Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 434. Repairs to welded seams
Not yet checked against the official Gazette; verify before relying on it.
434. Repairs to welded seams.─ (1) Any repair to a weld carried out by the manufacturer shall first be agreed to by the Competent person.
(2)(a)Where defects are distributed over the whole length of the seam, the total length of the portions which may be cut from any one longitudinal or circumferential seam to remove all defects shall not exceed 15 percent of the total length of the seam.
(b)When, however, the defects are all located in a single continuous length which may be cut out to remove all defects shall not exceed 10 percent of the total length of the seam.
(3)Defect shall be cut out by chipping, machining or other approved methods.
(4)In the case of Class I boilers, all repaired areas shall be subjected to radiographic examination.
In short
Controls who approves weld repairs, how much of a welded seam may be cut out, and how repairs are checked.
Key points
- (1) Any weld repair by the manufacturer must first be agreed to by the Competent Person.
- (2)(a) Where defects are spread over the whole seam, the total length cut out from any one longitudinal or circumferential seam must not exceed 15 percent of the seam length.
- (2)(b) Where all defects lie in a single continuous length, that length must not exceed 10 percent of the seam length.
- (3) Defects are cut out by chipping, machining or other approved methods.
- (4) For Class I boilers, all repaired areas must be radiographically examined.
Watch out
- The limit is lower when the defects are in one continuous length than when they are spread along the seam.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
No candidate heading found in the historical print edition.
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 434, Regulation 434, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.766. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.