Compression of tube plates
a)For fire-box or combustion chamber tube plates which are subject to compression due to the pressure on the roof plate, the maximum working pressure shall be:
C x (P-D) x t
WP = Equation XII/17
L x P
t is thickness of the tube plate in thirty seconds of an inch.
P is pitch of the tubes in inches, measured horizontally where the tubes are chain pitched or diagonally where the tubes are zig zag pitched and the diagonal pitch is less than the horizontal.
D is internal diameter of the plain tubes in inches.
L is internal length of the fire-box or combusion chamber in inches measured at top between tube plate and firehole plate or back plate, or between tube plates in double ended boilers with combustion chambers common to two opposite furnaces.
C = 875.
Provided that the above formula shall not apply in the cases of fireboxes where the girders do not rest on the tube plate, or where the roof plate is stayed direct to the outer shell or to girders supported by the shell.
b)Where girders rest on the side plates or the roof plate is so formed that the load is carried both by side and end plates, the compressive stress on the plate shall not in either case exceed 14,000 pounds per square inch.