Reg. 583 Girders for fire-box and combustion chamber crowns
Reg. 584 Girder sling stays
| |||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Girders for fire-box and combustion chamber crowns
a)For girders supporting crown plates of rectangular fire-boxes, where the ends of the girders are supported by the vertical end or side plates, their proportions shall be calculated by the following formula:
CST d²
WP= Equation XII/18
L² Y
Where,
WP is Working pressure in pounds per square inch,
S is Minimum tensile stress of the material in tons per square inch,
T is Total thickness of the stay in thirty seconds of an inch. d is Depth of the girder stay in inches,
L is Length of girder stay in inches measured between the inside of the tube plate and the fire-hole plate, or between the inside of the side plates, according to the method of support.
Y is Pitch of girder stays in inches.
C = 22 for steel plates or steel forgings, = 19 for steel castings.
b)Where girders are welded to the crown plate the dimensions of the welds shall be such that the stress calculated on an area equal to the sum of the effective lengths of the welds attaching each girder multiplied by the effective throat thickness shall not exceed 7,500 pounds per square inch multiplied by the appropriate weld factor in
Table XII/7, (“effective length” and “effective throat thickness” are defined in Regulation 591). The load on the welds shall be taken as that due to the design pressure acting on the area LY; L and Y being as defined in Regulation 583.