Regulation 407. Internal flues

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 758–759Figure referenced

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

407. Internal flues.─ (1) Sections of internal flues shall each be made from one plate, which shall be rolled while cold to circular form. The longitudinal seam shall be fusion butt-welded by the metal arc process.

(2)The maximum permissible variation in diameter of any cross-section shall not exceed 6 mm or half of the thickness of the plate, whichever is greater.

(3)The longitudinal welds shall be placed at lower part of the furnace and shall break joint in successive sections at least by 150 mm. This requirement shall not be applicable if successive sections are separated by tube plate or end plate or bowling hoops.

(4)Where flue sections are flanged for circumferential joints, the flanging shall be carried out at one heat by suitable machinery.

(5)Edges of all flue flanges shall be machined or flame-cut by machine (see regulation 402).

(6)Flanged circumferential seams shall be so arranged that they do not fall in line with those of the adjacent flue or with circumferential seams of the shell.

(7)The minimum mean internal diameter of furnaces shall not be less than those given in Figure 12/23 depending on the net heat input.

(8)Where furnace flue is made up of plain or corrugated sections or both, they may be connected to each other by fusion butt welded circumferential seams.

(9)(a) Plain furnaces shall not exceed 3 meter in length except in the case of reverse flame boilers, which are considered to be inherently flexible or as provided in clause (d). In all other cases flexibility shall be provided in the furnace by means of corrugations or blowing hoops or stepping of a minimum of 150 mm in the diameter of the furnace. (see figures 12/24 to 12/28.

(b)If corrugations are used to provide flexibility, at least one-third of the furnace length shall be corrugated.

(c)Breathing spaces as per regulation 483 shall be provided for boilers made as per this clause.

(d)Notwithstanding the provisions of clauses (a) and (b), plain furnaces longer than 3 meter are allowed to be used in a boiler when the length between boiler end plates do not exceed 6.5 meters provided that breathing spaces used in this case are in accordance with regulation 484 .

(10)Where a complete flue is constructed of short plain sections, the ends of each adjoining section shall either be swaged out to a radius to provide an adequate point of support and longitudinal flexibility and butt-welded together or be butt-welded to each side of a bowling hoop. The dimensions shall comply with Figures 12/31, 12/32 or 12/33.

(11)Stress relieving by heat-treatment shall be carried out when the construction of a flue involves the use of a circumferential weld such stress relieving being carried out on the completion of all welding in accordance with regulation 453.

(12)The forms of flue connections to end plates shall be as shown in Figures 12/14, 12/15, 12/16, 12/17 and 12/18 or be in any other form of welding groove subject to the approval of the Inspecting Authority.

Referenced provisions

Reg. 402 · Reg. 453 · Reg. 483 · Reg. 484

Figures cited in this regulation (13, exact crops of the Gazette)

Gazette Fig. 12/14: Attachment of Flues to End Plates – Dished or Flat
Fig. 12/14Attachment of Flues to End Plates – Dished or Flat
View Gazette page 800 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/15
Fig. 12/15(no caption printed with this figure)
View Gazette page 800 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/16: Flue Connections to End Plates (Dished or Flat)
Fig. 12/16Flue Connections to End Plates (Dished or Flat)
View Gazette page 800 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/17: Flue Connections to End Plates (Dished or Flat)
Fig. 12/17Flue Connections to End Plates (Dished or Flat)
View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/18
Fig. 12/18(no caption printed with this figure)
View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/24: Reverse Fired Boiler
Fig. 12/24Reverse Fired Boiler
View Gazette page 803 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/25: Dry Back Boiler
Fig. 12/25Dry Back Boiler
View Gazette page 803 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/26: Wet Back Boiler
Fig. 12/26Wet Back Boiler
View Gazette page 803 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
See Gazette page
Fig. 12/27Semi-Wet Back Boiler
Gazette p.803
Gazette Fig. 12/28: Semi-Wet Back Boiler
Fig. 12/28Semi-Wet Back Boiler
View Gazette page 804 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/31: Bowling Hoop
Fig. 12/31Bowling Hoop
View Gazette page 804 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/32: Bowling Hoop
Fig. 12/32Bowling Hoop
View Gazette page 804 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/33: Detail Flue Joint
Fig. 12/33Detail Flue Joint
View Gazette page 804 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 407 sets the construction rules for internal flues (furnaces) of welded boilers.

Key points

  • (1) Each flue section is made from one plate, cold-rolled to circular form, with the longitudinal seam fusion butt-welded by the metal arc process.
  • (2) Variation in diameter at any cross-section must not exceed 6 mm or half the plate thickness, whichever is greater.
  • (3) Longitudinal welds go in the lower part of the furnace and break joint in successive sections by at least 150 mm, unless the sections are separated by a tube plate, end plate or bowling hoop.
  • (4) Flanging for circumferential joints is done at one heat by suitable machinery. (5) Flange edges are machined or machine flame-cut (see regulation 402).
  • (6) Flanged circumferential seams must not line up with those of the adjacent flue or the shell's circumferential seams.
  • (7) Minimum mean internal diameter depends on net heat input (Figure 12/23).
  • (8) Plain and corrugated sections may be joined by fusion butt welded circumferential seams.
  • (10) Flues made of short plain sections have swaged ends butt-welded together, or are butt-welded to a bowling hoop, to the dimensions in the figures.
  • (11) A flue with a circumferential weld is stress relieved by heat treatment after all welding, in accordance with regulation 453.
  • (12) Flue-to-end-plate connections follow the listed figures, or another welding groove approved by the Inspecting Authority.

Watch out

  • (9)(a) Plain furnaces may not exceed 3 meter in length, except reverse flame boilers or under (d). Otherwise flexibility is needed: corrugations, bowling hoops, or stepping of at least 150 mm in diameter.
  • (9)(b) If corrugations are used, at least one-third of the furnace length must be corrugated. (9)(c) Breathing spaces follow regulation 483.
  • (9)(d) Plain furnaces longer than 3 meter are allowed where the length between end plates does not exceed 6.5 meters, with breathing spaces as per regulation 484.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
567Dished ends subject to internal pressure73%Chapter XII (DPIIT scan), image 4
IBR 1950 regulation 567 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 567 page for its amendments.

Reg. 567, Reg. 567A

Dished ends subject to internal pressure

a)

For unstayed ends of shells and tops of vertical boilers and the like boiler parts, when dished to partial spherical form the maximum working pressure shall be determined by the following formula:-

WP = 15 x S X (t-1)
Equation XII/7
R

WP is the working pressure in pounds per square inch.

t is thickness of the end plate in thirty seconds of an inch but in no case this shall be less than the thickness of the shell to which it is attached.

R is the inner radius of curvture of the end in inches, which shall not exceed the external diameter of the shell to which it is attached.

S is the minimum tensile breaking strength of plate in tons per square inch, or whatever is allowed for it.
b) The inside radius to which a crown plate is dished shall be not greater than the external diameter of the cylinder to which it is attached.
c) The inside radius of curvature of the flanges to the shell shall be not less than 4 times the thickness of the crown plate and in no case less than 2 ½ inches.
d) The inside radius of curvature of flanges to uptakes shall be not less than twice the thickness of the crown plate and in no case less than 1 inch.
e) When the end has a manhole in it (t-5), shall be substituted for (t -1) in the formula.
f) The total depth of flange of manhole from the outer surface in inches measured on the minor axis shall be at least equal to-

ÖT X W depth of flange in inches Equation XII/8

where T is the thickness of the plate in inches and W is the minor axis of the hole in inches.
g) The depth of the crown plate opening from the commencement of the curvature of the flanging radius shall be not less than twice the plate thickness with a minimum of one inch.


Reg. 567A

Nothing in Regulation 567 shall preclude the use of dished ends in compliance with Regulations 275 to 278, where not fitted with an uptake.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
758–759
PDF page index
758–759 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 1c1b17745ff08dff
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log