Regulation 241. Operating Position

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 640

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

241. Operating Position.─ Feed check valves or regulating valves shall be so arranged as to enable them to be satisfactorily operated from the boiler floor.

Independent explanation — not the law · draft · engineer review in progress

In short

Feed check valves or regulating valves must be arranged so that they can be satisfactorily operated from the boiler floor.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
336Operating position100%Chapter VI (DPIIT scan), image 9
IBR 1950 regulation 336 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 336 page for its amendments.

Reg. 334, Reg. 335, Reg. 336, Reg. 336 A

Attachment to Boiler



Wherever practicable fusible plugs shall be screwed into the boiler plates from the waterside. The screwed portion shall have threads of Whitworth form not more than 11 per inch.


Reg. 335
FEED VALVES

General

a) Feed check valves shall be of the non-return type.
b) Where the valve is not of screw-down non-return type a separate screw-down valve shall be provided.
c) The discharge from the feed check valve or from the internal feed pipe (if provided) shall be above low water level and in the case of Lancashire and Cornish boilers shall be at least 5 ft. beyond the fire bridge. Provided that the restriction aforesaid regarding the position of feed discharge level would not apply in the case of water tube boilers.
d) The discharge end of feed pipe shall be so located that it is not close to any riveted joint of the furnace plates or of the shell.


Reg. 336

Operating position

Feed check valves or regulating valves shall be so arranged as to enable them to be satisfactorily operated from the boiler floor.


Reg. 336 A

Requirements as to feed apparatus in certain cases

In the case of a battery of boilers connected to a common feed range, the requirements of regulation 281 in respect of the number of feed apparatus shall be considered to have been fulfilled provided a total supply of feed water, not less than the combined maximum continuous rating of all active boilers can be maintained even if any one of the sources of power supply should fail.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
640
PDF page index
640 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 894b197d56fb9570
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 241, Regulation 241, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.640. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.