361. Hydraulic test for new economisers.─(1) The hydraulic test for all new economisers shall be conducted as per

Table11/1 given below,─

Table 11/1

Serial No.On components before
assembly
Maximum allowable
working pressure in
kg/cm2 (g)
Hydraulic test pressure in
kg/cm2 (g)
(1)(2)(3)(4)
1.Cast Iron tubes, headers
and bends
Twice Maximum allowable working pressure.
Minimum pressure 49.
2.Steel tubes and bends35 or less70
3.Steel tubes and bendsAbove 35 but not
exceeding 70
Twice the Maximum allowable
working pressure
4.Steel tubes and bendsAbove 7070
above
the
Maximum
allowable working pressure
5.HeadersBelow 70Twice the Maximum allowable
working pressure
6.HeadersAbove 70Maximum allowable Working
pressure plus 70 kg/cm2 (g)

Table structure read from the Gazette PDF, page 743. Verification status as for the text above.

Show original extracted text (diagnostic, not authoritative)
Serial No.         On components before      Maximum allowable    Hydraulic test pressure in
                   assembly
         (1)                                 working pressure in  kg/cm2 (g)
     1.                           (2)
     2.            Cast Iron tubes, headers  kg/cm2 (g)
     3.            and bends
                   Steel tubes and bends                 (3)                         (4)
     4.
                                             Twice Maximum allowable working pressure.
     5.
                                                               Minimum pressure 49.
     6.
                                             35 or less           70

                   Steel tubes and bends     Above 35 but not     Twice the Maximum allowable
                                             exceeding 70         working pressure

                   Steel tubes and bends     Above 70             70 above the Maximum
                                                                  allowable working pressure

                   Headers                   Below 70             Twice the Maximum allowable
                                                                  working pressure

                   Headers                   Above 70             Maximum allowable Working
                                                                  pressure plus 70 kg/cm2 (g)

          (2) For all assembled sections, the hydraulic test pressure shall not be less than 1.5 times of the maximum
allowable working pressure.

(3)Maximum allowable working pressure shall be the highest pressure at which the economiser relief valves are to be set.

(4)The above test pressure shall be held for a minimum period of ten minutes.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 361 sets the hydraulic test pressures for new economisers: one set for components before assembly (Table 11/1), and a minimum for assembled sections.

Key points

  • (1) Components before assembly are tested to Table 11/1. In outline:
  • Cast iron tubes, headers and bends: twice the maximum allowable working pressure, with a minimum pressure of 49 kg/cm² (g).
  • Steel tubes and bends: 70 kg/cm² (g) where the maximum allowable working pressure is 35 or less; twice the maximum allowable working pressure above 35 but not exceeding 70; and 70 above the maximum allowable working pressure where it is above 70.
  • Headers: twice the maximum allowable working pressure below 70; maximum allowable working pressure plus 70 kg/cm² (g) above 70.
  • (2) Assembled sections: test pressure not less than 1.5 times the maximum allowable working pressure.
  • (3) The maximum allowable working pressure is the highest pressure at which the economiser relief valves are to be set.
  • (4) Hold the test pressure for a minimum of ten minutes.

Watch out

  • The table layout in the extracted text is broken. Check the Official text tab and the Gazette page for the exact rows and values.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
56Hydraulic Test100%Chapter II (DPIIT scan), image 10
72Hydraulic Test100%Chapter II (DPIIT scan), image 14
504Hydraulic test for new economisers100%Chapter XI (DPIIT scan), image 2

Amendment history of the candidate IBR 1950 regulations: Reg. 56 (3 amendments)

IBR 1950 regulation 56 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 56 page for its amendments.

Reg. 56
MATERIALS OF CONSTRUCTION

SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE

 Hydraulic Test

(i) Each pipe shall be tested by the manufacturer and shall withstand a hydraulic pressure to one and half times the design pressure but not greater than pressure calculated by the following formula given below.  In the absence of working pressure is indicated in the Test Certificate then the tested pressure indicated in the Test Certificate divided by 1.5 shall be the maximum working pressure 

P = 2 S t / d                          

where     P = test pressure

                D = specified outside diameter of the pipe

                t = specified wall thickness of the pipe

S = stress which shall be taken as 40% of the minimum tensile strength at room temperature.

(ii)  Notwithstanding anything contained in the above clause, the hydraulic test at the maker's works may be dispensed with provided that the pipes are subject to non destructive testing by an appropriate method like Ultrasonic or Eddy current or stray flux testing

IBR 1950 regulation 504 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 504 page for its amendments.

Reg. 502, Reg. 503, Reg. 504
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

ECONOMISERS

Modification of formula

Where no certificates are produced, the working pressure as found by formula will be reduced by 10%. When the workmanship is, however, in any way doubtful and the Chief Inspector is not satisfied that any of the foregoing conditions would be sufficient to meet the circumstances he may at his discretion reduce the working pressure by such percentage as he deems fit.



Reg. 503
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

ECONOMISERS

Maker’s Certificates for Steel Economisers

The Maker shall furnish the Inspecting Officer with a certificate in the following form:-

“We hereby certify that the material described below has been made by the Open Hearth or an Electric process acid/basic and has been satisfactorily tested in the presence of the Inspecting Officer/our Test House Manager in accordance with the Standard Tests.”



Reg. 504
STANDARD CONDITIONS FOR THE DESIGN AND CONSTGRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

ECONOMISERS

Hydraulic test for new economisers

For all new economisers the hydraulic test must be applied as shown below:-

On Components before assembly
Design pressure lbs/sq. in.
Hydraulic test pressure lbs./sq.in.
Cast iron tubes, headers and bends
Twice working pressure minimum pressure, 700.

Steel tubes and bends

500 or less

Above 500 but not exceeding 1,000

Above, 1000

1,000

Twice the working pressure

1,000 above the working pressure.

Headers Below 1,000

Above 1,000

Twice the working pressure.

Working pressure plus 1,000 lbs./sq.in.

For all assembled sections the Hydraulic Test pressure shall be not less than 1 ½ times the working pressure.

“Working pressure” shall be the highest pressure at which the economiser relief valves are to be set.

The above test pressure shall be held for a minimum period of ten minutes.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
743
PDF page index
743 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash ca8f309673c38401
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 361, Regulation 361, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.743. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.