Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 504 — Hydraulic test for new economisers
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 502, 503. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 502, Reg. 503, Reg. 504 ECONOMISERS | ||||||||||||||
| ||||||||||||||
|
ECONOMISERS | ||||||||||||||
| ||||||||||||||
|
ECONOMISERS | ||||||||||||||
|
Earlier text: the 2008 DIPP web edition
STANDARD CONDITIONS FOR THE DESIGN AND CONSTGRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS
ECONOMISERS
Hydraulic test for new economisers
For all new economisers the hydraulic test must be applied as shown below:-
On Components before Design pressure lbs/sq. Hydraulic test pressure
assembly in. lbs./sq.in.
Cast iron tubes, headers Twice working pressure
and bends minimum pressure, 700.
500 or less 1,000
Above 500 but not Twice the working pressure
Steel tubes and bends
exceeding 1,000
1,000 above the working
Above, 1000 pressure.
Below 1,000 Twice the working pressure.
Above 1,000 Working pressure plus 1,000
Headers
lbs./sq.in.
For all assembled sections the Hydraulic Test pressure shall be not less than 1 ½ times the working pressure.
“Working pressure” shall be the highest pressure at which the economiser relief valves are to be set.
The above test pressure shall be held for a minimum period of ten minutes.