277. Materials in the construction of steam receivers, separators, catch waters , accumulators and similar vessels.─(1)Material for plates, bars and sections used in the construction of steam receivers, separators, catch waters, accumulators and similar Vessels shall comply in all respects with the requirements of relevant regulations of Chapters-2 and 4, depending upon the mode of construction.

(2)Branches, bosses and drain pockets may be solid forged, fabricated by fusion welding, machined from solid bars or made from tubes.

(3)Materials for flanges shall comply with the appropriate provisions of regulation 258.

(4)Forgings shall comply with the requirements of regulations 58 to 62

(5)Steel castings for shells or pressure parts of shell shall comply with regulations 51 to 57.

Referenced provisions

Reg. 5 · Reg. 51 · Reg. 57 · Reg. 58 · Reg. 62 · Reg. 258

Independent explanation — not the law · draft · engineer review in progress

In short

This regulation sets material requirements for steam receivers, separators, catch waters, accumulators and similar vessels.

Key points

  • (1) Plates, bars and sections must meet the relevant regulations of Chapters-2 and 4, depending on the mode of construction.
  • (2) Branches, bosses and drain pockets may be solid forged, fusion welded, machined from solid bar or made from tubes.
  • (3) Flange materials per regulation 258.
  • (4) Forgings per regulations 58 to 62.
  • (5) Steel castings for shells or shell pressure parts per regulations 51 to 57.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
626Materials100%Chapter XV (DPIIT scan), image 1
416Construction and Workmanship73%Chapter X (DPIIT scan), image 5
624Construction and Workmanship73%Chapter XV (DPIIT scan), image 1

Amendment history of the candidate IBR 1950 regulations: Reg. 626 (1 amendment) · Reg. 624 (1 amendment)

IBR 1950 regulation 626 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 626 page for its amendments.

Reg. 626

FEED WATER FOR BOILER


Test Methods

Tests shall be carried out as prescribed in the appropriate clauses of IS : 3025-1964* and IS : 3550-1965! as indicated against the characteristics in Table 1.

TABLE 1: CHEMICAL REQUIREMENTS OF FEED WATER AND BOILER WATER FOR LOW AND MEDIUM PRESSURE BOILERS (Regulation 624 and 626)
Sl.. No. CHARACTERISTIC REQUIREMENT FOR BOILER PRESSURE
----------------------------------------
METHOD OF TEST (Ref. to Cl. No. of)
--------------------------
Up to 2.0 2.1 to 3.9 4.0 to 5.9 IS : 3550- IS : 3025-_
MN/m2 MN/m2 MN/m2 1965* 1964!
(1) (2) (3) (4) (5) (6) (7)
i) Feed Water
a)
Total hardness
(as CaCO2 ),mg/l, Max
10 1.0 0.5 -- 16.1
-----------------------------------------------------------------------------------------------------------------------
(1) (2) (3) (4) (5) (6) (7)
b) pH value 8.5 to 9.5 8.5 to 9.5 8.5 to 9.5 -- 8
c) Dissolved Oxygen, mg/1, Max 0.1 0.02 0.01 25 --
d) Silica (as SiO2), mg/l, Max -- 5 0.5 16 --
ii) Boiler Water
a) Total hardness(of filteredsample) (as CaCO3), mg/l, --------- Not detectable ------------- -- 16.1
b

Total alkalinitya (as CaCO3), mg/l,Max

700 500 300 -- 13
c) Caustic alkalinity (as CaCO3), mg/lMax 350 200 60 -- 15
d) pH value 11.0 to 12.0 11.0 to 12.0 10.5 to 11.0 -- 8
e) b Residual sodi um sulphite (asNa2SO3) mg/l
30 to 50 20 to 30 -- -- 21
f) Residual hydrazine (as N2H4),mg/l 0.1 to 1
(if added)
0 .1 to 0.5
(if added)
0.05 to 0.3 26 --
g) j Ratio Na2SO4/Caustic alkalinity (as NaOH)
               or
Ratio NaNO3/ total alkalinity (as NaOH)
------------ above 2.5 --------------- -- 20.2
and 15
------------- above 0.4 ---------------- -- 48
and 13
h) Phosphates (asPO4), mg/l (if added )

20 to 40 15 to 30 5 to 20 14 --
i) Total dissoslved solids mg/l, Max 3500s 2500 1500 9 12
k) Silica (as SiO2), mg/l Less than 0.4 of caustic
alkalinity
15 16 30
------------------------------------------------------------------------------------------------------------------------
Note 1- Recovery Boilers - The boiler feed water used shall be completely de-mineralized and also the boiler feed water and boiler water shall be conditioned in accordance with high pressure boilers working at 60 kg/cm2 and above (see IS : 4343-1967**)

Note 2 - When feed water heaters are of copper or copper alloy constructions, the pH of the feed water shall be maintained between 8.5 and 9.2 while when feed water heaters are of iron constructions, the pH of the feed may be maintained between 8.5 and 9.5.

Note 3 - Silica in Boiler Water - Lower concentration of silica may be advisable for steam of turbines, which generally requires less than 0.02 mg/l silica in steam.

* Methods of test for routine control for water used in industry.

! Methods of sampling and test (physical and chemical) for water used in industry.

a Total alkalinity should preferably be about 20 percent of total dissolved solids.

b Shall not apply if reducing agents other than sodium sulphite are used.

j For riveted boilers only.

s For shell type boilers depending on parameters, the limits can be relaxed.

** Code of practice for treatment of water for high pressure boilers (under revision).

IBR 1950 regulation 416 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 416 page for its amendments.

Reg. 413, Reg. 414, Reg. 415, Reg. 416
RIVETED STEEL BOILERS

Thickness of Angle Rings

Where flange or angle rings are used for pressure purposes in no case shall the thickness after machining be less than 5/16 inch. The thickness shall be as given in Regulation 106.



Reg. 414
RIVETED STEEL BOILERS

Bolts, Nuts and Studs

These shall conform to Regulation 208.



Reg. 415
RIVETED STEEL BOILERS

Hydraulic Test

Each completed boiler shall pass the hydraulic adopted see Fig 44, 45, 46, 47, 48 & 49.



Reg. 416
FUSION WELDED BOILERS

Construction and Workmanship

Construction and workmanship shall comply with the provisions made in Chapter V for fusion welded drums subject to the following conditions, namely:-

Class I boilers shall comply with the requirements of Chapter V.
For end plate connection by welding, the type of steam shown in Figure 44 may be adopted.
Class II boilers shall comply with the following requirements.

The longitudinal seams shall comply with Regulation 253. For end plate connections by welding any of the following types of seams, may be adopted (see Figure 44,45,46,47,48 & 49 ).

Forms of welded joints for circumferential seams acceptable for  for all class of boilers

acceptable For Class II welded boilers

Forms of welded joints for circumferential seams acceptable for seamless shell boilers and for Class II boilers.

For plates over 3/4 inch thick, width of gap between the edges of the plates to be agreed upon by inspecting authority & manufacturer.

Forms of welded joints for circumferential seams acceptable for seamless shell boilers and for Class II boilers.

FORMS OF WELDED JOINTS FOR FLAT END PLATES FOR CLASS II BOILERS NOT EXCEEDING 20 INCH DIAMETER.

Class I Boilers, the working pressure of which exceeds 165 lbs./ sq. in. or the product of the working pressure in pounds per square inch and the internal diameter in inches exceeds 8250.

Class II Boilers, the working pressure of which is 165 lbs./sq. in. and below or the product of the working pressure in pounds per square inch and the internal diameter in inches is below 8250.

IBR 1950 regulation 624 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 624 page for its amendments.

Reg. 623, Reg. 624, Reg. 625
FEED WATER FOR BOILER

Scope

a)

This chapter lays down specifications for feed water and boiler water for low and medium pressure boilers (boilers operating up to 60 kg/cm2).
b) For boilers operating at pressures higher than 60 kg/cm2, better quality of water to IS:10496-1983 may be adopted.


Reg. 624

Requirements

The water shall comply with the requirements given in Table 1 when tested by the methods prescribed in col. 6 and 7 of the table.


Reg. 625

Sampling

Sampling shall be done following general directions given in 2 of IS:3025-1964*. In particular, the following points shall be observed :

a) It is necessary that a stainless steel or monel metal coil is fitted on the sampling cock so that the temperature of the water sample will be well below the boiling point at atmospheric pressure and there is no risk of aeration and concentration due to flashing into steam; and
b) Samples of feed water shall be collected from the delivery of the boiler feed pump, samples of boiler water from the top drum, and samples of condensate from the delivery of the condensate extraction pump.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
675–676
PDF page index
675–676 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash 9dddc2d4935d556b
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 277, Regulation 277, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.675–676. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page

Engineers like you keep IBRsource accurate. Every checked correction or tip helps the next reader.