361. Hydraulic test for new economisers.─(1) The hydraulic test for all new economisers shall be conducted as per
Table11/1 given below,─
Table 11/1
| Serial No. | On components before assembly | Maximum allowable working pressure in kg/cm2 (g) | Hydraulic test pressure in kg/cm2 (g) |
| (1) | (2) | (3) | (4) |
| 1. | Cast Iron tubes, headers and bends | Twice Maximum allowable working pressure. Minimum pressure 49. | |
| 2. | Steel tubes and bends | 35 or less | 70 |
| 3. | Steel tubes and bends | Above 35 but not exceeding 70 | Twice the Maximum allowable working pressure |
| 4. | Steel tubes and bends | Above 70 | 70 above the Maximum allowable working pressure |
| 5. | Headers | Below 70 | Twice the Maximum allowable working pressure |
| 6. | Headers | Above 70 | Maximum allowable Working pressure plus 70 kg/cm2 (g) |
Table structure read from the Gazette PDF, page 743. Verification status as for the text above.
Show original extracted text (diagnostic, not authoritative)
Serial No. On components before Maximum allowable Hydraulic test pressure in
assembly
(1) working pressure in kg/cm2 (g)
1. (2)
2. Cast Iron tubes, headers kg/cm2 (g)
3. and bends
Steel tubes and bends (3) (4)
4.
Twice Maximum allowable working pressure.
5.
Minimum pressure 49.
6.
35 or less 70
Steel tubes and bends Above 35 but not Twice the Maximum allowable
exceeding 70 working pressure
Steel tubes and bends Above 70 70 above the Maximum
allowable working pressure
Headers Below 70 Twice the Maximum allowable
working pressure
Headers Above 70 Maximum allowable Working
pressure plus 70 kg/cm2 (g)
(2) For all assembled sections, the hydraulic test pressure shall not be less than 1.5 times of the maximum
allowable working pressure.(3)Maximum allowable working pressure shall be the highest pressure at which the economiser relief valves are to be set.
(4)The above test pressure shall be held for a minimum period of ten minutes.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 361 sets the hydraulic test pressures for new economisers: one set for components before assembly (Table 11/1), and a minimum for assembled sections.
Key points
- (1) Components before assembly are tested to Table 11/1. In outline:
- Cast iron tubes, headers and bends: twice the maximum allowable working pressure, with a minimum pressure of 49 kg/cm² (g).
- Steel tubes and bends: 70 kg/cm² (g) where the maximum allowable working pressure is 35 or less; twice the maximum allowable working pressure above 35 but not exceeding 70; and 70 above the maximum allowable working pressure where it is above 70.
- Headers: twice the maximum allowable working pressure below 70; maximum allowable working pressure plus 70 kg/cm² (g) above 70.
- (2) Assembled sections: test pressure not less than 1.5 times the maximum allowable working pressure.
- (3) The maximum allowable working pressure is the highest pressure at which the economiser relief valves are to be set.
- (4) Hold the test pressure for a minimum of ten minutes.
Watch out
- The table layout in the extracted text is broken. Check the Official text tab and the Gazette page for the exact rows and values.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 56 | Hydraulic Test | 100% | Chapter II (DPIIT scan), image 10 |
| 72 | Hydraulic Test | 100% | Chapter II (DPIIT scan), image 14 |
| 504 | Hydraulic test for new economisers | 100% | Chapter XI (DPIIT scan), image 2 |
Amendment history of the candidate IBR 1950 regulations: Reg. 56 (3 amendments)
IBR 1950 regulation 56 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 56 page for its amendments.
| Reg. 56 MATERIALS OF CONSTRUCTION SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE Hydraulic Test |
| (i) Each pipe shall be tested by the manufacturer and shall withstand a hydraulic pressure to one and half times the design pressure but not greater than pressure calculated by the following formula given below. In the absence of working pressure is indicated in the Test Certificate then the tested pressure indicated in the Test Certificate divided by 1.5 shall be the maximum working pressure P = 2 S t / d where P = test pressure D = specified outside diameter of the pipe t = specified wall thickness of the pipe S = stress which shall be taken as 40% of the minimum tensile strength at room temperature. (ii) Notwithstanding anything contained in the above clause, the hydraulic test at the maker's works may be dispensed with provided that the pipes are subject to non destructive testing by an appropriate method like Ultrasonic or Eddy current or stray flux testing |
IBR 1950 regulation 504 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 504 page for its amendments.
| Reg. 502, Reg. 503, Reg. 504 ECONOMISERS | ||||||||||||||
| ||||||||||||||
|
ECONOMISERS | ||||||||||||||
| ||||||||||||||
|
ECONOMISERS | ||||||||||||||
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 361, Regulation 361, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.743. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.