213. Dimensions.─(1) For ordinary lift valves, the compression or extension of safety valve springs required to load the valves to the set pressure shall not be less than one quarter of the diameter of the valve due consideration being given in the case of spring loaded level safety valves to the ratio of leverage.

(2)The proportion of unloaded length to external diameter of the spring shall not exceed 4:1.

(3)These requirements do not apply to full lift and high lift safety valves.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 213 sets spring proportions for ordinary lift safety valves.

Key points

  • (1) The compression or extension of the spring needed to load the valve to set pressure must be not less than one quarter of the valve diameter. For spring loaded lever valves, the leverage ratio must be taken into account.
  • (2) The ratio of unloaded length to external diameter of the spring must not exceed 4:1.

Watch out

  • (3) These requirements do not apply to full lift and high lift safety valves.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

No candidate heading found in the historical print edition.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
634
PDF page index
634 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash bb85adfcef2c1c0a
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 213, Regulation 213, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.634. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.