page for its amendments.

Reg. 582, Reg. 583, Reg. 584

Compression of tube plates

a)

For fire-box or combustion chamber tube plates which are subject to compression due to the pressure on the roof plate, the maximum working pressure shall be:

WP = C x (P-D) x t Equation XII/17
L x P

t is thickness of the tube plate in thirty seconds of an inch.

P is pitch of the tubes in inches, measured horizontally where the tubes are chain pitched or diagonally where the tubes are zig zag pitched and the diagonal pitch is less than the horizontal.

D is internal diameter of the plain tubes in inches.

L is internal length of the fire-box or combusion chamber in inches measured at top between tube plate and firehole plate or back plate, or between tube plates in double ended boilers with combustion chambers common to two opposite furnaces.

C = 875.

Provided that the above formula shall not apply in the cases of fireboxes where the girders do not rest on the tube plate, or where the roof plate is stayed direct to the outer shell or to girders supported by the shell.
b) Where girders rest on the side plates or the roof plate is so formed that the load is carried both by side and end plates, the compressive stress on the plate shall not in either case exceed 14,000 pounds per square inch.


Reg. 583

Girders for fire-box and combustion chamber crowns

a) For girders supporting crown plates of rectangular fire-boxes, where the ends of the girders are supported by the vertical end or side plates, their proportions shall be calculated by the following formula:

WP= CST d² Equation XII/18
L² Y

Where,

WP is Working pressure in pounds per square inch,
S is Minimum tensile stress of the material in tons per square inch,
T is Total thickness of the stay in thirty seconds of an inch.
d is Depth of the girder stay in inches,
L is Length of girder stay in inches measured between the inside of the tube plate and the fire-hole plate, or between the inside of the side plates, according to the method of support.
Y is Pitch of girder stays in inches.
C = 22 for steel plates or steel forgings,
= 19 for steel castings.
b) Where girders are welded to the crown plate the dimensions of the welds shall be such that the stress calculated on an area equal to the sum of the effective lengths of the welds attaching each girder multiplied by the effective throat thickness shall not exceed 7,500 pounds per square inch multiplied by the appropriate weld factor in Table XII/7, (“effective length” and “effective throat thickness” are defined in Regulation 591). The load on the welds shall be taken as that due to the design pressure acting on the area LY; L and Y being as defined in Regulation 583.


Reg. 584

Girder sling stays

For slung girders the proportion of slings, links, pins and connections to the shell shall be sufficient to carry the whole load that would otherwise be carried on the toes of the girders and for any of the above parts in tension a stress of 9,000 pounds per square inch of net section, and for parts in shear a stress of 8,000 pounds per square inch of net section shall not be exceeded. In the case of parts in double shear, the net area of the section should be taken as 1.875 times the single section.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
782–783
PDF page index
782–783 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 12bf3113d77096fa
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 474, Regulation 474, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.782–783. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page