BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 5 · Valves, Gauges and Auxiliaries

Regulation 226. Drains

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 638

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

226. Drains.─ A drain cock or valve with a suitable discharge pipe shall be fitted to each water gauge.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 226 requires a drain cock or valve, with a suitable discharge pipe, to be fitted to each water gauge.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
299Drainage71%Chapter VI (DPIIT scan), image 4
372Drainage71%Chapter VIII (DPIIT scan), image 36
IBR 1950 regulation 299 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 299 page for its amendments.

Reg. 297, Reg. 298, Reg. 299

Opening in Shell

No accessories other than those integral with the Safety Valve shall obstruct the openings in the boiler shell. Discharging steam shall have direct access to the safety valve without flowing through internal pipes.


Reg. 298

Discharge Passage

The safety valve discharge pipes shall comply with the requirements of clauses (a) and (b) of this regulation. The discharge pipe shall be as short and straight as possible and be fitted with open drain to prevent accumulation water in the pipe. Suitable arrangement shall be provided in the discharge pipe system so that the discharge can readily be heard by the Boiler Attendant.

a) Steam safety valves: -

(i) Ordinary and high lift valves. Where a waste steam-pipe is fitted the pipe and the passage leading to it shall have a cross-sectional area not less than the minimum combined area of the safety valves required by Regulation 293.
(ii) Full lift valves. For full lift valves the area of waste steam-pipe and passages leading to it shall have a cross-sectional area not less than twice A, or such area above this minimum as may be required for valves having a higher approved constant, where A,E and P are as defined in regulation 293.
b) Economiser safety valves. The area of the discharge pipe from an economiser safety valve shall be at least twice the area of the valve seating. Where the discharge from several economiser safety valves is connected to the main discharge pipe, the diameter of the main discharge pipe shall be designed to prevent accumulation of pressure due to the formation of steam under the particular conditions of temperature and pressure which may be applicable.


Reg. 299

Drainage

For each enclosed safety valve chest a means of draining shall be provided. The drain pipe shall be laid with a continuous downward gradient clear of the boiler to a place where the discharge is visible and cannot do injury to any person.
IBR 1950 regulation 372 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 372 page for its amendments.

Reg. 371, Reg. 372

Pipe work supports

All pipe work shall be adequately supported in order to permit free movement for expansion and contraction, and the amount of such movement shall be proportioned throughout the whole of any main by the provision of anchors at suitable points. Where pipes may be subject to vertical movement, spring supports designed to carry the load under all conditions shall be provided. It is desirable that points of supports should, as for as practicable, be arranged adjacent to the pipe joints. Slings are in general preferable to roller supports and these latter should be used only where necessary. All pipe supports should as far as practicable, be of mild steel and pipe anchors either of mild steel or cast steel.



Reg. 372

Drainage

a)

In the case of steam mains, attention should be paid to the adequate provision of drainage points in the form of drain pockets. Drainage points connected to stream-traps, shall be provided wherever water can collect under working conditions. Hand drains shall be provided at all points at which water can collect in any portion of the steam main, by valve leakage or other means, when shut down, or when warming up prior to use.
b) Where practicable a suitable gradient shall be provided in the pipe work to ensure the passage of condensed water in the direction of flow of steam towards the drainage point.
c) It is recommended that a by pass should be fitted at each steam-trap.
d) Where the volume of water deposited is likely to be of serious proportions, separator should be installed. Each separator shall be furnished with a steam trap which shall be connected to it by means of a three-way cock one end of which is connected to a manually operated drain.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
638
PDF page index
638 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash a2c5e0a1bc754057
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 226, Regulation 226, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.638. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.