BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 2026 · Chapter 17 · Small Solar Boilers

Regulation 591. Materials

Official text — not yet verifiedGazette 1 Oct 2026 · printed pp. 865–866

Not yet checked against the official Gazette; verify before relying on it.

Reproduced from the Gazette of India · verification status above

591. Materials.─ (1) The materials used in the construction of small solar boilers shall conform to the provisions made in these regulations.

(2)(a) Plates used in the construction of the boilers shall be either of IS: 2062 or equivalent or as per Chapter-2.

(b)The plate for shell and heads shall be not less than 6 mm in thickness and the heads as tube sheets for tubes rolled in shall be at least 8 mm in thickness.

(3)The tubes and pipes shall be made of carbon steel, alloy steel, stainless steel or copper.

(4)Corrosion allowance of 0.75 mm shall be provided for parts of the boiler directly exposed to atmosphere and solar radiation.

(5)No corrosion allowance is required for stainless steel parts of the boiler.

(6)Materials need not be certified with Indian Boiler Regulations forms from the maker provided all other certification requirements as mentioned in applicable regulations are complied with.

Independent explanation — not the law · draft · engineer review in progress

In short

This regulation sets the materials, minimum plate thicknesses and corrosion allowance for small solar boilers, and relaxes material certification on IBR forms.

Key points

  • (1) Materials must conform to the provisions of these regulations.
  • (2)(a) Plates must be IS: 2062 or equivalent, or as per Chapter-2.
  • (2)(b) Plates for shell and heads: not less than 6 mm thick. Heads acting as tube sheets for rolled-in tubes: at least 8 mm thick.
  • (3) Tubes and pipes may be carbon steel, alloy steel, stainless steel or copper.
  • (4) A corrosion allowance of 0.75 mm is required on parts directly exposed to atmosphere and solar radiation.
  • (5) Stainless steel parts need no corrosion allowance.
  • (6) Materials need not be certified on Indian Boiler Regulations forms from the maker, provided all other certification requirements in the applicable regulations are met.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
6Standard specifications for materials100%Chapter I (DPIIT scan), image 3
626Materials100%Chapter XV (DPIIT scan), image 1

Amendment history of the candidate IBR 1950 regulations: Reg. 626 (1 amendment)

IBR 1950 regulation 6 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 6 page for its amendments.

Reg. 6
Standard specifications for materials.

The standard specifications for steel wrought iron and copper plates and bar, and for cast steel shall be those prescribed in Chapter II.

IBR 1950 regulation 626 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 626 page for its amendments.

Reg. 626

FEED WATER FOR BOILER


Test Methods

Tests shall be carried out as prescribed in the appropriate clauses of IS : 3025-1964* and IS : 3550-1965! as indicated against the characteristics in Table 1.

TABLE 1: CHEMICAL REQUIREMENTS OF FEED WATER AND BOILER WATER FOR LOW AND MEDIUM PRESSURE BOILERS (Regulation 624 and 626)
Sl.. No. CHARACTERISTIC REQUIREMENT FOR BOILER PRESSURE
----------------------------------------
METHOD OF TEST (Ref. to Cl. No. of)
--------------------------
Up to 2.0 2.1 to 3.9 4.0 to 5.9 IS : 3550- IS : 3025-_
MN/m2 MN/m2 MN/m2 1965* 1964!
(1) (2) (3) (4) (5) (6) (7)
i) Feed Water
a)
Total hardness
(as CaCO2 ),mg/l, Max
10 1.0 0.5 -- 16.1
-----------------------------------------------------------------------------------------------------------------------
(1) (2) (3) (4) (5) (6) (7)
b) pH value 8.5 to 9.5 8.5 to 9.5 8.5 to 9.5 -- 8
c) Dissolved Oxygen, mg/1, Max 0.1 0.02 0.01 25 --
d) Silica (as SiO2), mg/l, Max -- 5 0.5 16 --
ii) Boiler Water
a) Total hardness(of filteredsample) (as CaCO3), mg/l, --------- Not detectable ------------- -- 16.1
b

Total alkalinitya (as CaCO3), mg/l,Max

700 500 300 -- 13
c) Caustic alkalinity (as CaCO3), mg/lMax 350 200 60 -- 15
d) pH value 11.0 to 12.0 11.0 to 12.0 10.5 to 11.0 -- 8
e) b Residual sodi um sulphite (asNa2SO3) mg/l
30 to 50 20 to 30 -- -- 21
f) Residual hydrazine (as N2H4),mg/l 0.1 to 1
(if added)
0 .1 to 0.5
(if added)
0.05 to 0.3 26 --
g) j Ratio Na2SO4/Caustic alkalinity (as NaOH)
               or
Ratio NaNO3/ total alkalinity (as NaOH)
------------ above 2.5 --------------- -- 20.2
and 15
------------- above 0.4 ---------------- -- 48
and 13
h) Phosphates (asPO4), mg/l (if added )

20 to 40 15 to 30 5 to 20 14 --
i) Total dissoslved solids mg/l, Max 3500s 2500 1500 9 12
k) Silica (as SiO2), mg/l Less than 0.4 of caustic
alkalinity
15 16 30
------------------------------------------------------------------------------------------------------------------------
Note 1- Recovery Boilers - The boiler feed water used shall be completely de-mineralized and also the boiler feed water and boiler water shall be conditioned in accordance with high pressure boilers working at 60 kg/cm2 and above (see IS : 4343-1967**)

Note 2 - When feed water heaters are of copper or copper alloy constructions, the pH of the feed water shall be maintained between 8.5 and 9.2 while when feed water heaters are of iron constructions, the pH of the feed may be maintained between 8.5 and 9.5.

Note 3 - Silica in Boiler Water - Lower concentration of silica may be advisable for steam of turbines, which generally requires less than 0.02 mg/l silica in steam.

* Methods of test for routine control for water used in industry.

! Methods of sampling and test (physical and chemical) for water used in industry.

a Total alkalinity should preferably be about 20 percent of total dissolved solids.

b Shall not apply if reducing agents other than sodium sulphite are used.

j For riveted boilers only.

s For shell type boilers depending on parameters, the limits can be relaxed.

** Code of practice for treatment of water for high pressure boilers (under revision).

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
865–866
PDF page index
865–866 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 5bcdaa1e827b8bcf
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 591, Regulation 591, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.865–866. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.