Indian Boiler Regulations, 2026 · Chapter 10 · Electrode Boilers
Regulation 353. Determination of maximum allowable working pressure
Not yet checked against the official Gazette; verify before relying on it.
353. Determination of maximum allowable working pressure.─(1) The maximum allowable working pressure shall be determined as per with regulation 346 except the minimum thickness of the shell shall be as mentioned in the following table: -
| Serial No. | Internal diameter in mm | Minimum thickness in mm |
|---|---|---|
| (1) | (2) | (3) |
| 1. | Upto and including 610 | 6.3 |
| 2. | Over 610 upto and including 914 | 8 |
| 3. | Over 914 | 10 |
Table structure read from the Gazette PDF, page 741. Verification status as for the text above.
Show original extracted text (diagnostic, not authoritative)
Serial No. Table 10/2 Minimum thickness
Internal diameter in mm in mm
(1) (3)
1. (2) 6.3
2. Upto and including 610 8
3. Over 610 upto and including 914 10
Over 914(2)In no case the factor of safety of the cylindrical shell and ends shall be less than 4.
(3)The value of “c” in the equation shall be taken as 35.
(4)Where the ends are welded to shell or mechanically secured and welded, they shall be stress-relived.
Parts of this extracted text look garbled; read the Gazette page before using any value.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
For seamless shell electrode boilers, the maximum allowable working pressure is found as in regulation 346, with these changes:
- (1) The minimum shell thicknesses are those in Table 10/2, banded by internal diameter. The extracted table is misaligned, so check the Gazette page for the exact values.
- (2) The factor of safety of the cylindrical shell and ends must never be less than 4.
- (3) The value of "c" in the equation is 35.
- (4) Where the ends are welded to the shell, or mechanically secured and welded, they must be stress-relieved.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 434 | Determination of Working Pressure | 100% | Chapter X (DPIIT scan), image 9 |
IBR 1950 regulation 434 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 434 page for its amendments.
| Reg. 431, Reg. 432, Reg. 433, Reg. 434
Reg. 432
Reg. 433
Reg. 434
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 353, Regulation 353, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.740–741. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.