Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 407. Internal flues
Not yet checked against the official Gazette; verify before relying on it.
407. Internal flues.─ (1) Sections of internal flues shall each be made from one plate, which shall be rolled while cold to circular form. The longitudinal seam shall be fusion butt-welded by the metal arc process.
(2)The maximum permissible variation in diameter of any cross-section shall not exceed 6 mm or half of the thickness of the plate, whichever is greater.
(3)The longitudinal welds shall be placed at lower part of the furnace and shall break joint in successive sections at least by 150 mm. This requirement shall not be applicable if successive sections are separated by tube plate or end plate or bowling hoops.
(4)Where flue sections are flanged for circumferential joints, the flanging shall be carried out at one heat by suitable machinery.
(5)Edges of all flue flanges shall be machined or flame-cut by machine (see regulation 402).
(6)Flanged circumferential seams shall be so arranged that they do not fall in line with those of the adjacent flue or with circumferential seams of the shell.
(7)The minimum mean internal diameter of furnaces shall not be less than those given in Figure 12/23 depending on the net heat input.
(8)Where furnace flue is made up of plain or corrugated sections or both, they may be connected to each other by fusion butt welded circumferential seams.
(9)(a) Plain furnaces shall not exceed 3 meter in length except in the case of reverse flame boilers, which are considered to be inherently flexible or as provided in clause (d). In all other cases flexibility shall be provided in the furnace by means of corrugations or blowing hoops or stepping of a minimum of 150 mm in the diameter of the furnace. (see figures 12/24 to 12/28.
(b)If corrugations are used to provide flexibility, at least one-third of the furnace length shall be corrugated.
(c)Breathing spaces as per regulation 483 shall be provided for boilers made as per this clause.
(d)Notwithstanding the provisions of clauses (a) and (b), plain furnaces longer than 3 meter are allowed to be used in a boiler when the length between boiler end plates do not exceed 6.5 meters provided that breathing spaces used in this case are in accordance with regulation 484 .
(10)Where a complete flue is constructed of short plain sections, the ends of each adjoining section shall either be swaged out to a radius to provide an adequate point of support and longitudinal flexibility and butt-welded together or be butt-welded to each side of a bowling hoop. The dimensions shall comply with Figures 12/31, 12/32 or 12/33.
(11)Stress relieving by heat-treatment shall be carried out when the construction of a flue involves the use of a circumferential weld such stress relieving being carried out on the completion of all welding in accordance with regulation 453.
(12)The forms of flue connections to end plates shall be as shown in Figures 12/14, 12/15, 12/16, 12/17 and 12/18 or be in any other form of welding groove subject to the approval of the Inspecting Authority.
Figures cited in this regulation (13, exact crops of the Gazette)

View Gazette page 800 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 800 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 800 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 801 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 803 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 803 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 803 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 804 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 804 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 804 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 804 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
In short
Regulation 407 sets the construction rules for internal flues (furnaces) of welded boilers.
Key points
- (1) Each flue section is made from one plate, cold-rolled to circular form, with the longitudinal seam fusion butt-welded by the metal arc process.
- (2) Variation in diameter at any cross-section must not exceed 6 mm or half the plate thickness, whichever is greater.
- (3) Longitudinal welds go in the lower part of the furnace and break joint in successive sections by at least 150 mm, unless the sections are separated by a tube plate, end plate or bowling hoop.
- (4) Flanging for circumferential joints is done at one heat by suitable machinery. (5) Flange edges are machined or machine flame-cut (see regulation 402).
- (6) Flanged circumferential seams must not line up with those of the adjacent flue or the shell's circumferential seams.
- (7) Minimum mean internal diameter depends on net heat input (Figure 12/23).
- (8) Plain and corrugated sections may be joined by fusion butt welded circumferential seams.
- (10) Flues made of short plain sections have swaged ends butt-welded together, or are butt-welded to a bowling hoop, to the dimensions in the figures.
- (11) A flue with a circumferential weld is stress relieved by heat treatment after all welding, in accordance with regulation 453.
- (12) Flue-to-end-plate connections follow the listed figures, or another welding groove approved by the Inspecting Authority.
Watch out
- (9)(a) Plain furnaces may not exceed 3 meter in length, except reverse flame boilers or under (d). Otherwise flexibility is needed: corrugations, bowling hoops, or stepping of at least 150 mm in diameter.
- (9)(b) If corrugations are used, at least one-third of the furnace length must be corrugated. (9)(c) Breathing spaces follow regulation 483.
- (9)(d) Plain furnaces longer than 3 meter are allowed where the length between end plates does not exceed 6.5 meters, with breathing spaces as per regulation 484.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 567 | Dished ends subject to internal pressure | 73% | Chapter XII (DPIIT scan), image 4 |
IBR 1950 regulation 567 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 567 page for its amendments.