Regulation 186. Covers and Spindles

Official text — not yet verifiedGazette 1 Oct 2026 · printed p. 626

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

186. Covers and Spindles.─(1)Valves of 38 mm bore and above directly connected to boilers, and other valves of 63 mm bore and over where fitted with a cover shall have such cover secured by bolts or studs and the screwed portion of the spindle shall be outside the stuffing box. All valves for superheated steam shall be fitted with an external screwed spindle.

(2)(a) Where the covers of valves are secured by studs shall be screwed into the body with full thread for a length of at least one diameter.

(b)The stud holes shall not penetrate into the pressure space of any casting.

(3)Valves with screwed covers shall be fitted with suitable locking device to prevent rotation of the cover.

Independent explanation — not the law · draft · engineer review in progress

In short

Regulation 186 sets rules for valve covers and spindles, including how covers are secured and where the spindle thread sits.

Key points

  • (1) Valves of 38 mm bore and above directly connected to boilers, and other valves of 63 mm bore and over that have a cover, must have the cover secured by bolts or studs, and the screwed part of the spindle must be outside the stuffing box.
  • (1) All valves for superheated steam must have an external screwed spindle.
  • (2)(a) Where covers are secured by studs, the studs must be screwed into the body with full thread for a length of at least one diameter.
  • (2)(b) Stud holes must not penetrate into the pressure space of any casting.
  • (3) Valves with screwed covers need a suitable locking device to stop the cover rotating.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

No candidate heading found in the historical print edition.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
626
PDF page index
626 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash de44b7bbc7a02714
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 186, Regulation 186, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.626. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.