Indian Boiler Regulations, 2026 · Chapter 7 · Pipes and Fittings
Regulation 274. Steel butt Welded fittings
Not yet checked against the official Gazette; verify before relying on it.
274.Steel butt Welded fittings.─ (1) (a) Branches, bosses and drain pockets welded to the pipes shall conform to the requirements of regulations 148 to 152.
(b)Branches shall not be welded to any main at an angle of less than 60°.
(2)(a) If the thickness of the main or branches of a single or multiple branch piece is less than given by the Equation(7/6),external reinforcement shall be provided.
(b)Such reinforcement may take the form of multiple radial plates of 'horse shoe' form or the form of collars or other reinforcement, approved by the Inspecting Authority or Chief Inspector as the case may be, applied to or around the junction between the branch and the main.
(3)(a)Thickness where no external reinforcement is provided; where more than one branch is attached to a pipe, the opening of each branch shall be projected perpendicularly on the axis of the main and the distance between each pair of these projection measured. If the distance so measured between two branches is less than the sum of their bores, the two branches are deemed to affect each other; if this distance is equal to or greater than the sum of their bores, the two branches are deemed not to affect each other and in calculating the reinforcement required, each branch is to be considered in turn together with all the branches by which it is affected.
(b)In case a branch not affected by any other branch, where no external reinforcement is to be applied to a branch piece the thickness of the branch shall be determined from Equation (7/6).
PD Equation (7/6)
tm = ---------------- + C
(2 SE + P) X
Where, tm = nominal thickness of the branch less the permissible negative tolerance,
P = Maximum allowable working pressure,
S = Maximum permissible stress values available in the governing codes of the
country of the material to which it belongs,
E = Efficiency factor given in regulation256.
X = 1 - B (1 - 0.7 sin y) Equation (7/7)
B = ratio of bore of branch to bore of main
y = angle between branch and main in degrees
D= outside Diameter
C = 0.75 mm
The values of tm derived from Equation (7/6) is the minimum thickness and further provision
shall be made for any minus tolerance.
No reinforcement is required if –
B is less than Y
-----------
Y + 90 Equation (7/8)
(c)In case a branch affected by one or more other branches (see Fig. 7/6), determine the 'X' values for each branch alone from equation (7/7). Let 'X' be the value for the branch under consideration and Xa, Xb, the value for the other branches.
Then X1 = 1 - C (1 - Xa)
X2 = 1 - C (1 - Xb)
Equation (7/9)
Where, C is a factor the value of which is to be taken from Table 7/6.
Table 7/6
| Serial No. | L ----------- d1+ d2 | C |
| (1) | (2) | (3) |
| 1. | 1 or greater | 0 |
| 2. | 0.9 | 0.10 |
| 3. | 0.8 | 0.34 |
| 4. | 0.7 | 0.66 |
| 5. | 0.6 | 0.80 |
| 6. | 0.5 | 0.90 |
| 7. | 0.4 | 0.94 |
| 8. | 0.3 | 0.97 |
| 9. | 0.2 | 0.98 |
| 10. | 0.1 | 0.99 |
| 11. | 0.0 | 1 |
Table structure read from the Gazette PDF, page 664. Verification status as for the text above.
Show original extracted text (diagnostic, not authoritative)
Serial No. L
----------- C
d1+ d2
(1) (2) (3)
1. 1 or greater 0
2. 0.9 0.10
3. 0.8 0.34
4. 0.7 0.66
5. 0.6 0.80
6. 0.5 0.90
7. 0.4 0.94
8. 0.3 0.97
9. 0.2 0.98
10. 0.1 0.99
11. 0.0 1(L = distance between projections of bores, d1 and d2)
Intermediate values by linear interpolation:
It is to be specially noted that a branch may form part of two distinct, multiple branches, when its thickness shall be the greater of the thickness calculated for it as a component of each multiple branch.
The thickness of each branch which is a component of a multiple branch shall be determined from Equation (7/10). Equation (7/6) shall not apply:
Pd 1 * tm = ----------------- x ----------- + C Equation (7/10) 2 (Se + P) X X1. X2
Where C = 0.75 mm.
*SHAPE OF PROFILE - Unless the weld is dressed flush, there shall be external weld reinforcement, preferably within the limits recommended in Table 7/7 below and this reinforcement shall be substantially symmetrical about the centre line of the joint and the shape of the reinforcement may vary according to the type of electrode or welding technique used and the welding position, but shell in all cases be of smooth contour, the profile running out smoothly into the pipe on each side without notching or reduction of thickness of the pipe at the edges of the weld.
Table 7/7: Amount of weld Reinforcement
| Serial No. | Pipe thickness | Recommended limits | ||
|---|---|---|---|---|
| Over | Upto and including | Minimum | Maximum | |
| mm. | mm. | mm. | mm. | |
| (1) | (2) | (3) | (4) | (5) |
| 1. | - | 6 | 1.6 | 5 |
| 2. | 6 mm | 13 | 1.6 | 5 |
| 3. | 13 mm | - | 1.6 | 6 |
Table structure read from the Gazette PDF, page 665. Verification status as for the text above.
Show original extracted text (diagnostic, not authoritative)
Serial No. Pipe thickness Recommended limits
(1) Over Upto and including Minimum Maximum
1. mm.
2. (2) mm. mm. mm.
3.
- (3) (4) (5)
6 mm
13 mm 6 1.6 5
13 1.6 5Original extracted text of the table above, continued (diagnostic)
- 1.6 6
(d)For mains (see Figs. 7/6, 7/7, 7/8 and 7/9), (i) the thickness of main carrying a single or a multiple branch shall be determined as for the single branch or one component of the multiple branch except that the symbols ‘D’ and ‘E’ shall apply to the main.
(ii)The thickness of a main carrying more than one branch, single or multiple, shall be the greatest of the thickness of the main calculated in connection with each branch separately.
(iii)The additional thickness of a main for branch reinforcement shall extend over the length covered by the branch and beyond it for a distance not less than the bore of the branch on each side.
Tables and formulae are shown in their extracted layout. Alignment, superscripts and subscripts may be lost. The Gazette page image is authoritative.
Figures cited in this regulation (4, exact crops of the Gazette)

View Gazette page 669 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 669 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 669 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)

View Gazette page 670 · figure catalogue
Reconstructed CAD: DXF · SVG · Preview (redrawn, checked against the print; technical review pending)
In short
Regulation 274 covers branches welded to pipes: when external reinforcement is needed, and how to calculate branch and main thickness for single and multiple branches.
Key points
- (1) Branches, bosses and drain pockets welded to pipes must meet regulations 148 to 152. Branches must not be welded to a main at an angle of less than 60°.
- (2) If the main or branch is thinner than Equation (7/6) requires, external reinforcement must be provided. This may be radial "horse shoe" plates, collars or other reinforcement approved by the Inspecting Authority or Chief Inspector.
- (3)(a) Branch interaction: project each branch opening onto the main axis. If the distance between two projections is less than the sum of their bores, they affect each other.
- (3)(b) Single branch: thickness by Equation (7/6), using factor X from Equation (7/7), which depends on the bore ratio B and the branch angle y. C = 0.75 mm. No reinforcement is needed if B is below the limit in Equation (7/8). Further allowance must be made for minus tolerance.
- (3)(c) Multiple branches: use Equation (7/9) with factor C from Table 7/6 (based on L divided by d1 + d2, with linear interpolation), then Equation (7/10). Equation (7/6) does not apply. A branch in two multiple-branch groups takes the greater thickness.
- Weld profile: unless dressed flush, external weld reinforcement within Table 7/7, symmetrical, smooth and without notching the pipe.
- (3)(d) Mains: calculated as for the branch, with D and E for the main. With several branches, take the greatest thickness. The extra thickness extends beyond the branch by at least the branch bore on each side.
Written by IBRsource editors · last edited 2026-11-20. Explanations simplify and are not a design method, testing procedure or authorisation. Requirements come from the complete regulations, the Gazette and approved documentation.
Comparison pending: the IBR 1950 text in force on 30 September 2026 is not yet established for this provision, so no change is claimed (how this works).
Orientation hints (unverified)
These candidates come from automated heading matching against DPIIT's scanned historical print edition of IBR 1950. That edition uses imperial units and riveted-construction provisions, so it is not the operative 2026 predecessor text. Regulation numbers alone never prove equivalence.
No candidate heading found in the historical print edition.
Images of the official Gazette pages that contain this regulation. Click to zoom. Compare word by word before relying on the extracted text.




Indian Boiler Regulations, 2026, reg. 274, Regulation 274, Gazette of India, Extraordinary, Part III—Section 4, No. 596, 1 October 2026, printed p.662–665. https://egazette.gov.in/WriteReadData/2026/276813.pdf (text consulted via IBRsource, 2026-11-23).
The citation refers to the government publication. Cite the Gazette, not this website.