Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction

Regulation 478. Fire-box crown stays for Loco-type boilers

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 784–785Figure referenced

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

478. Fire-box crown stays for Loco-type boilers.─(1) Where fire-box crown stays are directly attached to a semi-cylindrical outer casing, and the fire-box top is chambered and fitted with stays arranged as shown in Figure 12/94, the thickness of the outer casing shall be sufficient to provide not less than three engaging threads, of which not less than one shall be full thread in stays not normal to the stayed surface, but if the thickness of the plate is not sufficient to give one engaging full thread, the plate shall be reinforced.

(2)Where vertical stays only are used to take part of the load on the fire box top, boilers with shells 1370 mm diameter and over shall be fitted with transverse stays (see Figures 12/95. Stays may be attached as shown in

Figures 12/47, 12/48 and 12/49.

Figures cited in this regulation (5, exact crops of the Gazette)

Gazette Fig. 12/47: Attachment of Firebox and Combustion Chamber Stays
Fig. 12/47Attachment of Firebox and Combustion Chamber Stays
View Gazette page 808 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/48: Attachment of Firebox and Combustion Chamber Stays
Fig. 12/48Attachment of Firebox and Combustion Chamber Stays
View Gazette page 808 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/49: Attachment of Firebox and Combustion Chamber Stays
Fig. 12/49Attachment of Firebox and Combustion Chamber Stays
View Gazette page 809 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
Gazette Fig. 12/94: Arrangement of Firebox Crown Stays for Locomotive Boilers
Fig. 12/94Arrangement of Firebox Crown Stays for Locomotive Boilers
View Gazette page 825 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Gazette Fig. 12/95: Arrangement of Firebox Crown and Transverse Stays for Locotype Boilers
Fig. 12/95Arrangement of Firebox Crown and Transverse Stays for Locotype Boilers
View Gazette page 825 · figure catalogue
Auto-traced outline: SVG · DXF (not to scale, may copy print defects)
Independent explanation — not the law · draft · engineer review in progress

In short

Sets rules for fire-box crown stays in loco-type boilers.

Key points

  • (1) Where crown stays attach directly to a semi-cylindrical outer casing and the fire-box top is stayed as in Figure 12/94, the casing must be thick enough for at least three engaging threads, at least one being a full thread for stays not normal to the stayed surface.
  • (1) If the plate cannot give one full engaging thread, it must be reinforced.
  • (2) Where only vertical stays carry part of the fire-box top load, boilers with shells of 1370 mm diameter and over must have transverse stays (Figure 12/95). Stays may be attached as in Figures 12/47 to 12/49.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
586Fire100%Chapter XII (DPIIT scan), image 10
IBR 1950 regulation 586 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 586 page for its amendments.

Reg. 585 a, Reg. 585 b, Reg. 586

Stays for fire-boxes and circular furnaces

(a) Solid screwed stays

For screw stays to combustion chambers and fire-boxes and for longitudinal and cross stays, the maximum working pressure for the stays is to be calculated from the appropriate one of the following two formulae:-

WP= C         1.28
(D - ------------)²
        N
Equation XII/19
A

WP= C x D1² Equation XII/20
A

WP is the working pressure in pounds per square inch.
D is diameter of stays over threads in inches.
D1 is diameter of body of stay at its smallest part in inches.
N is number of threads of stay per inch.

A is area in square inches supported by one stay for area to be supported by stays near tubes in fire-box tube plates of Loco-type boilers, [see Regulation 193(a)].

C=7,100 for steel or special wrought iron screw stays to combustion chamber or fire-boxes,
C=8,640 for steel longitudinal or cross stays fitted with nuts.
   =4,700 for copper stays.

Where stays are made with enlarged ends and the body of the stay is smaller in diameter than at the bottom of the thread the working pressure shall be calculated from the second formula.


Reg. 585 b

Circumferential stays for circular furnaces and fire-boxes

The diameter of the stay shall be not less than ¾ inch or twice the thickness of the fire-box plate, whichever is the greater. In the case of screwed threads the diameter shall be measured over the threads.

The pitch of the stays at the fire-box shall not exceed 14 times the thickness of the fire-box plate.


Reg. 586

Fire-box Crown stays for Loco-type Boilers

Where fire-box crown stays are directly attached to a semi-cylindrical outer casing, and the fire-box top is cambered and fitted with stays arranged as shown in Figure XII/78, the thickness of the outer casing shall be sufficient to provide not less than three engaging threads, of which not less than one shall be full thread in stays not normal to the stayed surface, but if the thickness of the plate is not sufficient to give one engaging full thread the plate shall be reinforced.

Where vertical stays only are used to take part of the load on the fire-box top, boilers with shells 4 feet and 6 inches diameter and over shall be fitted with transverse stay (see Figure XII/79). Stays may be attached as shown in Figures XII/39, XII/40 and XII/41.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
784–785
PDF page index
784–785 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 32989bd7df834f69
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 478, Regulation 478, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.784–785. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.