Regulation 495. Plain furnaces of vertical boilers

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 794Formula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

495. Plain furnaces of vertical boilers.─ (1) The maximum allowable working pressure of plain furnaces of vertical boilers shall be the lesser of the two values obtained by Equations (12/23) and (12/24).

Where, external diameter of the fire-box in mm. Where the firebox is tapered the diameter taken shall be D = the mean of that at the top and at the bottom where it meets the substantial support from the flange or ring,

L = is length of the firebox in mm between points of substantial support measured from the commencement of flange curvature or from the foundation connection, or from a row of screwed stays which comply with regulation 416 and sub-regulation (3) of regulation 477, whichever is applicable.

(2)The thickness shall be not greater than 22 mm and shall be not less than 10 mm.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Referenced provisions

Reg. 416 · Reg. 477

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 495 sets the maximum allowable working pressure of plain furnaces in vertical boilers. It uses the lesser of the values from Equations (12/23) and (12/24) in regulation 488, and limits thickness to between 10 mm and 22 mm.

Key points

  • (1) Diameter D: the external diameter of the firebox. For a tapered firebox, take the mean of the diameters at the top and at the bottom where it meets the substantial support from the flange or ring.
  • (1) Length L: the firebox length between points of substantial support. Measure it from the commencement of flange curvature, the foundation connection, or a row of screwed stays complying with regulation 416 and sub-regulation (3) of regulation 477, as applicable.
  • (2) Thickness: not greater than 22 mm and not less than 10 mm.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
596Foundations of Vertical Boiler Furnaces85%Chapter XII (DPIIT scan), image 14
595Hemispherical Furnacesof Vertical Boilers80%Chapter XII (DPIIT scan), image 14
122Furnaces of Horizontal Boilers78%Chapter III (DPIIT scan), image 3
IBR 1950 regulation 596 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 596 page for its amendments.

Reg. 596, Reg. 597

Foundations of Vertical Boilers Furnaces

When circular furnaces of fireboxes of vertical boilers are not connected to the shell crown by uptake tube, smoke tubes or bolt stays and the whole load on the firebox vertically is borne by the bottom part of the firebox where it is connected to the shell the working pressure for the part, if firebox is joggled out to meet the shell or if any ogee ring is fitted, shall not exceed that found by the following formula:-

W.P. = C(t-1)² Equation XII/31
D(D-D1)

W.P. is working pressure in pounds per square inch.
t is thickness of the joggled firebox plate or ogee ring in thirty seconds of an inch.
D is inside diameter of the boiler shell in inches.
D1 is outside diameter of the joggled firebox at the commencement of curvature
Above joggled part or the outside diameter of the firebox where it joins the ogee ring.
C = 140 for Ogee rings (see Fig XII/26 and XII/27.
C = 100 where ‘U’ ring section is used (see Fig. XII/28)


Reg. 597

Foundations of Loco-type Boiler Fireboxes

Where the firebox roof in loco-type boilers is, not stayed direct to the external casing crown or to girders carried by the casing or if not connected to the casing by slings the working pressure for the parts, if plates are joggled out to meet the casing or if an ogee ring is fitted, shall not exceed that found by the following formula:-

W.P. = 70 (t-1) x (L+W)
Equation XII/32
L+W(W-W1)

WP is working pressure in pounds per square inch.
t  is thickness of the joggled firebox side plates or fire hole plate (whichever is less) or ogee ring in thirty seconds of an inch.
L  is length of firebox casing in inches measured between the water sides of front end plate and saddle plate at the foundation seam.
W  is width of firebox casing in inches measured between the water side of casing side plates at the foundation seam.
W1  is width of firebox in inches measured between the water sides of firebox side plates at the commencement of curvature above joggled part or where it joins the ogee ring.


Where only a comparatively narrow strip of the firebox roof is stayed directly to the casing crown the area so stayed shall be deducted from the area represented by LXW in the bottom line of the formula thus:

(L X W – A)(W-W1) and so used in Equation XII/32 in determining the working pressure for the parts, “A” being the area in square inches of the part of roof supported by the casing crown.
IBR 1950 regulation 595 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 595 page for its amendments.

Reg. 593, Reg. 594, Reg. 595

Plain Furnaces of Vertical Boilers

The maximum working pressure of Plain Furnaces of Vertical boilers shall be the lesser of the two values obtained by Equations XII/25 and XII/26.

Where,

D = external diameter of the firebox in inches. Where the firebox is tapered the diameter taken shall be the mean of that at the top and at the bottom where it meets the substantial support from the flange or ring.

L is length of the firebox in inches between points of substantial support measured from the commencement of flange curvature or from the foundation connection, or from a row of screwed stays which comply with Regulations 550(b), 585(b), whichever is applicable.

In no case, however, shall the thickness be more than 7/8 inch. For fireboxes under 2 feet and 6 inches in diameter, the thickness shall be not less than 5/16 inch and for fireboxes 2 feet and 6 inches in diameter and over the thickness shall be not less than 3/8 inch.


Reg. 594

Corrugated Fireboxes of Vertical Boilers

For the semi-spirally corrugated fireboxes of ‘Sentinel’ standard motor wagon boilers the working pressure shall be determined by the following formula-

W.P. = C(t-1) Equation XII/29
D

W.P. is working pressure in pounds per square inch.
t is thickness of the firebox plate in thirty seconds of an inch.
D is mean of the external diameters of firebox measured over the plain part at each end at commencement of curvature of flange.
C = 390.

No corrugated furnace shall be less than 3/8 inch thick.
 

Reg. 595

Hemispherical Furnaces of Vertical Boilers

When furnaces are hemispherical in form and subject to pressure on the convex side and are without support from stays of any kind the maximum working pressure shall be found by the following formula:-

W.P. = 275(t-1) Equation XII/30
R

W.P. is working pressure in pounds per square inch.
t is thickness of the top plate in thirty seconds of an inch.
R is outer radius of curvature of the furnace in inches.
The thickness of these furnaces shall in no case exceed 7/8 inch
IBR 1950 regulation 122 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 122 page for its amendments.

Reg. 122
FURNACES
Furnaces of Horizontal boilers

a) The sections of the internal flues shall each be in one plate and shall be bent while cold to circular form and shall be welded longitudinally.
b) The maximum permissible variation in diameter at any cross section shall not exceed the thickness of the plate.
c) The weld shall be placed at the lower part of the flues, and shall break joint in successive sections by at least 12 inches.
d) Each flange for the circular seams shall be formed at one heat by suitable machinery.
e) The sections shall be allowed to cool gradually to avoid internal stresses.
f) The caulking edges of all flue flanges shall be machined or machine gas cut.
g The circular seams shall be arranged so that they do not fall in line with those of the adjacent flue or with the circumferential seams of the shell and are at least 6 inches apart.
h) When flues are flanged for attachment to both end plates the total length of each completed flue shall not exceed the length of the shell measured from the inner surface of the back end plate to the inner surface of the front end plate, both adjacent to the shell.
i) Where the flues are flanged for attachment to the end plates, the end sections shall be 1/16 inch thicker than the remaining sections, except in cases where the calculated thickness is over 13/16 inch, when the end section shall be 7/8 inch in thickness.
j) The flanged portion of furnace rings shall have radius of curvature of not less than 1 inch on water side.
k) Sections of corrugated flues may be fusion butt welded circumferentially and afterwards stress relieved by heat treatment.
l) As an alternative to Adamson flanges, furnaces which are partly fitted with corrugated sections shall be strengthened by means of suitable stiffening rings adequately welded to the furnaces. The moment of inertia of the stiffener shall be not less than that required by Regulation 592(b). In no case shall a flat stiffener be less than 63 mm. x 13 mm. (2½” x ½”).

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
794
PDF page index
794 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 3df78c16c131b484
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 495, Regulation 495, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.794. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.