BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 10 · Electrode Boilers

Regulation 356. Mounting, fittings and connections

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 741–742

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

356. Mounting, fittings and connections.─(1) For all types of electrode boilers, mounting, fitting and connections shall comply with regulation 181 for all types of electrode boilers.

(2)For electrode boilers, one means of indicating water level of the tubular glass type water level gauge and one means of feeding the boilers shall be sufficient and the safety valves shall be spring loaded type.

(3)If an Electrode boiler is fitted with a magnetic valve, the said valve will be accepted in lieu of the second safety valve provided the source of power supply to both the valves and the boiler are the same and both are operated by one signal switch.

Referenced provisions

Reg. 181

Independent explanation — not the law · draft · engineer review in progress

In short

Mountings, fittings and connections of all electrode boilers must comply with regulation 181, with some relaxations.

Key points

  • (1) Regulation 181 applies to all types of electrode boilers.
  • (2) One tubular glass type water level gauge and one means of feeding the boiler are sufficient. The safety valves must be spring loaded.
  • (3) A magnetic valve may be accepted in place of the second safety valve.

Watch out

  • (3) The magnetic valve is accepted only if both valves and the boiler share the same power supply and are operated by one signal switch.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
368Other Fittings and Mountings72%Chapter VIII (DPIIT scan), image 36
IBR 1950 regulation 368 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 368 page for its amendments.

Reg. 368, Reg. 369

Bronze Screwed and Socketed joints and mountings and fittings of bronze

Mountings and fittings of bronze upto 76 mm (3”) diameter may be attached directly to steel pipes by screwing when the pressures and temperatures do not exceed 8.5 kg/cm² (120 lbs./sq.in.) and 225°C (435°F) respectively; where tapered threads are employed, such joints may be used for pressures not exceeding 17.6 kg/cm² (250 lbs./sq. in.). Bronze fittings above 76 mm (3”) diameter shall be of flanged construction.



Reg. 369

Reducing Valve

Where a reducing valve is installed in a pipe line the pipe line and accessories on the low pressure side of the reducing valve shall be protected by a suitable safety valve or valves so adjusted as to permit the steam to escape as soon as the safe working pressure is exceeded or by a suitable appliance for cutting off automatically the supply of steam as soon as the safe working pressure is exceeded.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
741–742
PDF page index
741–742 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 2dee88317ce9b6f6
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 356, Regulation 356, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.741–742. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.