BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 5 · Valves, Gauges and Auxiliaries

Regulation 191. Chests and fittings in General

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 627–629TableFormula / symbols

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

191. Chests and fittings in General.─(1) (a) All chests and fittings shall be smooth, sound and free from flaws, cracks or other injurious defects and after completion, the chests shall be hydraulically tested at minimum one and half times the maximum allowable working pressure of the valve for which they are intended.

(b)Hydraulic test shall be made with water which may contain a corrosion inhibiter, with kerosene or with other suitable liquid provided its viscosity is not greater than that of water at a test temperature not above 52°C.

(2)(a) (i) Valves may be fabricated from seamless steel pipes for pressures not exceeding 17.6 kg/cm2(g) and temperatures not exceeding 426°C.The welding shall conform to regulation 97 and valve chest shall be stress relieved after fabrication.

(ii)Valves meant for use in pipe work may also be fabricated by welding from seamless steel pipes but no restriction as above regarding pressure and temperature shall apply to them provided the welding complies with all the relevant requirements of fusion welding such as stress relieving and radiographic inspection of the weld as prescribed in Chapter-4 of these regulations.

(b)The maximum allowable working pressure of the chests shall be determined by equation (7/3), where the term ‘2 fE’ shall be substituted by the term ‘1.8 x f’.

(3)The maximum allowable working pressure and the thickness of the bronze and cast Iron valve chests shall be determined by the following formulae, subject to the minimum thickness as specified in sub-regulation

(2)of regulation 184.

                        R x (T – C)

                        P = --------------                             Equation (5/1)

                        4.5 x D

                                  4.5 x P x D                          Equation (5/2)
                        T = ---------------- + C

                                      R

Where,             is maximum allowable working pressure
P                  is the minimum specified tensile strength of the grade of the material,
R                  is the external diameter of the chest,
D                  is the minimum thickness of the chest, excluding tolerance, and
T                  is the minimum positive tolerance as specified hereunder:

C

For Bronze Chests C = 1.5 mm
For Cast Iron Chests C = 5 mm

(4)The maximum allowable working pressure and the thickness of the steel valve chests of circular cross-section shall be determined by the following formulae, namely: -

      2f (T – C)     Equation (5/3)
P = ---------------

      D – T + C

               P x D
        T = ------------- + C Equation (5/4 )

               2f + P

Where,
P is maximum allowable working pressure in kg/cm2(g)

f = maximum allowable stress as available in the governing codes of the country of the material to which it belongs in kg/mm2. In case of non-availability of the value, the following procedure for evaluating the allowable stress values shall be adopted.

For temperature at or below 454°C is the lower of the following two values:

        Et                           R

f =                        f =

        1.5                          2.7

For temperature above 454°C the least of the following three values-

                       Et                Sr    (c) f = Sc
             (a) f = ---        (b) f = -----

                     1.5                 1.5

Where,

Et = Minimum value of yield point (0.2 per cent proof stress) at temperature ‘t’,

R = Minimum specified tensile strength for the grade of steel concerned at room temperature,

Sr = the average stress for the grade of steel concerned to produce rupture in 100,000 hours.

If the width of the scatter band of results obtained when determining this value exceeds + 20 per cent of the average value, then Sr shall be taken as 1.25 times the minimum stress at temperature ‘t’ to produce rupture in 100,000 hours.

Sc = The average stress to produce an elongation (creep) for the grade of steel concerned of 1 percent in 100,000 hours at temperature ‘t’. For metal temperature ‘t’ below 250°C values ‘f’ for 250°C shall be used.

Note: In case Sc values are not available in Material Standard and such materials are known to have been used in boiler in India or abroad, then for such materials, the allowable stress may be taken as the lower of

EtSr
or
1.51.5

Columns reconstructed from the extracted text; check against the Gazette page.

Show original extracted text (diagnostic, not authoritative)
Et                      Sr

     or

1.5                     1.5

Note: The allowable stress for cast steel shall be 80 per cent of that determined on the above basis.

D = the external diameter of the chest,
T = the minimum positive tolerance as specified hereunder:

For cast steel chest C = 5 mm
For forged or stainless chest C = 2.5 mm

Note: Over and above the calculated thickness, additional thickness needed for assembly stresses, Valve closing stresses, shapes other than circular and stress concentrations, shall be provided by the manufacturers to the satisfaction of the Inspecting Authority.

(5)(a) The number of valves and fittings which shall be made available to the Competent Person (excluding mechanical tests) shall be, following, namely:-

Serial                                                       Table 5/1A                Number
Serial No.Size of valves and fittingsNumber
(1)(2)(3)
1.Up to and including 51 mm10 per cent
2.Over 51 mm and up to and including 76 mm15% of the number of chests
3.Over 76 mm and up to and including 114 mm20% of the number of chests
4.Over 114 mm100 per cent.

Table structure read from the Gazette PDF, page 629. Verification status as for the text above.

Show original extracted text (diagnostic, not authoritative)
No.                                  Size of valves and fittings
                                                                                          (3)
  (1)                                              (2)                   10 per cent
     1.            Up to and including 51 mm                             15% of the number of chests
     2.            Over 51 mm and up to and including 76 mm              20% of the number of chests
     3.            Over 76 mm and up to and including 114 mm
     4.            Over 114 mm                                                     100 per cent.

(b)If the Inspecting Authority is satisfied that the manufacturer has adequate facilities for testing and Inspection of valves intended for service pressure exceeding 10.5 kg/cm2(g) or temperature exceeding 204°C and actually tests each fitting at his works, the Inspecting Authority may, at his discretion, undertake test on a sample basis.

(6)The maximum allowable working pressure and the minimum thickness of the steel valve chest of spherical cross section shall be determined by the following formula, namely,

                               4f (T – C)                                Equation (5/5)
                   P = ----------------

                              D – 0.8 (T – C)

                              P x D                                      Equation (5/6)
                   T = --------------- + C

                             4f + 0.8 P

Where,             maximum allowable working pressure,
P =                the minimum thickness of the chest,
T =                the external diameter of the chest,
D =                allowable stress for the material to be determined on the basis given in clause (d) above.
f =                the minimum positive tolerance as specified hereunder:
C =                For Cast Steel Chest C = 5 mm.
                   For forged or stainless steel chest C = 2.5 mm.

Parts of this extracted text look garbled; read the Gazette page before using any value.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Referenced provisions

Reg. 97 · Reg. 184

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 191 covers the soundness, hydraulic testing, fabrication and thickness design of valve chests and fittings, and how many valves are presented to the Competent Person.

Key points

  • (1)(a) Chests and fittings must be smooth, sound and free from flaws or cracks. After completion, chests are hydraulically tested at minimum one and half times the maximum allowable working pressure of the valve.
  • (1)(b) The test liquid may be water (with or without a corrosion inhibitor), kerosene or another suitable liquid whose viscosity is not greater than that of water, at a test temperature not above 52°C.
  • (2)(a)(i) Valves may be fabricated from seamless steel pipes for pressures not exceeding 17.6 kg/cm²(g) and temperatures not exceeding 426°C. Welding must conform to regulation 97 and the chest must be stress relieved.
  • (2)(a)(ii) Valves for pipe work may be fabricated by welding from seamless pipes without those limits, provided the welding meets the fusion welding requirements of Chapter-4 (such as stress relieving and radiography).
  • (2)(b) Chest working pressure is found from equation (7/3), with "2 fE" replaced by "1.8 x f".
  • (3) Bronze and cast iron chests use Equations (5/1) and (5/2), with C = 1.5 mm for bronze and C = 5 mm for cast iron, subject to the minimum thickness in regulation 184.
  • (4) Steel chests of circular section use Equations (5/3) and (5/4). The allowable stress f is taken from the governing material code or, if unavailable, worked out from yield, rupture and creep values, with separate rules at or below and above 454°C. Cast steel gets 80 per cent of that stress. C = 5 mm for cast steel and 2.5 mm for forged or stainless chests.
  • (5)(a) Table 5/1A sets how many valves and fittings, by size, are made available to the Competent Person.
  • (6) Steel chests of spherical section use Equations (5/5) and (5/6).

Watch out

  • The symbol lists under the equations and Table 5/1A are misaligned in the extracted text. Check the Gazette page for the exact definitions and values.
  • (4) A note requires the manufacturer to add thickness for assembly and valve closing stresses, non-circular shapes and stress concentrations, to the satisfaction of the Inspecting Authority.
  • (5)(b) For valves above 10.5 kg/cm²(g) or 204°C, the Inspecting Authority may test on a sample basis if satisfied with the manufacturer's facilities and that each fitting is tested at the works.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
52General100%Chapter II (DPIIT scan), image 9
276General100%Chapter V (DPIIT scan), image 11
317General100%Chapter VI (DPIIT scan), image 7

Amendment history of the candidate IBR 1950 regulations: Reg. 52 (2 amendments)

IBR 1950 regulation 52 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 52 page for its amendments.

Reg. 52
MATERIALS OF CONSTRUCTION

SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE

General

(i) These regulations cover both hot finished and cold drawn seamless pipes of ferritic alloy steel grades.  These shall conform in all respects with the requirements herein specified.

(ii)  The seamless pipes conforming to other national/international standards which are known to be commonly used as being suitable for high temperature service can also be used with the designations of the national/international standards, provided such materials are not specifically prohibited by the regulations.

(iii)  While making pipes to other national/international standards the allowable stresses of the respective standard shall be strictly followed while designing the tubes.

(iv)   The design metal temperatures shall not exceed the following limits

Grade                                                              Temp. Degree C (Degree F)

P1, P2                                                                          537 (1000)

P5, P9, P11, P12, P22, P91, X20CrMoV121                    648 (1200)

IBR 1950 regulation 276 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 276 page for its amendments.


Reg. 276, Reg. 277


General

The thickness T specified in equation 74 of Regulation 278 is the thickness of the end plate after manufacture and is applicable over the whole area of the end plate up to the point where, for ends of partially spherical shape, the dishing radius joins the corner radius; from this point a gradual thinning is permissible up to maximum of 10 per cent of the thickness T at the point where the corner radius joins the straight portion of flanged end plate. A similar gradual thinning is permissible for end plates of semi-ellipsoidal shape. This permissible reduction in thickness applies also to the flange for the manhole opening. In no case, however, when the end plate is but welded to the drum shell, shall the thickness of the edge of the flange for connection to the shell be less than the thickness of an unpierced seamless shell of the same diameter and material, determined by equation 72.


Reg. 277

Dished End with Opening

a) Heads with openings:-
i) Holes cut in the heads (manholes or tube holes) should be round or elliptical.
ii) Small size openings complying with conditions of sub-regulation (c) do not require any additional thickness of head or reinforcement of opening.
iii)

Large size openings require an increase in thickness of the head, according to sub-regulation (b) or a reinforcement of the opening according to sub-regulation (d).

b) Shape factor K for heads with large unreinforced openings:- The shape factor K to be used in calculating the thickness of heads varies depending on the height of the head H and on the dimensions of the largest opening. The value of K is indicated in Fig. 23D, by means of curves, each of which corresponds to a value of the ratio.-
   d  ---------
Ö D T

where,

d = diameter of the largest opening in the head (in the case of an elliptical opening, the larger diameter of the ellipse);
D = outside diameter of the head; and
T = minimum thickness after dishing.

In addition, the following conditions shall be satisfied:

T < 0.1
D

d < 0.5
D

The same condition and the same curves apply for openings simply cut in the plate of the head as well as to those which are flanged inwards. In the latter case, the radius r’ of the flanging (see Fig. 23C) should not be smaller than 25 mm (1 inch). The thickness of the flanged portion may be smaller than the calculated thickness T.

Unreinforced openings and flanged-in openings in dished heads shall be arranged so that the distance from the edge of the head is not less than as shown in Fig. 23E.

In all cases the width of the band separating two adjacent openings should, in projection, be at least equal to the diameter of the smallest opening as shown in Fig. 23E.
c) Small openings which do not require any reinforcement:-

Figure 23D indicates that for a given ratio of H/d, the shape factor K of a plain head corresponds to a certain values of the ratio,

d       
(DT)1/2

Piercing of holes with a diameter smaller than or equal to that which corresponds to this value can thus be made without any reinforcement in a head, the thickness of which is equal to the minimum required for a plain head.

The position of those openings shall however comply with the conditions stated in sub-regulation (b).

d) Reinforcement of large openings:-Large holes may be cut without increasing the thickness of the head, provided they are sufficiently reinforced.

The reinforcement may consist either of a welded nozzle or one or two reinforcing welded plates, or of a combination of these two procedures.

To determine the strength of the construction, one shall proceed as follows (see Fig. 23F). Let the imaginary diameter d’ of the opening be given by the formula

d' = d - A
T

where,

d = actual diameter of the opening in the head (outside diameter of the nozzle);
T = minimum thickness of the head; and
A = effective cross-section of reinforcement.

This effective area A corresponds, within the Limits given below, with the actual cross-section of the reinforcing plates and with the cross-section of the nozzle decreased by the cross-section necessary to support the pressure, for those parts of the nozzle situated outside the internal surface of the head.

The shape factor K can then be read corresponding to the ratio
     
d         
(DT)1/2

The maximum limits for the are of reinforcement that should be taken into account are

(a) L1 = (2 RT)1/2. for the width of a reinforcing plate;
(b) L2 = (d Tt)1/2 for the length of a nozzle.

where,

R = internal radius of the spherical part of the head (or for elliptical heads the internal radius of curvature of the meridian at the centre of the opening)
Tt = actual thickness of the nozzle,
L1 and L2 = dimensions given in Fig. 23F.

The position of the outer edges of the reinforcement shall comply with the provisions of sub-regulation (b) and Fig. 23E.

In cases where the allowable stress of a part of the reinforcement is lower than that of the head, the corresponding area A should be multiplied by the ratio:

allowable stress of the reinforcement material -------------------------------------------------------------------------------------- allowable stress of the head material
IBR 1950 regulation 317 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 317 page for its amendments.

Reg. 317, Reg. 318, Reg. 319, Reg. 320
BLOW-DOWN COCK OR VALVE AND PIPES

General

The blow down cock or valve shall be of substantial construction. The waste pipe attached to the cock or valve shall not be bound fast in earth or brick work and shall discharge at a point where there is no danger of injury to any person. These pipes shall not be connected to a pipe common to another boiler. The continuous blow-downs may, however, be connected to a common header discharging freely to an adequately vented tank or sump. The headers shall be of sufficiently large cross section and the blow-off tank shall be provided with a vent pipe free from valves and of sufficient size to prevent accumulation of pressure. If, however, the tank is intended for collecting flash steam, a safety valve of adequate capacity shall be provided. The tank shall be so located that all parts will be accessible for inspection.


Reg. 318

Blow-down Mountings

a) Each boiler shall be fitted, with a suitable blow down valve or cock placed at, or as near as practicable, to the lowest point of the boiler.
b) For locomotive, vertical and marine type boilers, the valve or cock shall be

attached direct to the boiler or to a suitable pad or stand pipe. For water tube boilers the valve or cock shall be outside the brickwork with a substantial steel pipe between it and the mudbox.

c) For Cornish and Lancashire boilers the cock or valve may be attached to a cast steel elbow pipe of substantial section bolted to a suitable stand pipe or pad riveted to the boiler. But cast iron elbow pipes shall not be permitted.


Reg. 319

Blow-down Valve or Cock

a) Each valve or cock shall be fitted with a device which shall indicate clearly its open and closed positions, and any key or similar device for operating the valve or cock shall be such that it cannot be removed unless the valve or cock is fully closed.
b) The locking feather shall be secured by welding.
c) Cocks fitted with taper plugs shall be of the bolted cover type with separate packing glands.


Reg. 320
WATER GAUGES

a) Every boiler shall have two means of indicating the water in it of which one shall be conventional gauge glass:

Provided that in the case of boiler drums below 3 feet (91 cm) diameter where there is difficulty in fitting two water gauges, two test cocks and a glass water gauge shall be fitted.
b) The lowest visible part of the glass of the water gauge and lower test cock shall be fixed at safe working level. For locomotive type and vertical boilers this shall not be less than 50 millimetres above the highest part of the firebox roof plate.

Minimum length of the visible portion of the gauge glasses shall be 200 mm. The length may be increased depending upon the capacity of the boiler by the Chief Inspector/Director of boiler of the manufacturing State.
c) Glass water gauges shall be so placed as to be easily seen and reached by the boiler attendant. The fittings of glass water gauges and test cocks shall be of substantial make with large passage ways through them to facilitate cleaning. The gauge cocks when open shall have their handles in a vertical direction and each handle at its junction with the plug shall be plainly marked with a deep line to indicate the direction of the passage way through the plug. When detachable handle are provided arrangement shall be made to prevent incorrect fitting of the handles.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
627–629
PDF page index
627–629 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 78c0d0b6e736e31e
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 191, Regulation 191, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.627–629. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.