Indian Boiler Regulations, 2026 · Chapter 12 · Shell Type Boilers of Welded Construction
Regulation 472. Pitch of Tubes
Not yet checked against the official Gazette; verify before relying on it.
472. Pitch of Tubes.─ The spacing of tube holes shall be calculated as per either of the methods given below:
(i)The spacing of tube holes shall be calculated such that the minimum width (in mm) of any ligament between the tube holes shall be not less than:
𝐷
8 + 12.7
Where D is diameter of tube hole in mm.
(ii)The thickness and cross-section of the plate between the tube holes shall be not less than:
0.125D + 5.08 = minimum thickness in mm,
4.318D + 16.13 = minimum cross-section in mm2,
(iii)Spacing of tube hole = minimum cross-section in square mm / provided tube plate thickness. Where, D is diameter of the tube hole in mm.
In no case shall the minimum thickness of any tube plate in the tube area be less than following limits: T= 13 mm, where the diameter of the tube hole does not exceed 51 mm.
T = 14 mm, where the diameter of the tube hole is greater than 51 mm.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Sets how tube hole spacing in tube plates is worked out, and the minimum tube plate thickness in the tube area.
Key points
- (i) Ligament method: the minimum ligament width between tube holes must be at least D/8 + 12.7 (mm), where D is the tube hole diameter in mm.
- (ii) Section method: the plate between holes must have a minimum thickness of 0.125D + 5.08 mm and a minimum cross-section of 4.318D + 16.13 mm2.
- (iii) Spacing of tube holes = minimum cross-section ÷ provided tube plate thickness.
- Minimum tube plate thickness in the tube area: 13 mm where the tube hole diameter does not exceed 51 mm; 14 mm where it is greater than 51 mm.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 580 | Pitch of tubes | 100% | Chapter XII (DPIIT scan), image 9 |
| 631 | Tubes | 100% | Chapter XV (DPIIT scan), image 3 |
| 147 | Screw Threads of Stay Tubes | 73% | Chapter III (DPIIT scan), image 7 |
IBR 1950 regulation 580 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 580 page for its amendments.
| Reg. 580, Reg. 581 | |||||||||||||||||
Reg. 581 Stay tubes
| |||||||||||||||||
IBR 1950 regulation 147 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 147 page for its amendments.
| Reg. 147 STAY TUBES Screw Threads of Stay Tubes
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 472, Regulation 472, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.781–782. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.