Indian Boiler Regulations, 2026 · Chapter 5 · Valves, Gauges and Auxiliaries

Regulation 200. Openings in Shell

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 631

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

200. Openings in Shell.─(1) No accessories other than those integral with the Safety Valve shall obstruct the openings in the boiler shell.

(2)Discharging steam shall have direct access to the safety valve without flowing through internal pipes.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 200 keeps the boiler shell openings for safety valves clear. No accessory, other than those integral with the safety valve, may obstruct the opening, and steam must reach the safety valve directly without flowing through internal pipes.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
297Openings in Shell100%Chapter VI (DPIIT scan), image 4
427Manholes and other openings in Shells79%Chapter X (DPIIT scan), image 8
IBR 1950 regulation 297 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 297 page for its amendments.

Reg. 297, Reg. 298, Reg. 299

Opening in Shell

No accessories other than those integral with the Safety Valve shall obstruct the openings in the boiler shell. Discharging steam shall have direct access to the safety valve without flowing through internal pipes.


Reg. 298

Discharge Passage

The safety valve discharge pipes shall comply with the requirements of clauses (a) and (b) of this regulation. The discharge pipe shall be as short and straight as possible and be fitted with open drain to prevent accumulation water in the pipe. Suitable arrangement shall be provided in the discharge pipe system so that the discharge can readily be heard by the Boiler Attendant.

a) Steam safety valves: -

(i) Ordinary and high lift valves. Where a waste steam-pipe is fitted the pipe and the passage leading to it shall have a cross-sectional area not less than the minimum combined area of the safety valves required by Regulation 293.
(ii) Full lift valves. For full lift valves the area of waste steam-pipe and passages leading to it shall have a cross-sectional area not less than twice A, or such area above this minimum as may be required for valves having a higher approved constant, where A,E and P are as defined in regulation 293.
b) Economiser safety valves. The area of the discharge pipe from an economiser safety valve shall be at least twice the area of the valve seating. Where the discharge from several economiser safety valves is connected to the main discharge pipe, the diameter of the main discharge pipe shall be designed to prevent accumulation of pressure due to the formation of steam under the particular conditions of temperature and pressure which may be applicable.


Reg. 299

Drainage

For each enclosed safety valve chest a means of draining shall be provided. The drain pipe shall be laid with a continuous downward gradient clear of the boiler to a place where the discharge is visible and cannot do injury to any person.
IBR 1950 regulation 427 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 427 page for its amendments.

Reg. 427, Reg. 428, Reg. 429, Reg. 430
TESTS FOR CLASS II FUSION WELDED SEAMS

Manholes and other openings in Shells

Manholes and other openings in boiler shells shall be placed away from any welded seam. Oval openings shall be arranged with their minor axis parallel to the longitudinal centre line of the boiler.

(a) Un-compensated openings shall comply with Regulation 187.
(b) Compensated openings shall comply with Regulations 170, 171, 186 and 279.


Reg. 428
TESTS FOR CLASS II FUSION WELDED SEAMS

Dished End Plates with pressure on Concave side

This shall comply with Regulation 408.



Reg. 429
TESTS FOR CLASS II FUSION WELDED SEAMS

Unstayed Flat End Plates

The working pressure of unstayed flat end plates shall comply with Regulation 412.

Where the diameter of the openings in an unstayed flat end plate is greater than 2½ inches or the pitch in inches is less than four times the diameter of the holes full compensation shall be provided as in Regulation 279.



Reg. 430
TESTS FOR CLASS II FUSION WELDED SEAMS

Thickness of Angle Rings

Thickness of angle rings shall comply with Regulation 379(a).

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
631
PDF page index
631 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 6115468b5f8c9685
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 200, Regulation 200, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.631. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.