Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 475. Girders for fire-box and combustion chamber crowns
Not yet checked against the official Gazette; verify before relying on it.
475.Girders for fire-box and combustion chamber crowns.─ (1) For girders supporting crown plates of rectangular fire-boxes, where the ends of the girders are supported by the vertical end or side plates, their proportions shall be calculated by the following formula:
CSTd2 Equation (12/16)
P = --------
L2Y
Where,
P is maximum allowable working pressure in kg/cm2 (g)
S is Minimum tensile stress of the material in kg/cm2,
T is Total thickness of the stay in mm.
d is Depth of the girder stay in mm,
L is Length of girder stay in mm measured between the inside of the tube plate and the fire-hole plate, or between the inside of the side plates, according to the method of support.
Y is Pitch of girder stays in mm.
C = 0.352 for steel plates or steel forgings,
= 0.304 for steel castings.
(2)Where girders are welded to the crown plate the dimensions of the welds shall be such that the stress calculated on an area equal to the sum of the effective lengths of the welds attaching each girder multiplied by the effective throat thickness shall not exceed 527 kg/cm2multiplied by the appropriate weld factor in
Table 12/13, (“effective length” and “effective throat thickness” are defined in regulation486.The load on the welds shall be taken as that due to the maximum allowable working pressure acting on the area ‘LY’, ‘L’ and ‘Y’ being as defined in this regulation.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Sets the strength of girders supporting the crown plates of rectangular fire-boxes, and of their welds to the crown plate.
Key points
- (1) Where girder ends rest on the vertical end or side plates, pressure is found from Equation (12/16), using S (minimum tensile stress), T (total stay thickness), d (girder depth), L (girder length between supports) and Y (girder pitch).
- (1) C = 0.352 for steel plates or steel forgings and 0.304 for steel castings.
- (2) For girders welded to the crown plate, the stress on the welds (sum of effective weld lengths × effective throat thickness) must not exceed 527 kg/cm2 multiplied by the weld factor from Table 12/13. The load is the pressure acting on area LY.
- "Effective length" and "effective throat thickness" are defined in regulation 486.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 583 | Girders for fire | 100% | Chapter XII (DPIIT scan), image 10 |
| 586 | Fire | 100% | Chapter XII (DPIIT scan), image 10 |
IBR 1950 regulation 583 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 583 page for its amendments.
| Reg. 582, Reg. 583, Reg. 584 | |||||||||||||||||||
Reg. 583 Girders for fire-box and combustion chamber crowns
Reg. 584 Girder sling stays
| |||||||||||||||||||
IBR 1950 regulation 586 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 586 page for its amendments.
| Reg. 585 a, Reg. 585 b, Reg. 586 | |||||||||||||||||
Reg. 585 b Circumferential stays for circular furnaces and fire-boxes
Reg. 586 Fire-box Crown stays for Loco-type Boilers
| |||||||||||||||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 475, Regulation 475, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.783–784. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.