Indian Boiler Regulations, 2026 · Chapter 10 · Electrode Boilers
Regulation 352. Hydraulic Test
Not yet checked against the official Gazette; verify before relying on it.
352. Hydraulic Test.─ The hydraulic test shall comply with sub-regulation (1) of regulation 298.
In short
The hydraulic test for seamless shell electrode boilers must comply with sub-regulation (1) of regulation 298.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 56 | Hydraulic Test | 100% | Chapter II (DPIIT scan), image 10 |
| 72 | Hydraulic Test | 100% | Chapter II (DPIIT scan), image 14 |
| 504 | Hydraulic test for new economisers | 100% | Chapter XI (DPIIT scan), image 2 |
Amendment history of the candidate IBR 1950 regulations: Reg. 56 (3 amendments)
IBR 1950 regulation 56 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 56 page for its amendments.
| Reg. 56 MATERIALS OF CONSTRUCTION SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE Hydraulic Test |
| (i) Each pipe shall be tested by the manufacturer and shall withstand a hydraulic pressure to one and half times the design pressure but not greater than pressure calculated by the following formula given below. In the absence of working pressure is indicated in the Test Certificate then the tested pressure indicated in the Test Certificate divided by 1.5 shall be the maximum working pressure P = 2 S t / d where P = test pressure D = specified outside diameter of the pipe t = specified wall thickness of the pipe S = stress which shall be taken as 40% of the minimum tensile strength at room temperature. (ii) Notwithstanding anything contained in the above clause, the hydraulic test at the maker's works may be dispensed with provided that the pipes are subject to non destructive testing by an appropriate method like Ultrasonic or Eddy current or stray flux testing |
IBR 1950 regulation 504 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 504 page for its amendments.
| Reg. 502, Reg. 503, Reg. 504 ECONOMISERS | ||||||||||||||
| ||||||||||||||
|
ECONOMISERS | ||||||||||||||
| ||||||||||||||
|
ECONOMISERS | ||||||||||||||
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 352, Regulation 352, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.740. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.