Regulation 371. Maximum allowable working pressure of tubes

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 747

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

371. Maximum allowable working pressure of tubes.─ The maximum allowable working pressure of the tubes shall be calculated as per sub-regulation (1) of regulation 244, but the working metal temperature shall be taken as the maximum water temperature for which the part of the elements is designed plus 11°C.

Referenced provisions

Reg. 244

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 371 says the maximum allowable working pressure of economiser tubes is calculated by sub-regulation (1) of regulation 244. The working metal temperature used is the maximum water temperature for which that part is designed plus 11°C.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
631Tubes100%Chapter XV (DPIIT scan), image 3
434Determination of Working Pressure73%Chapter X (DPIIT scan), image 9
580Pitch of tubes73%Chapter XII (DPIIT scan), image 9
IBR 1950 regulation 434 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 434 page for its amendments.

Reg. 431, Reg. 432, Reg. 433, Reg. 434
TESTS FOR CLASS II FUSION WELDED SEAMS

Bolts, nuts and studs shall comply with Regulation 208.



Reg. 432
TESTS FOR CLASS II FUSION WELDED SEAMS

Seatings and mountings shall comply with Regulation 409.



Reg. 433
TESTS FOR CLASS II FUSION WELDED SEAMS

Hydraulic Test

The requirement of Hydraulic Test shall comply with regulation 379(a).



Reg. 434
SEAMLESS SHELL BOILERS

Determination of Working Pressure

The working pressure shall be determined in accordance with Regulation 425 except that the minimum thickness of the shell shall comply with the following table:-

Internal diameter inches Minimum thickness inches
Upto and including 24 1/4
Over 24 up to and including 36 5/16
Over 36 3/8

In no case shall the factor of safety of the cylindrical shell and ends be less than 4.

The value of C in the equation shall be taken as 35. Where the ends are welded to shell or mechanically secured and welded they shall be stress-relieved.
IBR 1950 regulation 580 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 580 page for its amendments.

Reg. 580, Reg. 581

Pitch of tubes

The spacing of tube holes shall be such that the minimum width in inches of any ligament between the tube holes shall be not less than:-

D + ½
8

alternatively,

the thickness and cross-section of the plate between the tube holes shall be not less than

0.125D+0.2=minimum thickness in inches.
0.17D+0.025=minimum cross-section in square inches where D is diameter of the tube holes in inches.

In no case shall the minimum thickness of any tube plate in the tube area be less than the following limits:-

T=1/2 inch, Where the diameter of the tube holes does not exceed 2 inches.
T=9/16 inch, Where the diameter of the tube hole is greater than 2 inches.



Reg. 581

Stay tubes

Stay tubes shall be of steel seamless or electrically resistance welded.
a) Minimum thickness of stay tubes – The minimum thickness of stay tubes shall be as per regulation 148.
b) The maximum working pressure for screwed in stay tube shall be calculated by the following formula:

WP = 5900         1.28
[(D---------------/N )² - D1²]
Equation XII/16
A

D is diameter of the stay tube over threads in inches.
D1 is internal diameter of the tubes under the threads in inches.
N is number of threads per inch.

A is the area in square inches supported by one Stay tube, measured from centre to centre of stay tubes. When the area contains tubes or parts of tubes their aggregate area, calculated from their smallest external diameter of body when in tension and smallest internal diameter when in compression, shall be deducted from the area of the containing figure and the remainder used as A in the formula.

Where stay tubes have their thickness increased at the screwed, ends to provide for plus threads the increased thickness shall be obtained by up-setting and not by welding, and the tubes shall be subsequently annealed.

Stay tubes may be attached to the tube plates either by screwing or by metal arc welding.

Where stay tubes are screwed into the tube plates they shall be screwed with a continuous thread not finer than 11 threads per inch at both ends and shall be expanded into the tube plates, by roller expander and, if desired, may be seal welded.

Welded attachment of stay tubes be as shown in Figure XII/67,XII/67A,XII/68, ,XII/68A and XII/69.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
747
PDF page index
747 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 87430340762724c6
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 371, Regulation 371, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.747. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.