Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 580 — Pitch of tubes
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 581. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 580, Reg. 581 | |||||||||||||||||
Reg. 581 Stay tubes
| |||||||||||||||||
Earlier text: the 2008 DIPP web edition
Pitch of tubes
The spacing of tube holes shall be such that the minimum width in inches of any ligament between the tube holes shall be not less than:-
D
+ ½
8
alternatively,
the thickness and cross-section of the plate between the tube holes shall be not less than
0.125D+0.2=minimum thickness in inches. 0.17D+0.025=minimum cross-section in square inches where D is diameter of the tube holes in inches.
In no case shall the minimum thickness of any tube plate in the tube area be less than the following limits:-
T=¹/2 inch, Where the diameter of the tube holes does not exceed 2 inches.
T=9/16 inch, Where the diameter of the tube hole is greater than 2 inches.
Possible IBR 2026 successors (heading match, unverified): Reg. 47, Reg. 117, Reg. 124, Reg. 243, Reg. 370, Reg. 371, Reg. 374, Reg. 472