Indian Boiler Regulations, 2026 · Chapter 5 · Valves, Gauges and Auxiliaries
Regulation 191. Chests and fittings in General
Not yet checked against the official Gazette; verify before relying on it.
191. Chests and fittings in General.─(1) (a) All chests and fittings shall be smooth, sound and free from flaws, cracks or other injurious defects and after completion, the chests shall be hydraulically tested at minimum one and half times the maximum allowable working pressure of the valve for which they are intended.
(b)Hydraulic test shall be made with water which may contain a corrosion inhibiter, with kerosene or with other suitable liquid provided its viscosity is not greater than that of water at a test temperature not above 52°C.
(2)(a) (i) Valves may be fabricated from seamless steel pipes for pressures not exceeding 17.6 kg/cm2(g) and temperatures not exceeding 426°C.The welding shall conform to regulation 97 and valve chest shall be stress relieved after fabrication.
(ii)Valves meant for use in pipe work may also be fabricated by welding from seamless steel pipes but no restriction as above regarding pressure and temperature shall apply to them provided the welding complies with all the relevant requirements of fusion welding such as stress relieving and radiographic inspection of the weld as prescribed in Chapter-4 of these regulations.
(b)The maximum allowable working pressure of the chests shall be determined by equation (7/3), where the term ‘2 fE’ shall be substituted by the term ‘1.8 x f’.
(3)The maximum allowable working pressure and the thickness of the bronze and cast Iron valve chests shall be determined by the following formulae, subject to the minimum thickness as specified in sub-regulation
(2)of regulation 184.
R x (T – C)
P = -------------- Equation (5/1)
4.5 x D
4.5 x P x D Equation (5/2)
T = ---------------- + C
R
Where, is maximum allowable working pressure
P is the minimum specified tensile strength of the grade of the material,
R is the external diameter of the chest,
D is the minimum thickness of the chest, excluding tolerance, and
T is the minimum positive tolerance as specified hereunder:
C
For Bronze Chests C = 1.5 mm
For Cast Iron Chests C = 5 mm
(4)The maximum allowable working pressure and the thickness of the steel valve chests of circular cross-section shall be determined by the following formulae, namely: -
2f (T – C) Equation (5/3)
P = ---------------
D – T + C
P x D
T = ------------- + C Equation (5/4 )
2f + P
Where,
P is maximum allowable working pressure in kg/cm2(g)
f = maximum allowable stress as available in the governing codes of the country of the material to which it belongs in kg/mm2. In case of non-availability of the value, the following procedure for evaluating the allowable stress values shall be adopted.
For temperature at or below 454°C is the lower of the following two values:
Et R
f = f =
1.5 2.7
For temperature above 454°C the least of the following three values-
Et Sr (c) f = Sc
(a) f = --- (b) f = -----
1.5 1.5
Where,
Et = Minimum value of yield point (0.2 per cent proof stress) at temperature ‘t’,
R = Minimum specified tensile strength for the grade of steel concerned at room temperature,
Sr = the average stress for the grade of steel concerned to produce rupture in 100,000 hours.
If the width of the scatter band of results obtained when determining this value exceeds + 20 per cent of the average value, then Sr shall be taken as 1.25 times the minimum stress at temperature ‘t’ to produce rupture in 100,000 hours.
Sc = The average stress to produce an elongation (creep) for the grade of steel concerned of 1 percent in 100,000 hours at temperature ‘t’. For metal temperature ‘t’ below 250°C values ‘f’ for 250°C shall be used.
Note: In case Sc values are not available in Material Standard and such materials are known to have been used in boiler in India or abroad, then for such materials, the allowable stress may be taken as the lower of
| Et | Sr |
| or | |
| 1.5 | 1.5 |
Columns reconstructed from the extracted text; check against the Gazette page.
Show original extracted text (diagnostic, not authoritative)
Et Sr
or
1.5 1.5Note: The allowable stress for cast steel shall be 80 per cent of that determined on the above basis.
D = the external diameter of the chest,
T = the minimum positive tolerance as specified hereunder:
For cast steel chest C = 5 mm
For forged or stainless chest C = 2.5 mm
Note: Over and above the calculated thickness, additional thickness needed for assembly stresses, Valve closing stresses, shapes other than circular and stress concentrations, shall be provided by the manufacturers to the satisfaction of the Inspecting Authority.
(5)(a) The number of valves and fittings which shall be made available to the Competent Person (excluding mechanical tests) shall be, following, namely:-
Serial Table 5/1A Number
| Serial No. | Size of valves and fittings | Number |
|---|---|---|
| (1) | (2) | (3) |
| 1. | Up to and including 51 mm | 10 per cent |
| 2. | Over 51 mm and up to and including 76 mm | 15% of the number of chests |
| 3. | Over 76 mm and up to and including 114 mm | 20% of the number of chests |
| 4. | Over 114 mm | 100 per cent. |
Table structure read from the Gazette PDF, page 629. Verification status as for the text above.
Show original extracted text (diagnostic, not authoritative)
No. Size of valves and fittings
(3)
(1) (2) 10 per cent
1. Up to and including 51 mm 15% of the number of chests
2. Over 51 mm and up to and including 76 mm 20% of the number of chests
3. Over 76 mm and up to and including 114 mm
4. Over 114 mm 100 per cent.(b)If the Inspecting Authority is satisfied that the manufacturer has adequate facilities for testing and Inspection of valves intended for service pressure exceeding 10.5 kg/cm2(g) or temperature exceeding 204°C and actually tests each fitting at his works, the Inspecting Authority may, at his discretion, undertake test on a sample basis.
(6)The maximum allowable working pressure and the minimum thickness of the steel valve chest of spherical cross section shall be determined by the following formula, namely,
4f (T – C) Equation (5/5)
P = ----------------
D – 0.8 (T – C)
P x D Equation (5/6)
T = --------------- + C
4f + 0.8 P
Where, maximum allowable working pressure,
P = the minimum thickness of the chest,
T = the external diameter of the chest,
D = allowable stress for the material to be determined on the basis given in clause (d) above.
f = the minimum positive tolerance as specified hereunder:
C = For Cast Steel Chest C = 5 mm.
For forged or stainless steel chest C = 2.5 mm.Parts of this extracted text look garbled; read the Gazette page before using any value.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
In short
Regulation 191 covers the soundness, hydraulic testing, fabrication and thickness design of valve chests and fittings, and how many valves are presented to the Competent Person.
Key points
- (1)(a) Chests and fittings must be smooth, sound and free from flaws or cracks. After completion, chests are hydraulically tested at minimum one and half times the maximum allowable working pressure of the valve.
- (1)(b) The test liquid may be water (with or without a corrosion inhibitor), kerosene or another suitable liquid whose viscosity is not greater than that of water, at a test temperature not above 52°C.
- (2)(a)(i) Valves may be fabricated from seamless steel pipes for pressures not exceeding 17.6 kg/cm²(g) and temperatures not exceeding 426°C. Welding must conform to regulation 97 and the chest must be stress relieved.
- (2)(a)(ii) Valves for pipe work may be fabricated by welding from seamless pipes without those limits, provided the welding meets the fusion welding requirements of Chapter-4 (such as stress relieving and radiography).
- (2)(b) Chest working pressure is found from equation (7/3), with "2 fE" replaced by "1.8 x f".
- (3) Bronze and cast iron chests use Equations (5/1) and (5/2), with C = 1.5 mm for bronze and C = 5 mm for cast iron, subject to the minimum thickness in regulation 184.
- (4) Steel chests of circular section use Equations (5/3) and (5/4). The allowable stress f is taken from the governing material code or, if unavailable, worked out from yield, rupture and creep values, with separate rules at or below and above 454°C. Cast steel gets 80 per cent of that stress. C = 5 mm for cast steel and 2.5 mm for forged or stainless chests.
- (5)(a) Table 5/1A sets how many valves and fittings, by size, are made available to the Competent Person.
- (6) Steel chests of spherical section use Equations (5/5) and (5/6).
Watch out
- The symbol lists under the equations and Table 5/1A are misaligned in the extracted text. Check the Gazette page for the exact definitions and values.
- (4) A note requires the manufacturer to add thickness for assembly and valve closing stresses, non-circular shapes and stress concentrations, to the satisfaction of the Inspecting Authority.
- (5)(b) For valves above 10.5 kg/cm²(g) or 204°C, the Inspecting Authority may test on a sample basis if satisfied with the manufacturer's facilities and that each fitting is tested at the works.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 52 | General | 100% | Chapter II (DPIIT scan), image 9 |
| 276 | General | 100% | Chapter V (DPIIT scan), image 11 |
| 317 | General | 100% | Chapter VI (DPIIT scan), image 7 |
Amendment history of the candidate IBR 1950 regulations: Reg. 52 (2 amendments)
IBR 1950 regulation 52 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 52 page for its amendments.
| Reg. 52 MATERIALS OF CONSTRUCTION SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE |
| (i) These regulations cover both hot finished and cold drawn seamless pipes of ferritic alloy steel grades. These shall conform in all respects with the requirements herein specified. (ii) The seamless pipes conforming to other national/international standards which are known to be commonly used as being suitable for high temperature service can also be used with the designations of the national/international standards, provided such materials are not specifically prohibited by the regulations. (iii) While making pipes to other national/international standards the allowable stresses of the respective standard shall be strictly followed while designing the tubes. (iv) The design metal temperatures shall not exceed the following limits Grade Temp. Degree C (Degree F) P1, P2 537 (1000) P5, P9, P11, P12, P22, P91, X20CrMoV121 648 (1200) |
IBR 1950 regulation 276 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 276 page for its amendments.
|
| ||||||||||||||||||||||||||||||||
Reg. 277
| ||||||||||||||||||||||||||||||||
IBR 1950 regulation 317 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 317 page for its amendments.
| Reg. 317, Reg. 318, Reg. 319, Reg. 320 | ||||||||||||||||||||
Reg. 318 Blow-down Mountings
Reg. 319 Blow-down Valve or Cock
Reg. 320 WATER GAUGES
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.



Indian Boiler Regulations, 2026, reg. 191, Regulation 191, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.627–629. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.