Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 478. Fire-box crown stays for Loco-type boilers
Not yet checked against the official Gazette; verify before relying on it.
478. Fire-box crown stays for Loco-type boilers.─(1) Where fire-box crown stays are directly attached to a semi-cylindrical outer casing, and the fire-box top is chambered and fitted with stays arranged as shown in Figure 12/94, the thickness of the outer casing shall be sufficient to provide not less than three engaging threads, of which not less than one shall be full thread in stays not normal to the stayed surface, but if the thickness of the plate is not sufficient to give one engaging full thread, the plate shall be reinforced.
(2)Where vertical stays only are used to take part of the load on the fire box top, boilers with shells 1370 mm diameter and over shall be fitted with transverse stays (see Figures 12/95. Stays may be attached as shown in
Figures 12/47, 12/48 and 12/49.
Figures cited in this regulation (5, exact crops of the Gazette)

View Gazette page 808 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 808 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 809 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 825 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)

View Gazette page 825 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
In short
Sets rules for fire-box crown stays in loco-type boilers.
Key points
- (1) Where crown stays attach directly to a semi-cylindrical outer casing and the fire-box top is stayed as in Figure 12/94, the casing must be thick enough for at least three engaging threads, at least one being a full thread for stays not normal to the stayed surface.
- (1) If the plate cannot give one full engaging thread, it must be reinforced.
- (2) Where only vertical stays carry part of the fire-box top load, boilers with shells of 1370 mm diameter and over must have transverse stays (Figure 12/95). Stays may be attached as in Figures 12/47 to 12/49.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 586 | Fire | 100% | Chapter XII (DPIIT scan), image 10 |
IBR 1950 regulation 586 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 586 page for its amendments.
| Reg. 585 a, Reg. 585 b, Reg. 586 | |||||||||||||||||
Reg. 585 b Circumferential stays for circular furnaces and fire-boxes
Reg. 586 Fire-box Crown stays for Loco-type Boilers
| |||||||||||||||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 478, Regulation 478, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.784–785. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.