Indian Boiler Regulations, 2026 · Chapter 5 · Valves, Gauges and Auxiliaries
Regulation 183. Materials, Temperature and Pressure Limits
Not yet checked against the official Gazette; verify before relying on it.
183. Materials, Temperature and Pressure Limits.─(1)The materials used in the manufacture of the bodies of the fittings shall comply with the following requirements, namely: -
(i)Castings of Carbon, Alloy and Stainless Steel shall comply with regulations 50 to 57.
(ii)Steel forgings shall comply with regulations 58 to 62.
(iii)Iron casting shall comply with the regulations 63 to 70.
(iv)Bronze castings shall comply with the following table 5/1:
| Serial No. | Chemical Composition | Grade A | Grade B |
|---|---|---|---|
| (1) | (2) | (3) | (4) |
| 1. | Tin | 5.5 to 8.0% | 4 to 6% |
| 2. | Lead | 1.0 to 3.0% | 4 to 6% |
| 3. | Zinc | 3.0 to 6.0% | 4 to 6% |
| 4. | Total of all elements other than those set out above and excluding Copper and incidental Nickel | 0.50% | 0.50% |
| 5. | Copper plus incidental Nickel | Balance | Balance |
| 6. | Physical Properties Ultimate tensile Strength | 22 kg/mm2 | 20.5 kg/mm2 |
| 7. | Sand Cost Elongation per cent minimum (cast on)on standard test piece C | 8% | 15% |
| 8. | Ultimate tensile Strength | 23 kg/mm2 | 20.5 kg/mm2 |
| 9. | Sand cost Elongation percent minimum (separately cast) on standard test piece C | 12% | 15% |
Table structure read from the Gazette PDF, page 625. Verification status as for the text above.
Show original extracted text (diagnostic, not authoritative)
Serial Table 5/1 Grade A Grade B
No. Chemical Composition (3)
(1) (4)
(2)
4 to 6%
1. Tin 5.5 to 8.0% 4 to 6%
4 to 6%
2. Lead 1.0 to 3.0% 0.50%
3. Zinc 3.0 to 6.0% Balance
20.5 kg/mm2
4. Total of all elements other than those set out 0.50%
above and excluding Copper and incidental
Nickel
5. Copper plus incidental Nickel Balance
6. Physical Properties 22 kg/mm2
Ultimate tensile Strength
7. Sand Cost Elongation per cent minimum 8% 15%
(cast on)on standard test piece C 23 kg/mm2 20.5 kg/mm2
8. Ultimate tensile Strength
9. Sand cost Elongation percent minimum
(separately cast) on standard test piece C 12% 15%(v)The seats and discs of valves shall be made of non-corrodible metal*.
*By non-corrodible metal is meant specially resistant to corrosion and /or erosion.
(2)Cast Iron shall not be used for:-
(i)Temperatures above 220°C.
(ii)Pressure exceeding 13 bar gauge.
(iii)Valves exceeding 200 mm nominal bore which are connected directly to the boiler.
(iv)Wedge or double disc gate valves which are connected directly to the boiler.
(v)Boiler blow down fittings.
Explanation- The expression connected directly to the boilers covers the valve which cannot itself be isolated from the boiler.
Note: Spheroidal iron may be used for temperature not exceeding 282°C and pressure not exceeding
17.58 kg/cm2(g) provided it complies with the following requirements in respect of the physical properties.
(a)0.2% proof stress 250 kg/mm2;
(b)Minimum elongation percent 12.
(3)Copper alloy shall not be used for temperatures above 225°C, where the valves are connected directly to the boiler. In the case of valves not connected directly to the boiler this temperature limitation may be increased to 260°C.
Parts of this extracted text look garbled; read the Gazette page before using any value.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 183 says which materials may be used for the bodies of boiler fittings, and sets temperature and pressure limits for cast iron and copper alloy.
Key points
- (1)(i) Carbon, alloy and stainless steel castings must comply with regulations 50 to 57.
- (1)(ii) Steel forgings must comply with regulations 58 to 62.
- (1)(iii) Iron castings must comply with regulations 63 to 70.
- (1)(iv) Bronze castings must comply with Table 5/1, which gives chemical composition and physical properties (tensile strength and elongation) for Grade A and Grade B. The table is broken in the extracted text, so check the Gazette page for the exact values.
- (1)(v) Valve seats and discs must be of non-corrodible metal, meaning metal specially resistant to corrosion and/or erosion.
- (2) Cast iron must not be used for temperatures above 220°C, pressures exceeding 13 bar gauge, valves exceeding 200 mm nominal bore connected directly to the boiler, wedge or double disc gate valves connected directly to the boiler, or boiler blow down fittings.
- (3) Copper alloy must not be used above 225°C where valves are connected directly to the boiler. For valves not connected directly, this limit may be increased to 260°C.
Watch out
- "Connected directly to the boiler" covers a valve that cannot itself be isolated from the boiler.
- A note allows spheroidal iron for temperatures not exceeding 282°C and pressures not exceeding 17.58 kg/cm²(g), provided it meets stated physical properties (0.2% proof stress and a minimum elongation percent of 12).
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 6 | Standard specifications for materials | 100% | Chapter I (DPIIT scan), image 3 |
| 626 | Materials | 100% | Chapter XV (DPIIT scan), image 1 |
Amendment history of the candidate IBR 1950 regulations: Reg. 626 (1 amendment)
IBR 1950 regulation 6 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 6 page for its amendments.
| Reg. 6 Standard specifications for materials. |
| The standard specifications for steel wrought iron and copper plates and bar, and for cast steel shall be those prescribed in Chapter II. |
IBR 1950 regulation 626 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 626 page for its amendments.
| Reg. 626 FEED WATER FOR BOILER | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Tests shall be carried out as prescribed in the appropriate clauses of IS : 3025-1964* and IS : 3550-1965! as indicated against the characteristics in Table 1.
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.



Indian Boiler Regulations, 2026, reg. 183, Regulation 183, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.624–626. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.