Indian Boiler Regulations, 2026 · Chapter 5 · Valves, Gauges and Auxiliaries
Regulation 181. Requisite Mountings, fittings and Auxiliaries
Not yet checked against the official Gazette; verify before relying on it.
181. Requisite Mountings, fittings and Auxiliaries. ─ (1) Every boiler shall be provided at least with the following, namely: -
(a)Two safety valves, one of which may be a high steam and low water type safety valve and in no case the bore of the seat of the valve should be less than 19 mm.
(b)Two means of indicating the water level;
(c)A steam pressure gauge;
(d)A steam stop valve;
(e)A feed check valve;
(f)One feed apparatus;
Provided that for boilers fired by gaseous, liquid or solid fuels in suspension where heating surface exceeds 20 m2, shall be provided with minimum two feed apparatus which shall have a combined capacity of not less than the maximum continuous rating of the boiler: Provided further that for other boilers where residual heat is there even after fuel supply cut-off, two feed apparatus each having a capacity of not less than maximum continuous rating of the boiler shall be provided. (For boilers in battery see regulation 242);
(g)A blow-down cock or valve;
(h)Fusible plugs as provided under Regulation 236;
(i)An attachment for Competent Person’s test gauge;
(j)A manhole, where size and construction permit, and such mud holes or sight holes as are necessary for effectively cleaning the boiler.
(2)In the case of boilers fitted with integral super heaters, an additional safety valve shall be fitted at the end of the super heaters outlet header.
(3)In the case of boilers with no fixed steam and waterline, the fitting of such accessories that are manifestly not needed or used, such as water gauges, water columns and gauge cocks, may not be insisted upon.
(4)In the case of a single boiler of the Shell type and not connected in a battery with other boilers, the heating surface of which does not exceed 102 m2, two independent source of power supply to the two feed apparatus shall not be necessary.
(5)In the case of miniature boilers coming under Chapter-14, the Steam pressure gauge may be connected to the steam space or to a steam connection to the water column by a syphon tube or equivalent device that will keep the gauge tube filled with water and if brass or bronze composition is used, the minimum size of the syphon tube shall be 6 mm standard pipe size; for other materials the minimum inside diameter of the pipe or tube shall be 13 mm.
(6)For Electrode boilers, see regulation 356.
(7)In case of boilers with reheaters, the reheaters shall be protected with one or more relieving devices of
105% capacity (15% of the total capacity shall be located in the steam flow path between reheater outlet and first stop valve) to avoid over pressure in case of internal failures.
In short
Regulation 181 is the minimum fittings checklist for boilers (subject to its own exceptions, e.g. (3) for boilers with no fixed steam and water line):
- Two safety valves (one may be a high-steam/low-water type), with a seat bore of at least 19 mm
- Two means of indicating water level
- A steam pressure gauge
- A steam stop valve
- A feed check valve
- Feed apparatus: one as a baseline, but see the provisos below
- A blow-down cock or valve
- Fusible plugs as provided in regulation 236
- An attachment for the Competent Person's test gauge
- A manhole where size and construction permit, plus mud holes or sight holes needed for cleaning
Points that are easy to miss
- Feed apparatus provisos. Boilers fired by gaseous, liquid or solid fuel in suspension with heating surface over 20 m² need at least two feed apparatus with combined capacity of at least the maximum continuous rating (MCR). Boilers with residual heat after fuel cut-off need two feed apparatus, each of at least MCR. For boilers in battery, see regulation 242.
- Integral superheaters need an additional safety valve at the superheater outlet header (sub-reg. 2).
- Boilers with no fixed steam and water line need not have fittings that are obviously not used, such as water gauges (sub-reg. 3).
- A single shell-type boiler, not in battery, with heating surface ≤ 102 m² does not need two independent power supplies for the two feed apparatus (sub-reg. 4).
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Original drawings for this regulation
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 368 | Other Fittings and Mountings | 88% | Chapter VIII (DPIIT scan), image 36 |
IBR 1950 regulation 368 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 368 page for its amendments.
| Reg. 368, Reg. 369 Bronze Screwed and Socketed joints and mountings and fittings of bronze
| |||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.


Indian Boiler Regulations, 2026, reg. 181, Regulation 181, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.622–623. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.