Indian Boiler Regulations, 2026 · Chapter 5 · Valves, Gauges and Auxiliaries

Regulation 238. Material

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 640

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

238. Material.─(1) The non-fusible portions of the plug shall be of bronze except where the nature of the boiler water precludes the use of non-ferrous material.

(2)The fusible metal shall be of an alloy melting readily at a temperature not less than 66°C in excess of the saturated steam temperature at the design pressure of the boiler.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 238 sets materials for fusible plugs.

Key points

  • (1) Non-fusible parts must be bronze, except where the nature of the boiler water rules out non-ferrous material.
  • (2) The fusible metal must be an alloy that melts readily at a temperature not less than 66°C above the saturated steam temperature at the boiler's design pressure.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
626Materials94%Chapter XV (DPIIT scan), image 1

Amendment history of the candidate IBR 1950 regulation: Reg. 626 (1 amendment)

IBR 1950 regulation 626 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 626 page for its amendments.

Reg. 626

FEED WATER FOR BOILER


Test Methods

Tests shall be carried out as prescribed in the appropriate clauses of IS : 3025-1964* and IS : 3550-1965! as indicated against the characteristics in Table 1.

TABLE 1: CHEMICAL REQUIREMENTS OF FEED WATER AND BOILER WATER FOR LOW AND MEDIUM PRESSURE BOILERS (Regulation 624 and 626)
Sl.. No. CHARACTERISTIC REQUIREMENT FOR BOILER PRESSURE
----------------------------------------
METHOD OF TEST (Ref. to Cl. No. of)
--------------------------
Up to 2.0 2.1 to 3.9 4.0 to 5.9 IS : 3550- IS : 3025-_
MN/m2 MN/m2 MN/m2 1965* 1964!
(1) (2) (3) (4) (5) (6) (7)
i) Feed Water
a)
Total hardness
(as CaCO2 ),mg/l, Max
10 1.0 0.5 -- 16.1
-----------------------------------------------------------------------------------------------------------------------
(1) (2) (3) (4) (5) (6) (7)
b) pH value 8.5 to 9.5 8.5 to 9.5 8.5 to 9.5 -- 8
c) Dissolved Oxygen, mg/1, Max 0.1 0.02 0.01 25 --
d) Silica (as SiO2), mg/l, Max -- 5 0.5 16 --
ii) Boiler Water
a) Total hardness(of filteredsample) (as CaCO3), mg/l, --------- Not detectable ------------- -- 16.1
b

Total alkalinitya (as CaCO3), mg/l,Max

700 500 300 -- 13
c) Caustic alkalinity (as CaCO3), mg/lMax 350 200 60 -- 15
d) pH value 11.0 to 12.0 11.0 to 12.0 10.5 to 11.0 -- 8
e) b Residual sodi um sulphite (asNa2SO3) mg/l
30 to 50 20 to 30 -- -- 21
f) Residual hydrazine (as N2H4),mg/l 0.1 to 1
(if added)
0 .1 to 0.5
(if added)
0.05 to 0.3 26 --
g) j Ratio Na2SO4/Caustic alkalinity (as NaOH)
               or
Ratio NaNO3/ total alkalinity (as NaOH)
------------ above 2.5 --------------- -- 20.2
and 15
------------- above 0.4 ---------------- -- 48
and 13
h) Phosphates (asPO4), mg/l (if added )

20 to 40 15 to 30 5 to 20 14 --
i) Total dissoslved solids mg/l, Max 3500s 2500 1500 9 12
k) Silica (as SiO2), mg/l Less than 0.4 of caustic
alkalinity
15 16 30
------------------------------------------------------------------------------------------------------------------------
Note 1- Recovery Boilers - The boiler feed water used shall be completely de-mineralized and also the boiler feed water and boiler water shall be conditioned in accordance with high pressure boilers working at 60 kg/cm2 and above (see IS : 4343-1967**)

Note 2 - When feed water heaters are of copper or copper alloy constructions, the pH of the feed water shall be maintained between 8.5 and 9.2 while when feed water heaters are of iron constructions, the pH of the feed may be maintained between 8.5 and 9.5.

Note 3 - Silica in Boiler Water - Lower concentration of silica may be advisable for steam of turbines, which generally requires less than 0.02 mg/l silica in steam.

* Methods of test for routine control for water used in industry.

! Methods of sampling and test (physical and chemical) for water used in industry.

a Total alkalinity should preferably be about 20 percent of total dissolved solids.

b Shall not apply if reducing agents other than sodium sulphite are used.

j For riveted boilers only.

s For shell type boilers depending on parameters, the limits can be relaxed.

** Code of practice for treatment of water for high pressure boilers (under revision).

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
640
PDF page index
640 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 859ef55a376436f8
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log