285. Steel screwed and socketed joints and mountings of steel.─(1) Steel couplings or sockets may be used on pipes within the limits given in Table-7/12 below:-

Table 7/12

Serial No.Nominal boreMaximum Allowable Working PressureMaximum permissible temperature
kg/cm2 (g)°C
(1)(2)(3)(4)
1.Upto and including 25 mm
Over 25 mm upto and including 38 mm
12.25
10.5
260
260
2.Over 38 mm upto and including
75 mm
8.75
7
260
260
3.Over 76 mm upto and including 102 mm8.5177
4.Over 102 mm upto and including 127 mm7171

Table structure read from the Gazette PDF, page 691. Verification status as for the text above.

Show original extracted text (diagnostic, not authoritative)
Serial No.                Nominal bore                            Maximum         Maximum permissible
                                                                  Allowable             temperature
    (1)                                                       Working Pressure
      1.                                                                                      °C
                                                              kg/cm2 (g)                     (4)
      2.                                                                                     260
                          (2)                                      (3)
      3.                                                                                     260
      4.           Upto and including 25 mm                   12.25                          260
                   Over 25 mm upto and including 38 mm        10.5
                                                                                             260
                   Over 38 mm upto and including                   8.75                      177
                                                                                             171
                   75 mm

                                                                   7

                   Over 76 mm upto and including 102 mm            8.5

                   Over 102 mm upto and including 127 mm           7

(2)Screwed joints shall be permitted at temperatures exceeding 260°C and size or pressure limits in excess of those given in the Table 7/12 of this regulation provided that the following conditions are satisfied, namely:-

(a)all threads are tapered unless pressure tightness depends on a seal weld or a seating surface other than the threads and experience or test demonstrates the suitability of the joint.

(b)pressure or temperature rating in appropriate component standard like BS, ASME, DIN or calculated as per relevant regulation is not exceeded.

(c)minimum specified tensile strength of screwed pipes is greater than 30.5 kg/mm2.

(d)the minimum thickness of screwed pipes is not to be less than that given in Table 7/13 of this regulation.

(e)the design temperature does not exceed 495°C.

(f)the pressure limits given in Table 7/14 of this regulation are not exceeded.

(3)Screwed joints are permitted for temperatures in excess of 495°C and pressure in excess of those given in Table 7/14 of this regulation for instrument insertion and tapping and for plug for access opening for radiographic inspection provided following conditions are satisfied:-

(a)They do not exceed 50 mm nominal bore size or one quarter of nominal pipe size, whichever is the smaller.

(b)The minimum thread engagement is not less than –

(i)6 for up to and including 20 mm nominal bore;

(ii)7 for over 20 mm up to and including 40 mm nominal bore; and

(iii)8 for 40 mm up to and including 50 mm nominal bore.

(c)The connection is seal-welded.

(d)The design of instrument insertion withstands the fluid characteristics, fluid flow and any vibrations.

(4)Screwed joints are permitted for pressure in excess of those given in Table 7/14 up to 345 bar for dead end instrument lines at the outlet end and downstream of shut off valves and instruments, control apparatus or discharge of a sample cooler provided that the nominal bore size of the pipe does not exceed 12 mm.

Table 7/13: MINIMUM THICKNESS OF SCREWED PIPES

Serial No.Nominal Pipe size (mm)Minimum thickness
17.5 kg/cm2(g) or less for
steam 7 kg/cm2 (g) and
less for water over 105°C
(mm)
Over 17.5 kg/cm2 (g) for
steam Over 7 kg/cm2 (g)
for water over 105°C
(mm)
(1)(2)(3)(4)
1.82.243.02
2.102.313.20
3.152.773.75
4.202.873.91
5.253.384.55
6.323.564.85
7.403.685.08
8.503.915.54
9.655.167.01
10.805.497.62

Table structure read from the Gazette PDF, page 692. Verification status as for the text above.

Table 7/14: MAXIMUM ALLOWABLE WORKING PRESSURE FOR SCREWED PIPES

Serial No.Nominal pipe size (mm)Maximum allowable working pressure [kg/cm2 (g)]
(1)(2)(3)
1.Over 50 up to and including 8028
2.Over 25 up to and including 5042
3.Over 20 up to and including 2584.5
4.Up to and including 20105.5

Table structure read from the Gazette PDF, page 693. Verification status as for the text above.

Show original extracted text (diagnostic, not authoritative)
Serial No.     Nominal            Minimum thickness
            Pipe size (mm)
    (1)                     17.5 kg/cm2(g) or less for  Over 17.5 kg/cm2 (g) for
      1.           (2)      steam 7 kg/cm2 (g) and      steam Over 7 kg/cm2 (g)
      2.            8       less for water over 105°C   for water over 105°C
      3.           10       (mm)                        (mm)
      4.           15
      5.           20                    (3)                         (4)
      6.           25                   2.24                        3.02
      7.           32
      8.           40       2.31                        3.20
      9.           50
      10.          65       2.77                        3.75
                   80
                            2.87                        3.91

                            3.38                        4.55

                            3.56                        4.85

                            3.68                        5.08

                            3.91                        5.54

                            5.16                        7.01

                            5.49                        7.62


Table 7/14: MAXIMUM ALLOWABLE WORKING PRESSURE FOR SCREWED PIPES

Serial No.         Nominal pipe size (mm)          Maximum allowable working pressure [kg/cm2 (g)]

(1)                     (2)                                           (3)

1.                 Over 50 up to and including 80                     28

2.                 Over 25 up to and including 50                     42

3.                 Over 20 up to and including 25                     84.5
                                                                      105.5
4.                 Up to and including 20

Parts of this extracted text look garbled; read the Gazette page before using any value.

Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.

Independent explanation — not the law · draft · engineer review in progress

In short

This regulation sets when steel screwed and socketed joints may be used on pipes, with size, pressure and temperature limits.

Key points

  • (1) Steel couplings or sockets may be used within the nominal bore, pressure and temperature limits of Table 7/12. The table is misaligned in the extracted text; check the Gazette page for the values.
  • (2) Screwed joints may go above 260°C and beyond Table 7/12 if: threads are tapered (unless sealing is by seal weld or another seating surface, proven by experience or test); component standard ratings are not exceeded; screwed pipe tensile strength is greater than 30.5 kg/mm2; thickness meets Table 7/13; design temperature does not exceed 495°C; and Table 7/14 pressure limits are not exceeded.
  • (3) For instrument insertions, tappings and radiography access plugs, screwed joints may exceed 495°C and Table 7/14 if they are not over 50 mm nominal bore or one quarter of the nominal pipe size (whichever is smaller), meet minimum thread engagement, are seal-welded, and are designed for the fluid, flow and vibration.
  • (4) Dead end instrument lines downstream of shut off valves, instruments, control apparatus or sample cooler discharges may use screwed joints up to 345 bar, if the nominal bore does not exceed 12 mm.
  • Table 7/13 gives minimum screwed pipe thickness by size and service. Table 7/14 gives maximum pressure by size. See the Official text.

Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.

Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).

Orientation hints (unverified)

These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.

Historical 1950-edition reg.Heading as OCR'dHeading similaritySource image
135Screwed Stays70%Chapter III (DPIIT scan), image 6

Amendment history of the candidate IBR 1950 regulation: Reg. 135 (1 amendment)

IBR 1950 regulation 135 as last published in the DPIIT web edition (archived 2022)

Unofficial archived copy, not verified; see the regulation 135 page for its amendments.

Reg. 135
SCREWED STAYS
Screwed Stays

a) Screwed stays and the holes for these shall be screwed with a continuous thread.
b) The screwed threads of the stay shall be clean free from checks or imperfections, of full depth, correct Whitworth form and a good fit in the holes. The middle portion shall preferably be turned down to the bottom of the thread.
c) The stays shall be screwed with fine threads of not less than 11 threads per inch.
d) The diameter of the stay over the threads shall not be less than ¾ inch or twice

the thickness of the firebox plate whichever is the greater.
e) The pitch of the stays at the furnace of vertical boilers shall not exceed 14 times the thickness of the furnace plate.
f) Where the stays are not fitted with nuts, the ends shall be riveted over to form substantial heads.

Alternatively stays may be screwed through the shell and firebox plates and the projecting ends shall be substantially fillet welded in an approved manner. The projection of the end of the stay from the surface of the plate shall be not less than one quarter of the diameter of the stay but in no case less than ¼ inch. The full end of the stay shall be visible on completion of the welding.
g) Crown stays of Loco type boilers shall either be fitted with nuts or riveted over on the fire side.

Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Instrument
Indian Boiler Regulations, 2026 (made by the Central Boilers Board under s.40 of the Boilers Act, 2025)
Notification
F.No. P-30014/3/2021-Boiler dated 7 Aug 2026
Published
Gazette of India, Extraordinary, Part III Sec. 4, No. 596, 1 Oct 2026 (CG-DL-E-06102026-276813)
In force
1 Oct 2026 (reg. 1(3): date of publication in the Official Gazette)
Printed Gazette page
691–693
PDF page index
691–693 · open official e-Gazette PDF
Extraction
pdftotext layout mode, sequential regulation detector · text hash ad277e520ee39532
Verification
Official text — not yet verified
Amendments checked
None known after 1 Oct 2026 as of build date (not a guarantee). Amendment log
How to cite

Indian Boiler Regulations, 2026, reg. 285, Regulation 285, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.691–693. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).

The citation refers to the government publication. Cite the Gazette, not this website.

Help improve this page