Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 488. Plain furnaces
Not yet checked against the official Gazette; verify before relying on it.
488.Plain furnaces.─ (1) The maximum allowable working pressure of plain furnaces shall be the lower of those obtained using equations 12/23 and 12/24 as follows, but the thickness shall be not less than 7 mm and shall not exceed 22 mm:
| 2 Et (e-C) | 1+ d 15L | |
| 𝑃= S1 d [1+ | 0.03du ] d (e-C)(1+0.3L) | Equation (12/23) Equation (12/24) |
| 𝑃 = 1.73 𝐸 | (𝑒−𝐶)2.5 𝑆2 𝐿 𝑑 |
Columns reconstructed from the extracted text; check against the Gazette page.
Show original extracted text (diagnostic, not authoritative)
2 Et (e-C) 1+ d
15L
𝑃= S1 d [1+ 0.03du ] Equation (12/23)
d Equation (12/24)
(e-C)(1+0.3L)
𝑃 = 1.73 𝐸 (𝑒−𝐶)2.5
𝑆2 𝐿 𝑑(2)Equation 12/23 and 12/24 may be expressed in terms of thickness using equation 12/25 and 12/26 respectively as follows and the greater of the thickness obtained shall be used.
Equation (12/25)
Where,
Equation (12/26)
(3)If the furnace/ combustion chamber has tubes radially to it, the thickness of that portion of the furnace is to be increased by the value of ligament efficiency.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 488 sets the maximum allowable working pressure of plain furnaces. It also limits their thickness to between 7 mm and 22 mm.
Key points
- (1) The pressure is the lower of the values from Equation (12/23) and Equation (12/24). These use the symbols defined in regulation 487.
- (2) The same equations can be written for thickness as Equation (12/25) and Equation (12/26). Use the greater of the two thicknesses.
- (3) Where tubes are attached radially to the furnace or combustion chamber, the thickness of that portion must be increased by the value of the ligament efficiency (as printed; ligament efficiency is a ratio, so this presumably means the calculated thickness is divided by it; confirm with the Inspecting Authority).
Watch out
- The equations did not extract cleanly. Use the Official text tab and the Gazette page for their exact form.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 122 | Furnaces of Horizontal Boilers | 73% | Chapter III (DPIIT scan), image 3 |
| 221 | Corrugated Furnaces of Horizontal Boilers | 73% | Chapter IV (DPIIT scan), image 14 |
| 592 | Furnaces and Flue Sections of Horizontal Boilers | 73% | Chapter XII (DPIIT scan), image 13 |
Amendment history of the candidate IBR 1950 regulations: Reg. 592 (6 amendments)
IBR 1950 regulation 122 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 122 page for its amendments.
| Reg. 122 FURNACES Furnaces of Horizontal boilers
|
IBR 1950 regulation 221 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 221 page for its amendments.
| Reg. 220, Reg. 221, Reg. 222 FURNACES Plain Furnaces of Horizontal Boilers For plain furnaces or furnaces strengthened by Adamson or other joints or stiffeners of sufficient strength and for the semi-cylindrical tops of fire-boxes and bottom of combustion chambers where the sides are securely stayed, the working pressure shall not exceed the smaller of the values obtained from the following formulae :-
Where d = the external diameter of the furnace or chamber top or bottom in inches t = the thickness of the furnace plate in 32nds of an inch. L = the length of the furnace or other part in inches measured between points of substantial support, i.e. centres of rows of rivets in end seams or commencement of curvature of flange, whichever is applicable. C = 1450 where the longitudinal seams of steel furnaces are welded and 1300 where they are riveted, C = 725 where the longitudinal seams of circular copper fireboxes or furnaces are fitted with double butt straps and 650 where they are lapped, C1 = 50 where the longitudinal seams of steel furnaces are welded and 45 where they are riveted, C1 = 25 where the longitudinal seams of circular copper fireboxes or furnaces are fitted with double butt straps and 22.5 where they are lapped. Reg. 221 FURNACES Corrugated Furnaces of Horizontal Boilers The maximum working pressure to be allowed on corrugated furnaces shall be determined by the following formula -
where D is the least external diameter in inches measured at the bottom of the corrugations on the water side. t is the thickness of the furnace plate in 32nds of an inch measured at the bottom of the corrugation or chamber, C = 480 for the Fox, Morrison, Deighton, Purves,, and other similar furnaces and 510 for the leeds Forge Bulb Suspension Furnace. Reg. 222 FURNACES Plain Furnaces of Vertical Boilers The same formulae as for the plain furnaces of horizontal boilers shall be used, but where the furnaces are tapered the diameter to be taken for calculation purposes shall be the mean of that at the top and of that at the bottom where it meets the substantial support from flange or ring. The length for the same purpose shall be the distance from the centre of the row of rivets connecting the crown and the body of the furnace to the substantial support at the bottom of the furnace, or to a row of screwed stays connecting the furnace to the shell, provided that the pitch of stays at the furnace does not exceed 14 times the thickness of the furnace plate when the stays are riveted at their ends or 16 times when the stays are fitted with nuts. Such screwed stays shall be in diameter over the threads not less than twice the thickness of the furnace plate and in no case less than 3/4" diameter {See Reg.135 (d)}. |
IBR 1950 regulation 592 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 592 page for its amendments.
| Reg. 592 | ||||||
|
| Next >>> |
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 488, Regulation 488, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.792. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.