Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 443. Radiographic examinations
Not yet checked against the official Gazette; verify before relying on it.
443. Radiographic examinations.─ (1) Every portion of the longitudinal and circumferential butt-welded seams of the shell of the boiler shall be subjected to radiographic or ultrasonic examination. Each Longitudinal and circumferential butt welded seams of Furnace, Reversal chamber, Access tube and drop pipes shall be subjected to 10% radiographic examination. The percentage of welds to be examined shall include each intersection of longitudinal and circumferential seams. Where ultrasonic examination is used, it shall be demonstrated to the satisfaction of the Inspecting Authority that the equipment and the technique used are satisfactory. The manufacturer shall ensure that the operator employed is competent to use the equipment, apply the technique and interpret the results of the examination.
(2)The methods employed in obtaining the radiographs shall be such as to show clearly differences equal to 2% of the thickness at the welded joints. To determine whether this result is being attained, an indicator of approved form which includes a portion equivalent to not more than2% of the joint thickness shall be placed in the vicinity of the weld so as to make a record on each radiograph. Each section of every weld shall be marked so that the radiographs can be easily correlated to the particular part of the seam represented.
(3)The examination shall be made from the original films and the acceptability of the welds shall be decided by the Inspecting Authority. The welds deemed unsatisfactory shall be rejected or dealt with under the condition of regulation 434 and can be radiographed again. The films shall be retained by the manufacturer for minimum three years for reference.
Notes: (1) Magnetic Particle Flaw Detection, Magnetic methods of flaw detection shall be employed wherever possible for ferrite steel.
(2)Dye-Penetrate Flaw Detection; Dye-penetrant or equivalent methods of flaw detection shall be employed for Austenitic or other non-magnetic steel.
(3)All butt-welded joints shall be subjected to non-destructive examination by radiographic, radioscopy or other approved methods such as ultrasonic testing, magnetic particle inspection or liquid dye penetrant inspection. When radioscopic examination is to be performed in lieu of radiography on welded components, the following requirements shall be met, namely:-
(a)A written procedure shall be submitted for approval to the Inspecting
Authority which shall contain the following:
(i)material and the thickness range;
(ii)equipment qualifications;
(iii)test object scan plan;
(iv)radioscopic parameters;
(v)image processing parameters;
(vi)image display parameters;
(vii)image archiving requirements;
(viii)accept-reject criteria (Code reference);
(ix)performance evaluation;
(x)Operator identification.
(b)The system shall be aided with an image processor to enhance the quality of the radioscopic images and system performance quality shall exhibit-
(i)a thin section contrast sensitivity of 3%;
(ii)a thick section contrast sensitivity of 2%;
(iii)a spatial resolution of 3 line pairs per mm;
(iv)IQI sensitivity - 2% of the joint thickness when wire IQI's are to be used, the wire diameter axis shall be oriented along the axis of the least sensitivity of the system.
(c)Radioscopes are to be properly marked to co-relate with particular part of joint represented.
(d)The radioscopic examination data shall be recorded and stored on videotape, magnetic disk or optical disk or any other electronic media at the maker's plant for a sufficient period after the date of radioscopic examination as specified by the Inspecting Authority, Efficient radioscopic examination record recall shall be made available at any time over the record retention period and shall be traceable to the test objects.
(e)When repair has been performed as a result of radioscopic examination, the repaired areas shall be re-examined using the same radioscopic technique to evaluate the effectiveness of the repair.
(f)To aid in proper interpretation of the radioscopic examination data, the details of the technique used shall accompany the data. As a minimum, the information shall include the approved procedure requirements and system performance test data.
In short
Sets the radiographic and other non-destructive examination required for welded seams, the image quality needed, and the conditions for using radioscopy instead of film.
Key points
- (1) Every part of the longitudinal and circumferential butt-welded shell seams must be examined by radiography or ultrasonics. Butt seams of the furnace, reversal chamber, access tube and drop pipes need 10% radiographic examination, including each intersection of longitudinal and circumferential seams.
- (1) If ultrasonics is used, the equipment and technique must satisfy the Inspecting Authority, and the manufacturer must ensure the operator is competent.
- (2) Radiographs must show differences equal to 2% of joint thickness, checked with an approved indicator placed near the weld on each radiograph. Each weld section is marked so films can be matched to the seam.
- (3) Films are examined from the originals; the Inspecting Authority decides acceptability. Unsatisfactory welds are rejected or dealt with under regulation 434 and may be radiographed again. The manufacturer keeps the films for at least three years.
- Notes (1)–(2): magnetic methods wherever possible for ferritic steel; dye-penetrant or equivalent for austenitic or other non-magnetic steel.
- Note (3): all butt welds need NDT by radiography, radioscopy or another approved method. Radioscopy in place of radiography needs an approved written procedure (material, equipment, scan plan, parameters, archiving, accept-reject criteria, performance evaluation, operator identification), an image processor, and system performance of 3% thin-section and 2% thick-section contrast sensitivity, 3 line pairs per mm spatial resolution and IQI sensitivity of 2% of joint thickness.
- Note (3): radioscopic images must be marked to the joint; data stored electronically for the period the Inspecting Authority specifies, retrievable and traceable; repaired areas re-examined with the same technique; and technique details must accompany the data.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
No candidate heading found in the historical print edition.
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.



Indian Boiler Regulations, 2026, reg. 443, Regulation 443, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.768–770. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.