Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction

Regulation 475. Girders for fire-box and combustion chamber crowns

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 783–784TableFormula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

475.Girders for fire-box and combustion chamber crowns.─ (1) For girders supporting crown plates of rectangular fire-boxes, where the ends of the girders are supported by the vertical end or side plates, their proportions shall be calculated by the following formula:

    CSTd2                                               Equation (12/16)

P = --------
      L2Y

Where,

P is maximum allowable working pressure in kg/cm2 (g)

S is Minimum tensile stress of the material in kg/cm2,

T is Total thickness of the stay in mm.

d is Depth of the girder stay in mm,

L is Length of girder stay in mm measured between the inside of the tube plate and the fire-hole plate, or between the inside of the side plates, according to the method of support.

Y is Pitch of girder stays in mm.

C = 0.352 for steel plates or steel forgings,

= 0.304 for steel castings.

(2)Where girders are welded to the crown plate the dimensions of the welds shall be such that the stress calculated on an area equal to the sum of the effective lengths of the welds attaching each girder multiplied by the effective throat thickness shall not exceed 527 kg/cm2multiplied by the appropriate weld factor in

Table 12/13, (“effective length” and “effective throat thickness” are defined in regulation486.The load on the welds shall be taken as that due to the maximum allowable working pressure acting on the area ‘LY’, ‘L’ and ‘Y’ being as defined in this regulation.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Referenced provisions

Reg. 486

Independent explanation — not the law · draft · engineer review in progress

In short

Sets the strength of girders supporting the crown plates of rectangular fire-boxes, and of their welds to the crown plate.

Key points

  • (1) Where girder ends rest on the vertical end or side plates, pressure is found from Equation (12/16), using S (minimum tensile stress), T (total stay thickness), d (girder depth), L (girder length between supports) and Y (girder pitch).
  • (1) C = 0.352 for steel plates or steel forgings and 0.304 for steel castings.
  • (2) For girders welded to the crown plate, the stress on the welds (sum of effective weld lengths × effective throat thickness) must not exceed 527 kg/cm2 multiplied by the weld factor from Table 12/13. The load is the pressure acting on area LY.
  • "Effective length" and "effective throat thickness" are defined in regulation 486.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
583Girders for fire100%Chapter XII (DPIIT scan), image 10
586Fire100%Chapter XII (DPIIT scan), image 10
IBR 1950 regulation 583 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 583 page for its amendments.

Reg. 582, Reg. 583, Reg. 584

Compression of tube plates

a)

For fire-box or combustion chamber tube plates which are subject to compression due to the pressure on the roof plate, the maximum working pressure shall be:

WP = C x (P-D) x t Equation XII/17
L x P

t is thickness of the tube plate in thirty seconds of an inch.

P is pitch of the tubes in inches, measured horizontally where the tubes are chain pitched or diagonally where the tubes are zig zag pitched and the diagonal pitch is less than the horizontal.

D is internal diameter of the plain tubes in inches.

L is internal length of the fire-box or combusion chamber in inches measured at top between tube plate and firehole plate or back plate, or between tube plates in double ended boilers with combustion chambers common to two opposite furnaces.

C = 875.

Provided that the above formula shall not apply in the cases of fireboxes where the girders do not rest on the tube plate, or where the roof plate is stayed direct to the outer shell or to girders supported by the shell.
b) Where girders rest on the side plates or the roof plate is so formed that the load is carried both by side and end plates, the compressive stress on the plate shall not in either case exceed 14,000 pounds per square inch.


Reg. 583

Girders for fire-box and combustion chamber crowns

a) For girders supporting crown plates of rectangular fire-boxes, where the ends of the girders are supported by the vertical end or side plates, their proportions shall be calculated by the following formula:

WP= CST d² Equation XII/18
L² Y

Where,

WP is Working pressure in pounds per square inch,
S is Minimum tensile stress of the material in tons per square inch,
T is Total thickness of the stay in thirty seconds of an inch.
d is Depth of the girder stay in inches,
L is Length of girder stay in inches measured between the inside of the tube plate and the fire-hole plate, or between the inside of the side plates, according to the method of support.
Y is Pitch of girder stays in inches.
C = 22 for steel plates or steel forgings,
= 19 for steel castings.
b) Where girders are welded to the crown plate the dimensions of the welds shall be such that the stress calculated on an area equal to the sum of the effective lengths of the welds attaching each girder multiplied by the effective throat thickness shall not exceed 7,500 pounds per square inch multiplied by the appropriate weld factor in Table XII/7, (“effective length” and “effective throat thickness” are defined in Regulation 591). The load on the welds shall be taken as that due to the design pressure acting on the area LY; L and Y being as defined in Regulation 583.


Reg. 584

Girder sling stays

For slung girders the proportion of slings, links, pins and connections to the shell shall be sufficient to carry the whole load that would otherwise be carried on the toes of the girders and for any of the above parts in tension a stress of 9,000 pounds per square inch of net section, and for parts in shear a stress of 8,000 pounds per square inch of net section shall not be exceeded. In the case of parts in double shear, the net area of the section should be taken as 1.875 times the single section.
IBR 1950 regulation 586 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 586 page for its amendments.

Reg. 585 a, Reg. 585 b, Reg. 586

Stays for fire-boxes and circular furnaces

(a) Solid screwed stays

For screw stays to combustion chambers and fire-boxes and for longitudinal and cross stays, the maximum working pressure for the stays is to be calculated from the appropriate one of the following two formulae:-

WP= C         1.28
(D - ------------)²
        N
Equation XII/19
A

WP= C x D1² Equation XII/20
A

WP is the working pressure in pounds per square inch.
D is diameter of stays over threads in inches.
D1 is diameter of body of stay at its smallest part in inches.
N is number of threads of stay per inch.

A is area in square inches supported by one stay for area to be supported by stays near tubes in fire-box tube plates of Loco-type boilers, [see Regulation 193(a)].

C=7,100 for steel or special wrought iron screw stays to combustion chamber or fire-boxes,
C=8,640 for steel longitudinal or cross stays fitted with nuts.
   =4,700 for copper stays.

Where stays are made with enlarged ends and the body of the stay is smaller in diameter than at the bottom of the thread the working pressure shall be calculated from the second formula.


Reg. 585 b

Circumferential stays for circular furnaces and fire-boxes

The diameter of the stay shall be not less than ¾ inch or twice the thickness of the fire-box plate, whichever is the greater. In the case of screwed threads the diameter shall be measured over the threads.

The pitch of the stays at the fire-box shall not exceed 14 times the thickness of the fire-box plate.


Reg. 586

Fire-box Crown stays for Loco-type Boilers

Where fire-box crown stays are directly attached to a semi-cylindrical outer casing, and the fire-box top is cambered and fitted with stays arranged as shown in Figure XII/78, the thickness of the outer casing shall be sufficient to provide not less than three engaging threads, of which not less than one shall be full thread in stays not normal to the stayed surface, but if the thickness of the plate is not sufficient to give one engaging full thread the plate shall be reinforced.

Where vertical stays only are used to take part of the load on the fire-box top, boilers with shells 4 feet and 6 inches diameter and over shall be fitted with transverse stay (see Figure XII/79). Stays may be attached as shown in Figures XII/39, XII/40 and XII/41.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
783–784
PDF page index
783–784 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 5b9f81b0703e17de
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 475, Regulation 475, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.783–784. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).