BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction

Regulation 489. Furnace components

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 792

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

489.Furnace components.─ The thickness of furnace components, e.g. ash drop-out tubes and fuel inlet connections, shall be calculated in accordance with regulation 488 with a minimum thickness of 10 mm and a maximum thickness of 22 mm.

Referenced provisions

Reg. 488

Independent explanation — not the law · draft · engineer review in progress

In short

Furnace components, such as ash drop-out tubes and fuel inlet connections, are sized with the plain furnace method in regulation 488. Their thickness must be at least 10 mm and no more than 22 mm.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
126Furnace Crown71%Chapter III (DPIIT scan), image 4
IBR 1950 regulation 126 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 126 page for its amendments.

Reg. 126
FURNACES
Furnace Crown

a)

The furnace crown shall be made from one plate and the seam connecting it to the furnace shall not fall in line with any circumferential seam of the boiler shell.

b) The furnace crown may be riveted to the vertical portion of the firebox, or alternatively, the joint may be fusion butt welded by the electric arc process, provided the conditions as to fusion welding in Regulation 125 are observed. Where the joint is to be welded the edges of the furnace crown and the firebox body shall be beveled in accordance with Fig. 3 or Fig. 4. The depth of the flange of the furnace crown plate from the commencement of the curvature of the flanging radius shall be not less than four times the plate thickness with a minimum of 1½ inches. On completion of welding the firebox shall be effectively stress relieved by heat treatment (see also Reg. 128).

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
792
PDF page index
792 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 551fd54eaf7edc83
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 489, Regulation 489, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.792. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.