Reg. 626

FEED WATER FOR BOILER


Test Methods

Tests shall be carried out as prescribed in the appropriate clauses of IS : 3025-1964* and IS : 3550-1965! as indicated against the characteristics in Table 1.

TABLE 1: CHEMICAL REQUIREMENTS OF FEED WATER AND BOILER WATER FOR LOW AND MEDIUM PRESSURE BOILERS (Regulation 624 and 626)
Sl.. No. CHARACTERISTIC REQUIREMENT FOR BOILER PRESSURE
----------------------------------------
METHOD OF TEST (Ref. to Cl. No. of)
--------------------------
Up to 2.0 2.1 to 3.9 4.0 to 5.9 IS : 3550- IS : 3025-_
MN/m2 MN/m2 MN/m2 1965* 1964!
(1) (2) (3) (4) (5) (6) (7)
i) Feed Water
a)
Total hardness
(as CaCO2 ),mg/l, Max
10 1.0 0.5 -- 16.1
-----------------------------------------------------------------------------------------------------------------------
(1) (2) (3) (4) (5) (6) (7)
b) pH value 8.5 to 9.5 8.5 to 9.5 8.5 to 9.5 -- 8
c) Dissolved Oxygen, mg/1, Max 0.1 0.02 0.01 25 --
d) Silica (as SiO2), mg/l, Max -- 5 0.5 16 --
ii) Boiler Water
a) Total hardness(of filteredsample) (as CaCO3), mg/l, --------- Not detectable ------------- -- 16.1
b

Total alkalinitya (as CaCO3), mg/l,Max

700 500 300 -- 13
c) Caustic alkalinity (as CaCO3), mg/lMax 350 200 60 -- 15
d) pH value 11.0 to 12.0 11.0 to 12.0 10.5 to 11.0 -- 8
e) b Residual sodi um sulphite (asNa2SO3) mg/l
30 to 50 20 to 30 -- -- 21
f) Residual hydrazine (as N2H4),mg/l 0.1 to 1
(if added)
0 .1 to 0.5
(if added)
0.05 to 0.3 26 --
g) j Ratio Na2SO4/Caustic alkalinity (as NaOH)
               or
Ratio NaNO3/ total alkalinity (as NaOH)
------------ above 2.5 --------------- -- 20.2
and 15
------------- above 0.4 ---------------- -- 48
and 13
h) Phosphates (asPO4), mg/l (if added )

20 to 40 15 to 30 5 to 20 14 --
i) Total dissoslved solids mg/l, Max 3500s 2500 1500 9 12
k) Silica (as SiO2), mg/l Less than 0.4 of caustic
alkalinity
15 16 30
------------------------------------------------------------------------------------------------------------------------
Note 1- Recovery Boilers - The boiler feed water used shall be completely de-mineralized and also the boiler feed water and boiler water shall be conditioned in accordance with high pressure boilers working at 60 kg/cm2 and above (see IS : 4343-1967**)

Note 2 - When feed water heaters are of copper or copper alloy constructions, the pH of the feed water shall be maintained between 8.5 and 9.2 while when feed water heaters are of iron constructions, the pH of the feed may be maintained between 8.5 and 9.5.

Note 3 - Silica in Boiler Water - Lower concentration of silica may be advisable for steam of turbines, which generally requires less than 0.02 mg/l silica in steam.

* Methods of test for routine control for water used in industry.

! Methods of sampling and test (physical and chemical) for water used in industry.

a Total alkalinity should preferably be about 20 percent of total dissolved solids.

b Shall not apply if reducing agents other than sodium sulphite are used.

j For riveted boilers only.

s For shell type boilers depending on parameters, the limits can be relaxed.

** Code of practice for treatment of water for high pressure boilers (under revision).

Earlier text: the 2008 DIPP web edition

FEED WATER FOR BOILER

Test Methods

Tests shall be carried out as prescribed in the appropriate clauses of IS : 3025-1964* and IS : 3550-1965! as indicated against the characteristics in Table 1.

TABLE 1: CHEMICAL REQUIREMENTS OF FEED WATER AND BOILER WATER FOR LOW AND MEDIUM PRESSURE BOILERS (Regulation 624 and 626)

Sl.. CHARACTERISTIC           REQUIREMENT FOR BOILER       METHOD OF TEST
No.                                   PRESSURE              (Ref. to Cl. No. of)
                               ----------------------------------------  --------------------------
                             Up to 2.0  2.1 to 3.9  4.0 to 5.9  IS :  IS : 3025-
                                                             3550-     _
                              MN/m²      MN/m²     MN/m²     1965*   1964!
 (1)           (2)              (3)        (4)       (5)      (6)     (7)

i)Feed Water

    a) Total hardness
                                10        1.0        0.5      --      16.1
       (as CaCO2 ),mg/l, Max
-----------------------------------------------------------------------------------------------------------------------
 (1)           (2)              (3)        (4)       (5)      (6)     (7)
    b) pH value              8.5 to 9.5  8.5 to 9.5 8.5 to 9.5  --     8
    c) Dissolved Oxygen,
                                0.1       0.02      0.01      25       --
       mg/1, Max
    d) Silica (as SiO2), mg/l,
                                --         5         0.5      16       --
       Max

ii)Boiler Water

a) Total hardness(of
   filteredsample) (as    --------- Not detectable -------------  --  16.1
   CaCO3), mg/l,
b        Total
         alkalinityα
         (as               700        500        300      --      13
         CaCO3),
         mg/l,Max
c) Caustic alkalinity (as
                           350        200        60       --      15
   CaCO3), mg/lMax
d) pH value             11.0 to 12.0 11.0 to 12.0  10.5 to
                                                          --       8
                                                11.0

e)β Residual sodi um

   sulphite (asNa2SO3)    30 to 50  20 to 30     --       --      21
   mg/l
f) Residual hydrazine (as  0.1 to 1  0 .1 to 0.5
                                    (if added)  0.05 to 0.3  26    --
   N2H4),mg/l            (if added)

g)ϕ Ratio Na2SO4/Caustic

alkalinity (as NaOH)                                           20.2
                       ------------ above 2.5 ---------------  --
or                                                            and 15

Ratio NaNO3/ total

alkalinity (as NaOH)
                                                               48
                       ------------- above 0.4 ----------------  --
                                                              and 13

h)Phosphates (asPO4),

       mg/l (if added )       20 to 40  15 to 30   5 to 20    14       --

    i) Total dissoslved solids  3500σ
                                          2500      1500      9       12
       mg/l, Max
    k) Silica (as SiO2), mg/l  Less than 0.4 of caustic
                                                     15       16      30
                                   alkalinity
------------------------------------------------------------------------------------------------------------------------

Note 1- Recovery Boilers - The boiler feed water used shall be completely de-mineralized and also the boiler feed water and boiler water shall be conditioned in accordance with high pressure boilers working at 60 kg/cm2 and above (see IS : 4343-1967**)

Note 2 - When feed water heaters are of copper or copper alloy constructions, the pH of the feed water shall be maintained between 8.5 and 9.2 while when feed water heaters are of iron constructions, the pH of the feed may be maintained between 8.5 and 9.5.

Note 3 - Silica in Boiler Water - Lower concentration of silica may be advisable for steam of turbines, which generally requires less than 0.02 mg/l silica in steam. * Methods of test for routine control for water used in industry.

! Methods of sampling and test (physical and chemical) for water used in industry.

α Total alkalinity should preferably be about 20 percent of total dissolved solids.

β Shall not apply if reducing agents other than sodium sulphite are used.

ϕ For riveted boilers only.

σ For shell type boilers depending on parameters, the limits can be relaxed.

** Code of practice for treatment of water for high pressure boilers (under revision).

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
2000-09-29G.S.R. 397SubstitutedReplaced as part of the substitution of Chapter XV by a feed-water chapter.listed before the capture

Possible IBR 2026 successors (heading match, unverified): Reg. 27, Reg. 28, Reg. 31, Reg. 143, Reg. 183, Reg. 212, Reg. 238, Reg. 277, Reg. 336, Reg. 398, Reg. 548, Reg. 562, Reg. 591