472. Pitch of Tubes.─ The spacing of tube holes shall be calculated as per either of the methods given below:

(i)The spacing of tube holes shall be calculated such that the minimum width (in mm) of any ligament between the tube holes shall be not less than:
𝐷
8 + 12.7

Where D is diameter of tube hole in mm.

(ii)The thickness and cross-section of the plate between the tube holes shall be not less than:

0.125D + 5.08 = minimum thickness in mm,

4.318D + 16.13 = minimum cross-section in mm2,

(iii)Spacing of tube hole = minimum cross-section in square mm / provided tube plate thickness. Where, D is diameter of the tube hole in mm.

In no case shall the minimum thickness of any tube plate in the tube area be less than following limits: T= 13 mm, where the diameter of the tube hole does not exceed 51 mm.

T = 14 mm, where the diameter of the tube hole is greater than 51 mm.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Independent explanation — not the law · draft · engineer review in progress

In short

Sets how tube hole spacing in tube plates is worked out, and the minimum tube plate thickness in the tube area.

Key points

  • (i) Ligament method: the minimum ligament width between tube holes must be at least D/8 + 12.7 (mm), where D is the tube hole diameter in mm.
  • (ii) Section method: the plate between holes must have a minimum thickness of 0.125D + 5.08 mm and a minimum cross-section of 4.318D + 16.13 mm2.
  • (iii) Spacing of tube holes = minimum cross-section ÷ provided tube plate thickness.
  • Minimum tube plate thickness in the tube area: 13 mm where the tube hole diameter does not exceed 51 mm; 14 mm where it is greater than 51 mm.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
580Pitch of tubes100%Chapter XII (DPIIT scan), image 9
631Tubes100%Chapter XV (DPIIT scan), image 3
147Screw Threads of Stay Tubes73%Chapter III (DPIIT scan), image 7
IBR 1950 regulation 580 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 580 page for its amendments.

Reg. 580, Reg. 581

Pitch of tubes

The spacing of tube holes shall be such that the minimum width in inches of any ligament between the tube holes shall be not less than:-

D + ½
8

alternatively,

the thickness and cross-section of the plate between the tube holes shall be not less than

0.125D+0.2=minimum thickness in inches.
0.17D+0.025=minimum cross-section in square inches where D is diameter of the tube holes in inches.

In no case shall the minimum thickness of any tube plate in the tube area be less than the following limits:-

T=1/2 inch, Where the diameter of the tube holes does not exceed 2 inches.
T=9/16 inch, Where the diameter of the tube hole is greater than 2 inches.



Reg. 581

Stay tubes

Stay tubes shall be of steel seamless or electrically resistance welded.
a) Minimum thickness of stay tubes – The minimum thickness of stay tubes shall be as per regulation 148.
b) The maximum working pressure for screwed in stay tube shall be calculated by the following formula:

WP = 5900         1.28
[(D---------------/N )² - D1²]
Equation XII/16
A

D is diameter of the stay tube over threads in inches.
D1 is internal diameter of the tubes under the threads in inches.
N is number of threads per inch.

A is the area in square inches supported by one Stay tube, measured from centre to centre of stay tubes. When the area contains tubes or parts of tubes their aggregate area, calculated from their smallest external diameter of body when in tension and smallest internal diameter when in compression, shall be deducted from the area of the containing figure and the remainder used as A in the formula.

Where stay tubes have their thickness increased at the screwed, ends to provide for plus threads the increased thickness shall be obtained by up-setting and not by welding, and the tubes shall be subsequently annealed.

Stay tubes may be attached to the tube plates either by screwing or by metal arc welding.

Where stay tubes are screwed into the tube plates they shall be screwed with a continuous thread not finer than 11 threads per inch at both ends and shall be expanded into the tube plates, by roller expander and, if desired, may be seal welded.

Welded attachment of stay tubes be as shown in Figure XII/67,XII/67A,XII/68, ,XII/68A and XII/69.
IBR 1950 regulation 147 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 147 page for its amendments.

Reg. 147
STAY TUBES
Screw Threads of Stay Tubes

a) Stay tubes shall be screwed at both ends with continuous threads, and the holes in the tube plates shall be tapped with continuous threads. The pitch of the threads shall not be finer than 11 threads per inch. The stay tubes shall be expanded by roller expanders and not made tight by caulking only.
b) Stay tubes may be attached by welding in which case they shall not be adjacent within the same tube next except in local areas, where not more than two adjacent stay tubes may be attached by welding. The form of attachment shall be such that there is a mechanical hold in addition to the welding, as shown in Figure 9A. On completion of welding the stay tubes shall be lightly re-expanded.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
781–782
PDF page index
781–782 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 4172776ecc340d35
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 472, Regulation 472, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.781–782. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.