Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 427. Attachment of pads
Not yet checked against the official Gazette; verify before relying on it.
427.Attachment of pads.─(1) Pads welded to the shell or end plate shall be welded internally and externally.
(2)Methods of attachment of pads shall be as shown in Figures 12/115, 12/116 or 12/117. Where the bore of the seating does not exceed 127 mm or the diameter of the opening in the shell does not exceed 127 mm plus twice the thickness of the plate to which it is attached, the pad may be welded to the plate without subsequent heat-treatment of the welds so made. If these limits are exceeded the whole plate to which the pad is attached shall be stress relieved by heat-treatment on completion of welding.
Figures cited in this regulation (3, exact crops of the Gazette)

View Gazette page 832 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 832 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 832 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
In short
Sets how pads are welded to the shell or end plate and when heat treatment is needed afterwards.
Key points
- (1) Pads welded to the shell or end plate must be welded both internally and externally.
- (2) Methods of attachment are shown in Figures 12/115, 12/116 and 12/117.
- (2) If the bore of the seating is not more than 127 mm, or the shell opening is not more than 127 mm plus twice the plate thickness, the pad may be welded on without later heat treatment of those welds.
Watch out
- If those limits are exceeded, the whole plate to which the pad is attached must be stress relieved by heat treatment on completion of welding.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 411 | Pads | 100% | Chapter X (DPIIT scan), image 4 |
| 600 | Pads Welded to shell or the attachment of Flanged Mountings | 100% | Chapter XII (DPIIT scan), image 15 |
| 633 | End plate attachments | 72% | Chapter XV (DPIIT scan), image 3 |
IBR 1950 regulation 411 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 411 page for its amendments.
| Reg. 410, Reg. 411, Reg. 412
Reg. 411
Reg. 412
|
IBR 1950 regulation 600 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 600 page for its amendments.
| Reg. 598, Reg. 599, Reg. 600, Reg. 601 | ||||||||||||||||||||||||||||||||||||||||||||||
Reg. 599 Cross Tubes
Reg. 600 Pads Welded to shell or the attachment of Flanged Mountings
Reg. 601
| ||||||||||||||||||||||||||||||||||||||||||||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 427, Regulation 427, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.764. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.