Indian Boiler Regulations, 2026 · Chapter 5 · Valves, Gauges and Auxiliaries
Regulation 232. Pressure Gauges Dials
Not yet checked against the official Gazette; verify before relying on it.
232. Pressure Gauges Dials.─ (1) For pressure upto35 kg/cm2 (g), pressure gauge dials shall be graduated in kg/cm2(g) from zero to twice the pressure as nearly as may be practicable.
(2)For pressure exceeding 35 kg/cm2(g),the range of the graduation shall be from zero to one and a half times the maximum allowable working pressure, as nearly as may be practicable, but in no case shall the maximum graduation on the gauge be less than 70 kg/cm2 (g).
(3)The scale on the dial shall be clearly and permanently marked in kg/cm2 (g).
(4)The maximum allowable working pressure shall be marked in red on the dial of each pressure gauge.
(5)(a) Where the gauge is compensated for a head of water between the gauge and the boiler connection, the amount of such compensation shall be marked on the dial. Pressure gauge shall be calibrated within an accuracy of +1 percent.
(b)Boiler pressure gauges shall not be less than 150 mm in diameter.
(6)The travel of the pointer of the dial gauge shall not exceed 325°.
In short
Regulation 232 sets how boiler pressure gauge dials are graduated, marked, sized and calibrated.
Key points
- (1) For pressure up to 35 kg/cm²(g), dials are graduated in kg/cm²(g) from zero to twice the pressure, as nearly as practicable.
- (2) For pressure exceeding 35 kg/cm²(g), the range is zero to one and a half times the maximum allowable working pressure, as nearly as practicable.
- (3) The dial scale must be clearly and permanently marked in kg/cm²(g).
- (4) The maximum allowable working pressure must be marked in red on every pressure gauge dial.
- (5)(a) If the gauge is compensated for a water head between gauge and boiler connection, the compensation must be marked on the dial. Gauges must be calibrated within an accuracy of +1 percent (as printed; read as within 1 percent).
- (5)(b) Boiler pressure gauges must be not less than 150 mm in diameter.
- (6) Pointer travel must not exceed 325°.
Watch out
- (2) Whatever the working pressure, the maximum graduation must never be less than 70 kg/cm²(g) for gauges in that range.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Original drawings for this regulation
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 327 | Dials | 100% | Chapter VI (DPIIT scan), image 8 |
Amendment history of the candidate IBR 1950 regulation: Reg. 327 (1 amendment)
IBR 1950 regulation 327 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 327 page for its amendments.
| Reg. 327, Reg. 328, Reg. 329 | |||||||||||||||
Reg. 328 Connections
Reg. 329 Gauge Cocks
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 232, Regulation 232, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.639. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.