Regulation 504. Safety valves

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 797

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

504.Safety valves.─ Boiler shall be provided safety valves complying with regulations 192 to 219, with following changes:-

(i)The safety valves shall be reset at a pressure at least 2.5% below, but not more than 5% below the safety valve set pressure.

(ii)The 5% limit is increased to 10% for valves having a body seat bore less than 32 mm and or having a set pressure of 24 bar gauge or less.

Referenced provisions

Reg. 192 · Reg. 219

Independent explanation — not the law · draft · engineer review in progress

In short

Boilers under this chapter must have safety valves that meet regulation 192 to regulation 219, with two changes to the reset (blowdown) rule.

Key points

  • (i) The safety valve must reset at least 2.5% below, but not more than 5% below, its set pressure.
  • (ii) The 5% limit becomes 10% for valves with a body seat bore under 32 mm and/or a set pressure of 24 bar gauge or less.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
324Safety Devices74%Chapter VI (DPIIT scan), image 8
IBR 1950 regulation 324 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 324 page for its amendments.

Reg. 321, Reg. 322, Reg. 323, Reg. 324, Reg. 325, Reg. 326

Drains

A drain cock or valve with a suitable discharge pipe shall be fitted to each water gauge.


Reg. 322

Protectors

Where tubular glass water gauges are fitted, substantial protectors shall be provided. The glass shall be suitable treated to prevent splintering.


Reg. 323

Glass size

Tubular water gauge glasses shall be not less than ½ inch and not more than 3/4 inch outside diameter.


Reg. 324

Safety Devices


Water gauge glass mountings shall be fitted with self-closing devices in the bottom arm and it is recommended that a similar device should be fitted in the top arm.


Reg. 325

Gauge columns


Where the gauges are mounted on a column there shall be no connecting passage between the top and bottom arms of the column unless valves or cocks are fitted between the columns and the boiler.


Reg. 326

Isolating Cocks


Where isolating cocks or valves connecting water gauge pipes to the boiler are fitted, they shall be not less than 1 inch bore and of the bolted cover type with separate packing gland.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
797
PDF page index
797 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 53628dcabf2d226e
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 504, Regulation 504, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.797. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.