Indian Boiler Regulations, 2026 · Chapter 7 · Pipes and Fittings
Regulation 261. Screwed on flanges
Not yet checked against the official Gazette; verify before relying on it.
261. Screwed on flanges.─ (1) Where flanges are secured by screwing, the screw thread on the pipes and in the flanges shall be arranged to end at a point just inside the back of boss of the flange and after the flange has been screwed on, the pipe shall be expanded into the flange by a roller expander.
(2)Such screwed and expanded flanges may be used for steam for a maximum allowable working pressure of
31.5 kg/cm2 (g) and maximum temperature of 399 0C and for feed for a maximum allowable working pressure of 42 kg/cm2 (g).
In short
Screwed-on flanges are allowed only with a specific thread arrangement and expansion, and within set pressure and temperature limits.
Key points
- (1) The thread on the pipe and flange must end just inside the back of the flange boss. After screwing on, the pipe must be expanded into the flange with a roller expander.
- (2) Such flanges may be used for steam up to a maximum allowable working pressure of 31.5 kg/cm2 (g) and 399°C, and for feed up to 42 kg/cm2 (g).
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
| Historical 1950-edition reg. | Heading as OCR'd | Heading similarity | Source image |
|---|---|---|---|
| 410 | Flanges | 100% | Chapter X (DPIIT scan), image 4 |
| 135 | Screwed Stays | 70% | Chapter III (DPIIT scan), image 6 |
Amendment history of the candidate IBR 1950 regulations: Reg. 135 (1 amendment)
IBR 1950 regulation 410 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 410 page for its amendments.
| Reg. 410, Reg. 411, Reg. 412
Reg. 411
Reg. 412
|
IBR 1950 regulation 135 as last published in the DPIIT web edition (archived 2022)
Unofficial archived copy, not verified; see the regulation 135 page for its amendments.
| Reg. 135 SCREWED STAYS Screwed Stays
|
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.

Indian Boiler Regulations, 2026, reg. 261, Regulation 261, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.655. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.